Modicon TM5 24VDC I/O Power Distribution Module (PDM)
It belongs to Schneider TM5 distributed remote I/O series, compatible with M258 / LMC058 controllers. It supplies power to the TM5 backplane bus, and provides segmented 24V field power for I/O modules. It isolates different I/O power domains and expands backplane power capacity.
✅ Core Functions
- Power supply for TM5 internal power bus: Max. output 1136mA (≤55°C); 740mA (55~60°C)
- I/O field power segment: 24VDC, max. 10A, to supply field side of DI/DO/AI/AO I/O modules on the right side of this base
- Segmented power isolation: A full TM5 station can be divided into multiple independent 24V I/O power domains. Short-circuit on one segment will not shut down the entire bus.
- Diagnostic status bits for bus: Bus OK / power warning, I/O data valid, readable via PLC program.
📋 Electrical Specifications
Rated input voltage: 24VDC, operating range 20.4 ~ 28.8VDC
Max current of I/O power segment: 10A. No built-in fuse; external Type T slow-blow fuse (max 10A/250V) is mandatory.
Reverse polarity protection: Not available. Never reverse +24V and 0V wiring.
Isolation: 500Vac RMS isolation between TM5 bus circuit and I/O power segment
Max power dissipation: 1.91W, module self-consumption 25mA@24V
Protection class: IP20 (cabinet mounting only)
Dimensions: W12.5mm × H99mm × D75mm, weight approx. 30g
Module ID code: 7104 (decimal)
Ambient operating temperature: -10 ~ +55°C (full current); derating from 55~60°C
🧩 Hardware & Configuration
Compatible bus bases: TM5ACBM01R / TM5ACBM05R; Terminal block TM5ACTB12PS
Mounting: DIN rail, slotted on TM5 bus base, mixed installation with TM5 I/O modules
Software: Machine Expert (SoMachine). Module status word is available for reading bus power warning and network status.
⚠️ TM5SPS2 vs TM5SPS2F (Key Selection Guide)
TM5SPS2: External fuse required, max 10A for I/O segment
TM5SPS2F: Built-in 6.3A fuse, I/O segment limited to 6.3A, no external fuse needed
📌 Typical Applications
Packaging machinery, material handling, machine tool distributed remote I/O islands. Deploy TM5SPS2 for backplane power shortage or segmented protection for sensor/actuator power.
🛠️ Troubleshooting Guide
- Bus warning bit triggered: Check 24V voltage drop, blown fuse, overload or short circuit in I/O segment
- Module no communication: Verify TM5 bus connector, base address and module ID recognition
- No field power to I/O modules: Check external 24V input at PS2 terminals and external fuse status
Note: All 0V connections must be tied together and connected to Functional Earth (FE) to meet EMC requirements. Only PELV safety extra-low voltage power is permitted; mains AC voltage cannot be directly connected.
📎 Alternatives & Series Comparison
TM5SPS1: I/O power segmentation only, no TM5 backplane bus power supply
TM5SPS2F: Same function with built-in 6.3A fuse
TM5SBER2: TM5 remote I/O receiver module with integrated bus power supply
Schneider TM5SPS2 Wiring Instructions
TM5SPS2 must be used with TM5ACTB12PS (12-pin spring terminal block). The terminal block snaps under the TM5ACBMxx bus base, and the electronic module plugs onto the base. Terminal numbers are printed on the terminal block.
- Terminal Definition (12-pin TM5ACTB12PS)
| Terminal No. | Signal Name | Description | Fuse Requirement |
| 1 | PS1 +24V | TM5 backplane bus positive supply (feeds internal TM5 bus) | Series Type T slow-blow 1A fuse (250V) upstream |
| 2 | PS1 0V | TM5 backplane bus negative | Common ground with PS1 power supply |
| 3 | NC | Not connected, no wiring allowed | — |
| 4 | NC | Not connected, no wiring allowed | — |
| 5 | PS2 +24V | I/O field power segment positive (supplies all DI/DO/AI/AO I/O modules to the right of this module) | Series Type T slow-blow fuse max.10A (250V) upstream |
| 6 | PS2 0V | I/O field power segment negative | Common ground with PS2 power supply |
| 7 | NC | Not connected | — |
| 8 | NC | Not connected | — |
| 9 | NC | Not connected | — |
| 10 | NC | Not connected | — |
| 11 | NC | Not connected | — |
| 12 | NC | Not connected | — |
✅ Quick distinction between two power rails:
PS1 (Pin1/2) = TM5 backplane bus power; PS2 (Pin5/6) = I/O field load power. Two separate 24V supplies can be used for isolated power segmentation.
- Two Typical Wiring Schemes
Scheme 1: Single 24V Power Supply (Standard)
+24V from power supply is split into two branches: one through 1A T-fuse → Terminal 1; another through 10A T-fuse → Terminal 5
Power 0V: Tie Terminal 2 and Terminal 6 together, connect to power supply 0V. Link 0V to Functional Earth (FE) for EMC compliance.
