Order No.: 1SFA898219R7000
Series: PSTX Intelligent 3-phase SCR Soft Starter (with built-in bypass)
Model Code Explanation
PSTX: PSTX intelligent soft starter series (3-phase control, built-in bypass)
840: Rated operational current 840A (In-Line connection)
690: Maximum main circuit voltage 690V AC
70: Control power supply version 100–250V AC (50/60Hz)
📋 Core Electrical Specifications
| Item | Model & rating | Remarks |
| Soft starter rated current | 840A | In-Line |
| Recommended ABB MCCB | T7S 1000 PR231/P-LI 3P | In=1000A, LI trip (long delay + instantaneous short circuit); rated for 690V |
| Trip setting | Long delay: 1.0×In; Instantaneous short circuit: 8~10×In | Do NOT use long delay for motor overload protection; motor overload is handled by PSTX internal electronic protection. Instantaneous threshold must avoid startup inrush. |
| Breaking capacity | S=50kA@400V | Upgrade to T7H / T7V (70/100kA) if short-circuit current at switchgear inlet is high |
| Application | Pumps, fans, general conveyors, most industrial projects | Easy commissioning, provides isolation & disconnection, standard cabinet solution |
⚙️ Standard Feature List
- Starting modes: Voltage ramp, torque ramp, current limiting, kickstart + ramp
- Stopping modes: Soft stop, pump stop (water hammer protection), dynamic braking, static braking
- Built-in bypass contactor: Bypasses SCRs at full speed to reduce heat and power loss; no external bypass cabinet required
- Protection functions: Motor overload, phase loss, phase sequence, overvoltage/undervoltage, earth fault, PT100 temperature sensing, SCR fault, overheat, locked rotor
- Special application functions: Fire mode (protections suppressed), jog mode, pipe cleaning, motor preheating, limp mode (degraded start with single SCR fault), sequential starting
- Communication: Standard Modbus RTU; optional Anybus modules for Profinet, EtherNet/IP, Modbus TCP, Profibus-DP
- IO & outputs: 3 programmable digital inputs, relay outputs (run / torque reached / event), 1 analog output (current / voltage / power factor selectable)
- HMI: Detachable graphic LCD panel, 17-language support; panel can be remotely mounted
🧰 Wiring Methods
In-Line: Standard connection, soft starter in series with main circuit, rated current 840A; most common selection
Inside-Delta: Installed in the branches of motor delta windings; same unit can drive larger motors. Note: Branch current = line current ÷ √3
📌 Selection Reference & Replacements
Adjacent models in the same series: PSTX720-690-70 (720A / 400V=400kW), PSTX1050-690-70 (1050A / 400V=560kW)
Legacy replacement: PST, PSS, PSR series are phased out; PSTX is the main upgraded model for new projects
Competitor equivalents: Schneider ATS480, Allen-Bradley SMC Flex / SMC-50, Siemens 3RW55
📎 Suitable Loads
Water pumps, fans, compressors, crushers, conveyors and large motors. Widely used in water supply, wastewater, HVAC, mining and cement industries. Fire pump applications are supported natively (built-in fire mode).
⚠️ Important Notes
- Derating calculation is mandatory for ambient temperature up to 60℃, altitude>1000m or frequent starting (>3 starts/hour)
- Built-in bypass version does not need an extra bypass contactor, but short-circuit protection (circuit breaker / fuse) on the incoming side is mandatory
- The panel can be removed and mounted separately on the cabinet door for convenient commissioning and maintenance
Control Modes of Soft Starters
Two categories: Command source control modes (3 standard modes for PSTX) and starting curve control modes (SCR voltage regulation logic)
- Command Source Control Modes (3 standard for ABB PSTX840-690-70, only one active at a time)
- Local HMI panel control
Detachable LCD panel mounted on the unit; can be removed for door mounting. Start, stop, reset and parameter modification via panel. Highest priority, overrides terminal and communication commands.
- Hardwired DI terminal control (dry contact, factory default)
2-wire (level): Continuous closed RUN contact = run; open = stop. Suitable for PLC dry contacts or remote pushbuttons.
