Series: Zelio / Harmony SSM1 Single-phase Solid State Relay|Status: Discontinued
Model Code Explanation
SSM1: DIN rail-mounted solid state relay of SSM1 series
A: AC output
1: Single phase
20: Rated load current 20A
BD: DC control (4-32VDC), Zero Voltage Switching (ZVS)
-📌 Core Specifications
| Item | Parameter |
| Control Input | DC 4~32 V, Turn-on ≥4V, Turn-off ≤1V; Input current 8~12mA |
| Load Output | AC 24~280 V, single phase, 1NO, SCR output, zero voltage switching |
| Rated Load Current | 20A (Derating required at elevated ambient temperature) |
| Mounting | Symmetrical DIN rail mounting |
| Overall Dimensions | 22.5 × 98.8 × 97.7 mm|Weight: 0.28 kg |
| Terminals | Screw terminals, wire gauge 0.2~5.3 mm² (AWG24~AWG10) |
| Torque | Input: 0.6–0.7 N·m; Output: 1.36–1.7 N·m |
| Status Indicator | Green LED, lights up when input is energized |
| On-state Voltage Drop | ≤1.6V |
| Off-state Leakage Current | ≤10mA |
| Surge Current | ≤250A / 16.6ms |
| Operating Temperature | -40℃ ~ +80℃; Storage: -40~125℃ |
| Dielectric Withstand Voltage (Input to Output) | 4kV AC |
| Protection Class | IP20 |
| Certifications | CE, UL, CSA, EAC, RoHS compliant |
📎 Features & Applications
Zero voltage switching: Turns on at AC zero crossing to suppress EMI, ideal for resistive loads (heating elements, incandescent lamps)
No mechanical contacts, no arcing, long service life, suitable for high-frequency switching and vibration-prone environments
Not recommended for heavy inductive loads or transformers (snubber circuit required)
|Typical Applications|Temperature-controlled heating, lighting control, ovens, HVAC heating circuits|
Replacement Notes
There is no direct pin-to-pin replacement model from the original manufacturer. Cross-reference within the same series:
SSM1A120BDR: Same electrical rating, random switching (non-zero-crossing). Pay attention to the switching mode difference.
Alternatives: New SSR models in SSM1 series or other brands of 20A zero-crossing SSR (e.g. Omron, Crydom)
Key selection checklist: Control voltage, output voltage, switching mode, thermal derating curve
- Input side: + / connect to PLC or digital DC signal (4-32VDC)
- Output side: Series-connected in AC load circuit, phase-insensitive for AC
- Heat dissipation must be guaranteed; leave gaps when densely mounted, derate current at high temperature, fit a suitable fast fuse at upstream
Schneider SSM1A120BD Full Original Datasheet (Zelio / Harmony SSM1 Single-phase Solid State Relay)
1. Model Coding Explanation
SSM1 A 1 20 BD
SSM1: Modular DIN rail solid state relay of SSM1 series
A: AC output type
1: Single phase
20: Rated current 20A
BD: DC control 4-32V DC, Zero Voltage Switching
2. Main Specification Table
| Parameter Item | Value |
| Product Type | Single-phase solid state relay, SCR output, 1NO normally open |
| Control Input Voltage Uc | 4~32 V DC; Turn-on ≥4VDC, Turn-off ≤1VDC |
| Input Current | 8~12 mA |
| Load Output Voltage | 24~280 V AC |
| Rated Load Current In | 20 A (Derating required at elevated ambient temperature) |
| Minimum Load Current | 0.15 A |
| Switching Mode | Zero voltage switching (ZVS) |
| On-state Voltage Drop | ≤1.6 V |
| Off-state Leakage Current | ≤10 mA |
| Off-state dV/dt | 500 V/μs |
| Transient Withstand Voltage | 600 V |
| Surge Current | ≤250 A @16.6 ms |
| I²t (for fuse selection) | 260 A²·s @8.3 ms |
| Response Time | Turn-on: 0.5 power frequency cycle; Turn-off: 0.5 power frequency cycle |
| Status Indicator | Green LED, lights up when input is powered |
3. Terminal & Mechanical Specifications
| Item | Parameter |
| Mounting | Symmetrical DIN rail snap mounting |
| Dimensions (W×H×D) | 22.5 × 98.8 × 97.7 mm |
| Net Weight | 0.28 kg |
| Terminal Type | Screw terminals |
| Suitable Wire Gauge | 0.2~5.3 mm² (AWG24~AWG10) for both input and output |
| Tightening Torque | Input terminal: 0.6~0.7 N·mOutput terminal: 1.36~1.7 N·m |
| Parasitic Capacitance between Input & Output | ≤8 pF |
4. Insulation, Protection & Environmental Ratings
| Item | Parameter |
| Input ↔ Output Dielectric Withstand Voltage | 4 kV AC |
| Input/Output ↔ Housing Withstand Voltage | 4 kV AC |
| Insulation Resistance | ≥1000 MΩ @500 V DC |
| Protection Class | IP20 (for cabinet internal use) |
| Operating Ambient Temperature | -40 ℃ ~ +80 ℃ |
| Storage Temperature | -40 ℃ ~ +125 ℃ |
| Pollution Degree | 2 |
| Overvoltage Category | III |
| Certifications | CE, UL, CSA, EAC, RoHS, Green Premium |