Notes: Bus power and I/O power share the same source. Short circuit on I/O side will not directly damage the bus, but the power supply capacity must cover both backplane and I/O loads.
Scheme 2: Two Independent 24V Supplies (Isolated Segmentation, Recommended)
PS1 (Pin1/2): Independent 24V supply with 1A slow-blow fuse, dedicated for TM5 backplane bus
PS2 (Pin5/6): Separate 24V supply with 10A slow-blow fuse for sensors and actuators of right-side I/O modules
The 0V of the two power supplies must be interconnected and connected to FE functional earth
Advantage: Short circuit in I/O circuit will blow only the PS2 fuse, while TM5 backplane bus remains online. Suitable for high-reliability machines.
- Wire Specification (Spring Terminal)
Wire gauge range: 0.08 ~ 2.5 mm², recommended:
Main power cable: 0.75~1.5 mm²
Low-current signal: 0.5 mm²
Wire temperature rating ≥80°C, stripping length approx.8mm
- LED Indicator Definition (On Module Body)
E Fault LED:
Blinking: Low bus voltage / insufficient PS1 voltage / bus overload. Common field mistake: only PS2 (Pin5/6) wired while PS1 (Pin1/2) is missing → E LED blinks.
Steady ON: PS2 I/O power segment fault, overload or short circuit
RUN LED: Steady ON: Module healthy; OFF: No module power or bus fault
- Critical Safety & Wiring Prohibitions
- ❌ No built-in fuse! External Type T slow-blow fuse is mandatory for PS2 (max 10A). PS1 requires 1A slow-blow fuse. Module damage may occur without proper fusing in short-circuit events.
- ❌ No reverse polarity protection. Never swap +24V and 0V; reversed polarity will permanently damage TM5SPS2.
- ❌ Only PELV/SELV safety isolated 24VDC power supplies are allowed. Mains AC cannot be connected directly.
- ❌ Do not wire NC unused terminals (3,4,7~12) to prevent accidental short circuits.
- ✅ EMC mandatory requirement: All 0V tied together and connected to FE functional earth; FE shall not be confused with protective earth PE.
- ✅ Current derating: ≤55°C ambient for full backplane 1136mA; reduced to 740mA for 55~60°C.
- Pre-power-on Wiring Check List
- Confirm PS1 (Pin1,2) 24V is connected; do not only wire PS2 (Pin5,6)
- Verify Type T slow-blow fuses with correct ratings
- All 0V commoned and bonded to FE
- Terminals fully clamped, no loose connection or exposed copper strands causing short
- Measure before power-up with multimeter: 24VDC between pin1-2; 24VDC between pin5-6, correct polarity
- Configuration Notes (Machine Expert / SoMachine)
When the module is inserted into the base, software recognizes Module ID:7104. Status words available:
DcOk: Boolean flag for valid bus power
Bus power warning bit: Low voltage pre-alarm, usable for PLC alarm programming
Schneider Modicon TM5 Full Series Model List & Bill of Materials
Compatible Controllers: M258 / LMC058 / LMC078; Programming Software: Machine Expert (formerly SoMachine)
System architecture: Bus base + electronic module + removable spring terminal block. SPS power distribution modules are core components for power segmentation.
- Power Distribution Modules (PDM, same series as TM5SPS2)
| Model | Description | Key Features | Compatible Base | Compatible Terminal Block |
| TM5SPS1 | I/O Power Segmentation Module | Supplies 24V field power only to right-side I/O modules. No TM5 backplane bus power supply. No built-in fuse, max 10A | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS1F | I/O Power Segmentation with Built-in Fuse | I/O segment power only, built-in 6.3A fuse, no backplane power supply | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS2 | Backplane Bus + I/O Dual Power Supply | Powers TM5 backplane bus and right-side I/O field power. No built-in fuse, I/O segment max 10A | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS2F | Dual Power Module with Fuse | Backplane bus + I/O segment power, replaceable built-in 6.3A fuse | TM5ACBM01R / 05R | TM5ACTB12PS |
| TM5SPS3 | IPDM Interface Power Module | Dedicated power module for Sercos III bus interface | TM5ACBN1 | TM5ACTB12PS |
- Bus Transceiver Modules (Remote Station Core)
| Model | Description | Application | Compatible Terminal Block |
| TM5SBET1 | TM5 Bus Transmitter | Controller-side bus transmitter, local start point | TM5ACTB12PS |