3-wire (pulse): Normally closed stop, momentary pulse start, consistent with traditional relay circuits.
PSTX has dedicated start/stop terminals plus 3 programmable DIs for fault reset, mode switching, fire mode activation, etc.
Switch via Local/Remote button on panel or parameter setting. Emergency stop terminals are independent and not affected by control source selection.
- Fieldbus communication control (PLC / DCS / SCADA)
Standard: Modbus RTU (RS485)
Optional Anybus modules: Profinet, EtherNet/IP, Modbus TCP, Profibus-DP
Functions: Remote start/stop, fault reset, read current/voltage/status, online parameter editing
- Starting Curve Control Modes (voltage regulation strategies supported by PSTX)
- Voltage ramp start (most common: fans, general conveyors)
Starts from initial voltage and rises linearly to full voltage over set time; gentle impact, current rises naturally with load.
- Current limiting start (pumps, compressors, weak power grids)
Starting current is clamped at a preset multiplier (typically 3~4×In) to avoid high inrush for grids with limited capacity.
- Torque ramp start (heavy-duty loads: crushers, high static friction loads)
Directly controls output torque instead of only voltage; smooth torque during startup, reduces slipping risk.
- Kickstart + ramp
Short high-voltage pulse at startup to overcome static friction (viscous materials, stuck loads), then automatically switches to ramp. Not recommended for pumps.
- Jog mode
Low-voltage inching for rotation test and maintenance positioning.
III. Stopping Modes
Free stop: Output cut off directly, motor coasts by inertia (default)
Soft stop (voltage ramp down): Preferred for pumps to suppress water hammer
Static braking (DC braking): Fast stop for fans and high-inertia loads
Pump cleaning mode: Intermittent start-stop for pipeline flushing
- Quick Comparison
Terminal control: Stable & simple, widely used for local cabinet pushbuttons and standard PLC digital outputs
Communication control: Centralised monitoring, sequential start of multiple units, SCADA supervision for pump stations and factory DCS
Panel control: Commissioning, maintenance and standalone local operation
Incoming Protection Selection Table for PSTX840-690-70 (840A In-Line)
Preconditions: In-Line connection, 400V system, 40℃ ambient, normal starting. The soft starter provides built-in motor overload protection; upstream devices only perform short-circuit protection.
Coordination definitions:
Type 1 coordination: MCCB / gG general fuse. SCRs of soft starter are likely damaged after short circuit; spare replacement required. Low cost, preferred for general projects.
Type 2 coordination: Semiconductor high-speed fuse. Soft starter unit can remain usable after short circuit (only the fuse blows). For critical loads where downtime is restricted, higher cost.
- MCCB Solution (ABB recommended, Type1)
| Item | Specification | Remarks |
| Fuse rating | 1000A aM/gG 690V | aM motor fuse preferred over gG |
| Fuse switch disconnector | OS800 fuse switch | ABB OS series |
| Features | Low cost; SCRs may fail after short circuit, soft starter inspection required after fault | General distribution, non-critical loads |
Same T7S1000 can be used for 690V systems, confirm MCCB Ue≥690V. This table is invalid for Inside-Delta connection, branch current recalculation required.
- Fuse Solutions (2 options: general gG / semiconductor fast fuse)
Option A: gG general fuse (Type1, economy)
| Item | Specification | Remarks |
| Fuse rating | 1000A aM/gG 690V | aM motor fuse preferred over gG |
| Fuse switch disconnector | OS800 fuse switch | ABB OS series |
| Features | Low cost; SCRs may fail after short circuit, soft starter inspection required after fault | General distribution, non-critical loads |
Option B: Semiconductor high-speed fuse (Type2, SCR protection for critical loads)
| Item | Recommended model | Remarks |
| Bussmann high-speed fuse | 170M6814 | 690V, semiconductor grade for SCR protection; listed in PSTX datasheet |
| Fuse base | OS800D03P | Matching fuse disconnector |
| Features | Fuse blows first under short circuit to protect SCRs; only fuse replacement needed, soft starter can often resume service | Fire pumps, critical compressors, main fans with minimum downtime requirement |
- Selection Rules & Derating Notes
- Altitude>1000m, ambient>40℃, frequent starting>3 times/hour: Soft starter must be derated; upstream protective devices also need downgrade verification.