| Applicable Standards | UL508, CSA C22.2 No.14, IEC60950-1 |
5. Derating Curve Guidance (Critical)
25℃ ambient: Full rating 20A
Linear current derating when ambient temperature>40℃; allowable current drops significantly at 80℃
Additional derating is required for densely side-by-side installation due to mutual thermal interference
✅ Recommended: For resistive heating loads, select at 70% of rated current; avoid continuous full-load operation
6. Terminal Definition
- Control Input: DC+, DCconnect to PLC / temperature controller transistor output (4-32VDC, polarity-sensitive)
- Load Output: Series-connected in 220VAC circuit, phase independent; one end to live line L, one end to load
- Fast fuse is recommended in series with load side; RC snubber or varistor is mandatory for inductive loads (transformers, solenoid valves)
7. ey Variant Comparison by Suffix
SSM1A120BD: Zero-cross switching ZVS, for heating and incandescent lamps, low EMI
SSM1A120BDR: Random switching, for instant turn-on or phase control applications. Not directly interchangeable
8. Application Limitations
✅ Suitable for: Resistive heating elements, infrared lamps, constant-temperature ovens, HVAC heating, low-interference lighting control
❌ Not recommended for: Heavy inductive loads, direct motor start-stop; snubber circuit is required
Application Cases of SSM1A120BD (Zero-cross SSR, 4-32VDC control, 20A, 24-280VAC for resistive loads preferred)
Core advantages: Zero-cross turn-on, low EMI, contactless, vibration resistant, compact DIN rail mounting, direct driving by PLC DC points. For resistive loads; snubber circuit required for inductive loads
Case 1: Barrel Heating Control for Injection Molding Machines (Most Common)
Load: Single-section 220V heating band (resistive, ≤4kW, 20A class)
Control architecture: PLC (4-24VDC output) → SSM1A120BD → heating band; PID output from temperature controller drives SSR
Selection logic: Zero-cross switching reduces grid harmonic distortion and inrush current of heating bands; contactless design avoids burning contacts under frequent switching
Auxiliary components: Fast fuse for each circuit; reserve heat dissipation gap for multi-section heating installed side by side and derate current at high temperature; thermocouple closed-loop temperature control
Risk note: Fuse provides protection against leakage and short circuit of heating bands; do not drive barrel cooling fans (inductive) directly
Case 2: HVAC / Air Duct Electric Heater & Fresh Air Preheating Module
Load: Single-phase duct heating tubes, PTC heating (resistive)
Control: DDC / PLC digital output for constant temperature start-stop and anti-freeze heating in winter
Highlights: Silent and spark-free, suitable for dense installation in BMS control cabinets; wide temperature range -40~80℃, available for cabinet installation in machine rooms or outdoor environments
Caution: Air duct heater must interlock with air differential pressure switch to cut off SSR and prevent dry heating when airflow is lost
Case 3: Textile Machinery — Stenter, Oven & Infrared Lamp Heating
Load: Infrared heating lamps, heating tubes in setting zone
Working conditions: Long-period cyclic switching, heavy equipment vibration, lint and dust environment
Advantages: No mechanical contacts, vibration resistance, far longer service life than AC contactors; zero-cross triggering reduces lamp inrush and extends lamp lifespan
Cabinet requirement: Dustproof control cabinet; avoid dust accumulation blocking SSR heat sink fins
Case 4: Heat Sealing, Hot Knife & Hot Stamping Heating for Packaging Machinery
Load: Heat sealing strip, hot stamping heating plate (resistive)
Working conditions: High-frequency short-cycle switching; conventional relays tend to stick under fast cycles
Solution: PLC output directly drives SSM1A120BD with temperature controller for stable sealing temperature
Comparison: Electromagnetic relays wear out after thousands of operations; SSR supports millions of switching cycles
Case 5: Food Drying, Constant Temperature Ovens & Laboratory Incubators
Load: Stainless steel heating tubes, 220V single-phase resistive load
Control: Temperature controller + SSR for ON/OFF or PID cycle power regulation (not phase angle regulation; zero-cross SSR is suitable for burst firing)
Scenarios: Food, herbal and material drying, low interference requirement to protect temperature sensors and weighing instruments
Case 6: Lighting Load (Halogen Lamps, Incandescent Lamps; NOT for LED Drivers)