| TM5SBET7 | High-speed Bus Transmitter | Long-distance high-speed transmission | TM5ACTB12PS |
| TM5SBER2 | TM5 Bus Receiver | Remote I/O island receiver with integrated backplane + I/O power supply | TM5ACTB12PS |
- Bus Bases (Mechanical Base, modules plug onto bases)
Two base types: White straight-through bases, Grey isolated bases (for SPS power/transceiver modules)
|TM5ACBM11|White Bus Base|24V I/O power pass-through, no address rotary switch|Standard DI/DO/AI/AO modules|
|TM5ACBM15|White Bus Base|Power pass-through, with rotary address switch|Standard DI/DO/AI/AO modules|
|TM5ACBM01R|Grey Isolated Base|Isolates I/O power on left side, no address switch|SPS power modules, SBER2 receiver|
|TM5ACBM05R|Grey Isolated Base|Left I/O power isolation, with address rotary switch|SPS power modules, SBER2 receiver|
|TM5ACBN1|Sercos Dedicated Base|Sercos III bus special base, used with TM5SPS3|TM5NS31, TM5SPS3|
- Removable Spring Terminal Blocks (Must be ordered separately)
| Model | Pins | Color | Applicable Module Types |
| TM5ACTB06 | 6-pin | White | Small channel DI/DO/AI modules |
| TM5ACTB12 | 12-pin | White | General-purpose I/O modules |
| TM5ACTB12PS | 12-pin | Grey | SPS power modules, SBER2 receiver |
| TM5ACTB16 | 16-pin | White | High-density I/O |
| TM5ACTB32 | 32-pin | White | High-density I/O |
- Digital Input Modules DI
| Model | Channels | Specifications |
| TM5SDI2D | 2DI | 24VDC sink, 3-wire |
| TM5SDI4D | 4DI | 24VDC sink, 3-wire |
| TM5SDI6D | 6DI | 24VDC sink, 2-wire |
| TM5SDI12D | 12DI | 24VDC sink, 1-wire |
| TM5SDI16D | 16DI | 24VDC sink, high density |
| TM5SDI2DF | 2DI | 24VDC high-current input type |
| TM5SDI2A | 2DI | AC100~240V AC input |
| TM5SDI6U | 6DI | Universal input |
- Digital Output Modules DO
| Model | Channels | Specifications |
| TM5SDO2T | 2DO | 24V transistor output |
| TM5SDO4T | 4DO | 24V transistor |
| TM5SDO4TA | 4DO | Enhanced transistor |
| TM5SDO6T | 6DO | 24V transistor |
| TM5SDO8TA | 8DO | Enhanced transistor |
| TM5SDO12T | 12DO | Transistor |
| TM5SDO16T | 16DO | High-density transistor |
| TM5SDO2R / 4R | 2/4DO | Relay dry contact output |
| TM5SDO2S | 2DO | Thyristor AC output |
- Mixed I/O Modules DI+DO
| Model | Channels | Description |
| TM5SDM8DTS | 8DI+4DO | 24V DC |
| TM5SDM12DT | 8DI+4DO | 12-point mixed I/O |
| TM5SMM6D2L | 6DI+2DO | Economical mixed module |
- Analog Modules AI / AO
| Model | Channels | Signal Type |
| TM5SAI2L | 2AI | 4~20mA current |
| TM5SAI4L | 4AI | 4~20mA |
| TM5SAI8L | 8AI | 4~20mA |
| TM5SAI2V | 2AI | ±10V voltage |
| TM5SAO2L | 2AO | 4~20mA output |
| TM5SAO4L | 4AO | 4~20mA |
| TM5SAO2V | 2AO | ±10V voltage output |
- High-speed Counter / Encoder Modules (SE Series)
| Model | Channels | Type |
| TM5SE1IC02505 | 1 Channel | 5V differential encoder |
| TM5SE1IC01024 | 1 Channel | 24V single-ended encoder |
| TM5SE2IC01024 | 2 Channel | 24V single-ended encoder |
| TM5SE1SC10005 | 1 Channel | 5V single-ended encoder |
- Communication Interface Modules
| Model | Interface | Protocol |
| TM5PCRS2 | RS232 | Modbus RTU |
| TM5PCRS4 | RS485 | Modbus RTU |
| TM5PCDPS | DP Slave | Profibus-DP |
| TM5NCO1 | CANopen Slave | CANopen |
| TM5NEIP1 | EtherNet/IP | EtherNet/IP Remote I/O |
| TM5NS31 | Sercos III | Sercos III motion bus |
- Accessories
- TM5SD000: Dummy filler module for reserved slots
- TM5SPDG12F / TM5SPDD12F: 12-channel power distribution terminal module
- TM5SPDG5D4F: Multi-channel combined power distribution module
✅ TM5SPS2 Minimum Complete BOM for Purchase
- TM5SPS2 Power Distribution Electronic Module
- TM5ACBM01R Grey Isolated Base (no address) / TM5ACBM05R (with address rotary switch), select one
- TM5ACTB12PS Grey 12-pin spring terminal block (mandatory, separate order item)
Assembly rule: Insert SPS module into grey isolated base TM5ACBM01R/05R; snap TM5ACTB12PS terminal block underneath the base.
✅ Quick Selection Rules
- Standard DI/DO/AI/AO → White base TM5ACBM11/15 + white terminal block ACTB06/12
- SPS power segmentation, SBER2 receiver module → Grey isolated base + Grey ACTB12PS terminal block
- Insufficient backplane power, need segment protection → TM5SPS2; prefer built-in fuse for simpler wiring → TM5SPS2F
- Sensor power segmentation only, no requirement to boost backplane power → TM5SPS1 / TM5SPS1F