- PSTX with built-in bypass: Extra bypass contactor is not required, yet short-circuit protection on incoming side cannot be omitted, SCRs have low short-circuit withstand capability.
- Do NOT rely on MCCB long delay for motor protection: PSTX integrates Class10 electronic overload, PT100, locked rotor and phase loss protection. MCCB is only for short-circuit protection and isolation.
- Prospective short-circuit current Icc must be lower than MCCB Icu or fuse rated breaking capacity, otherwise cabinet hazard will occur.
- Fire mode: Protection logic shall match fire mode settings (some protections suppressed), upstream short-circuit protection must be retained.
- Quick Selection Guide
Weak grid, low short-circuit current, budget limited → T7S1000 MCCB (Type1)
Critical equipment, soft starter retention required after short circuit → 170M6814 semiconductor fuse (Type2)
690V main circuit: All components voltage rating ≥690V, 400V grade MCCBs are not allowed
Inside-Delta connection: Branch current = line current/√3, this table is not applicable
- Optional Incoming Contactor (not mandatory)
AF1250-30 3P AC-3, 400V; used for main circuit isolation after fault for maintenance, not a compulsory soft starter component.
ABB PSTX Soft Starter List (690V, 100–250V AC control supply, suffix -70)
Built-in bypass, In-Line reference. PSTX840-690-70 is included in this table.
Model rule: PSTXcurrent-690-70; Order No. prefix: 1SFA8982
Matched power @400V: reference value under 40℃, normal start, In-Line wiring
PSTXxxx-600-70 (208–600V version, prefix 1SFA8981) is separate and not listed here.
Supplementary Remarks
- Suffix -70 = AC100–250V control supply; -50 = 24V DC control supply, different order numbers, rarely used.
- All PSTX units have built-in bypass contactor, standard Modbus RTU; Anybus communication modules optional for Profinet / EtherNet/IP etc.
- Inside-Delta connection: Same unit can drive larger motors, branch current = line current ÷ √3, protection selection must be recalculated.
- Legacy series (phase-out): PSR, PSS, PSE, old PST. Only for low-budget retrofits, not recommended for new projects.
- PSTB: Pre-assembled cabinet version of PSTX, not bare soft starter.
Common Accessories Order List (for PSTX)
| Accessory | Order No. |
| Remote panel kit | 1SFA899001R1000 |
| Profinet Anybus module | 1SFA899002R1000 |
| EtherNet/IP Anybus module | 1SFA899003R1000 |
ABB PSTX Cross-Brand Equivalent Table (Built-in bypass, 690V, -70 version)
Base conditions: In-Line, 400V, Class10 normal start, built-in bypass, main circuit 208–690V, control supply 100–250V AC
⚠️ Important disclaimer: Only equivalent by current & power for selection reference, NOT 1:1 electrical interchangeable. Terminal definitions, communication protocols, fire mode logic, braking algorithm, dimensions and derating curves differ. Recheck protection, PLC programming and cabinet cutout for replacement jobs.