Load: Halogen tubes, traditional incandescent lamps (resistive)
Description: Zero-cross turn-on suppresses inrush surge and extends lamp life; not suitable for LED power supplies or electronic ballasts-(internal capacitance causes large surge and may damage SSR)
Restriction: Special dimming modules are recommended for LED lamps instead of direct SSR switching
⚠️ Scenarios Not Recommended for Direct Use (Common On-site Failures)
- Single-phase motors, water pumps, solenoid valves (inductive loads): RC snubber + varistor must be fitted, otherwise false triggering or breakdown may occur
- Direct primary switching of transformers: High magnetizing inrush current easily damages this 20A SSR
- High-frequency voltage regulation and phase chopping: This model is ZVS zero-cross type, not random type (SSM1A120BDR for random triggering); cannot perform phase angle dimming
📌 General On-site Wiring Framework (Applicable to All Cases)
Input: DC+, DCconnect to PLC / temperature controller transistor output (4-32VDC, polarity-sensitive)
Output: Series-connected between 220VAC live wire and load, AC phase independent
Protection: Fast fuse (gG/aM) in series on output side; derate current when cabinet temperature>40℃
Diagnosis: Green LED lights up when input is energized for easy commissioning and troubleshooting
Complete List of Schneider Harmony SSM1 Single-phase Solid State Relays (DIN Rail Type)
Coding Rule:
SSM1 + Output type(A=AC / D=DC) + Output voltage code + 1(Single phase) + Current + Control code + R (R=Random switching; No suffix = Zero voltage switching)
Control Code: BD=4-32VDC; B7=18-36VAC; F7=90-140VAC; P7=200-265VAC; M7=90-280VAC
Remark: The whole SSM1 series is discontinued by original manufacturer
1. AC Output · 24~280VAC (Code 1, Most Common; SSM1A120BD belongs to this group)
| Model | Rated Current | Control Input | Switching Mode |
| SSM1A16BD | 6A | 4–32VDC | Zero-cross |
| SSM1A16BDR | 6A | 4–32VDC | Random |
| SSM1A16B7 | 6A | 18–36VAC | Zero-cross |
| SSM1A16B7R | 6A | 18–36VAC | Random |
| SSM1A16F7 | 6A | 90–140VAC | Zero-cross |
| SSM1A16F7R | 6A | 90–140VAC | Random |
| SSM1A16P7 | 6A | 200–265VAC | Zero-cross |
| SSM1A112BD | 12A | 4–32VDC | Zero-cross |
| SSM1A112BDR | 12A | 4–32VDC | Random |
| SSM1A112B7 | 12A | 18–36VAC | Zero-cross |
| SSM1A112B7R | 12A | 18–36VAC | Random |
| SSM1A112F7 | 12A | 90–140VAC | Zero-cross |
| SSM1A112F7R | 12A | 90–140VAC | Random |
| SSM1A112P7 | 12A | 200–265VAC | Zero-cross |
| SSM1A120BD | 20A | 4–32VDC | Zero-cross |
| SSM1A120BDR | 20A | 4–32VDC | Random |
| SSM1A120M7 | 20A | 90–280VAC | Zero-cross |
| SSM1A130BD | 30A | 4–32VDC | Zero-cross |
| SSM1A130BDR | 30A | 4–32VDC | Random |
| SSM1A130M7 | 30A | 90–280VAC | Zero-cross |
| SSM1A145BD | 45A | 3–32VDC | Zero-cross |
2. AC Output · 48~600/660VAC (Code 3/4, High Voltage Version)
| Model | Rated Current | Control Input | Switching Mode |
| SSM1A36BD | 6A | 4–32VDC | Zero-cross |
| SSM1A36BDR | 6A | 4–32VDC | Random |
| SSM1A36B7 | 6A | 18–36VAC | Zero-cross |
| SSM1A312BD | 12A | 4–32VDC | Zero-cross |
| SSM1A312BDR | 12A | 4–32VDC | Random |
| SSM1A312B7 | 12A | 18–36VAC | Zero-cross |
| SSM1A312F7 | 12A | 90–140VAC | Zero-cross |
| SSM1A430BD | 30A | 4–32VDC | Zero-cross |
| SSM1A430M7 | 30A | 90–280VAC | Zero-cross |
| SSM1A445BD | 45A | 3–32VDC | Zero-cross |
| SSM1A445F7 | 45A | 90–140VAC | Zero-cross |
| SSM1A455BD | 55A | 3–32VDC | Zero-cross |
| SSM1A455F7 | 55A | 90–140VAC | Zero-cross |
3. DC Output SSM1D (MOSFET DC Switch for DC Loads)
| Model | Rated Current | Control Input | Output Voltage |
| SSM1D212BD | 12A | 4–32VDC | 1–60VDC |
| SSM1D36BD | 6A | 4–32VDC | 1–100VDC |
| SSM1D312BD | 12A | 4–32VDC | 1–100VDC |
4. Additional Selection Notes (Avoid Pitfalls)
- Suffix R = Random switching: Suitable for phase angle regulation and inductive loads; No suffix = ZVS zero-cross, preferred for heating and resistive loads (SSM1A120BD)
- Width: 6A/12A →12/18mm; 20A/30A →22.5mm; 45A/55A →45mm
- All variants are single-channel single-phase 1NO normally open. SSM2 series is dual-channel single-phase and excluded from this single-phase SSR list
- Replacement strategy for discontinued parts: Prioritize verification of four parameters: control voltage, output voltage, switching mode, current rating. Alternatives include domestic SSR, Crydom and Omron equivalents
Contactor,circuit breaker,sensor,Encoder,PLC,Converter





















NH42-63-318x560.png)