Competitor series:
Schneider: ATS480 (new generation, replaces ATS48)
Siemens: 3RW55 (high-performance built-in bypass model)
Allen-Bradley: SMC-Flex (built-in bypass, full high-current range; SMC-50 limited for small sizes)
| ABB PSTX Model | Rated Current A | Order No. | Schneider ATS480 | Siemens 3RW55 | Allen‑Bradley SMC‑Flex |
| PSTX30-690-70 | 30 | 1SFA898203R7000 | ATS480D17Y | 3RW5516-6HA16 | 150-F31NBD |
| PSTX37-690-70 | 37 | 1SFA898204R7000 | ATS480D22Y | 3RW5518-6HA16 | 150-F37NBD |
| PSTX45-690-70 | 45 | 1SFA898205R7000 | ATS480D30Y | 3RW5520-6HA16 | 150-F43NBD |
| PSTX60-690-70 | 60 | 1SFA898206R7000 | ATS480D38Y | 3RW5524-6HA16 | 150-F60NBD |
| PSTX72-690-70 | 72 | 1SFA898207R7000 | ATS480D47Y | 3RW5526-6HA16 | 150-F72NBD |
| PSTX85-690-70 | 85 | 1SFA898208R7000 | ATS480D62Y | 3RW5528-6HA16 | 150-F85NBD |
| PSTX105-690-70 | 105 | 1SFA898209R7000 | ATS480D75Y | 3RW5530-6HA16 | 150-F108NBD |
| PSTX142-690-70 | 142 | 1SFA898210R7000 | ATS480D88Y | 3RW5534-6HA16 | 150-F140NBD |
| PSTX170-690-70 | 170 | 1SFA898211R7000 | ATS480C11Y | 3RW5536-6HA16 | 150-F170NBD |
| PSTX210-690-70 | 210 | 1SFA898212R7000 | ATS480C14Y | 3RW5538-6HA16 | 150-F210NBD |
| PSTX250-690-70 | 250 | 1SFA898213R7000 | ATS480C17Y | 3RW5540-6HA16 | 150-F240NBD |
| PSTX300-690-70 | 300 | 1SFA898214R7000 | ATS480C21Y | 3RW5542-6HA16 | 150-F300NBD |
| PSTX370-690-70 | 370 | 1SFA898215R7000 | ATS480C25Y | 3RW5544-6HA16 | 150-F370NBD |
| PSTX470-690-70 | 470 | 1SFA898216R7000 | ATS480C32Y | 3RW5546-6HA16 | 150-F430NBD |
| PSTX570-690-70 | 570 | 1SFA898217R7000 | ATS480C41Y | 3RW5548-6HA16 | 150-F550NBD |
| PSTX720-690-70 | 720 | 1SFA898218R7000 | ATS480C59Y | 3RW5550-6HA16 | 150-F720NBD |
| PSTX840-690-70 | 840 | 1SFA898219R7000 | ATS480C66Y | 3RW5552-6HA16 | 150-F850NBD |
| PSTX1050-690-70 | 1050 | 1SFA898220R7000 | ATS480C81Y | 3RW5554-6HA16 | 150-F1000NBD |
| PSTX1250-690-70 | 1250 | 1SFA898221R7000 | ATS480C11Y (heavy-duty upgrade) | 3RW5556-6HA16 | 150-F1250NBD |
Core Series Differences (Selection Focus Points)
- ABB PSTX
Standard Modbus RTU; Anybus modules for Profinet/EtherNet/IP; built-in bypass; Fire Mode, limp mode, PT100 support; removable panel. Ideal for pumps, wastewater and fire pump applications.
- Schneider ATS480
TCS torque control, dynamic braking, pump cleaning wizard; Inside-Delta setup guide; Modbus & Profinet communication. Legacy ATS48 phased out; slightly larger footprint for same power rating.
- Siemens 3RW55
Native SIRIUS ecosystem, seamless integration with Siemens PLC / ET200; built-in bypass variant in part number. Preferred for full Siemens automation packages; protection logic differs from ABB.
- Allen-Bradley SMC-Flex
Natively compatible with Allen-Bradley Logix PLCs; built-in bypass; complete high-current range. SMC-50 limited to smaller motors, SMC-Flex for large motors.
Replacement Risk Checklist (For Foreign Trade & Retrofit Projects)
Fire pump applications: ATS480 and SMC-Flex also support fire mode, but protection suppression logic is different. PSTX parameters cannot be copied directly.
Communication: PSTX Modbus RTU register map is independent; ATS480 / 3RW55 / SMC have different register addresses and message structures.
Braking: PSTX static braking and pump stop curves differ from ATS480 TCS torque algorithm.
Inside-Delta: Each manufacturer defines derating and protection thresholds differently.
Cabinet cutout: Panel dimensions and mounting hole positions vary; cabinet modification is usually required for retrofits.