Order No.: 1SFA898219R7000 Series: PSTX Intelligent 3-phase SCR Soft Starter (with built-in bypass) Model Code Explanation PSTX: PSTX intelligent soft starter series (3-phase control, built-in bypass) 840: Rated operational current 840A (In-Line connection) 690: Maximum main circuit voltage 690V AC 70: Control power supply version 100–250V AC (50/60Hz) 📋 Core Electrical Specifications Item Model & ...

  • Product Details

Order No.: 1SFA898219R7000

Series: PSTX Intelligent 3-phase SCR Soft Starter (with built-in bypass)

Model Code Explanation

PSTX: PSTX intelligent soft starter series (3-phase control, built-in bypass)

840: Rated operational current 840A (In-Line connection)

690: Maximum main circuit voltage 690V AC

70: Control power supply version 100–250V AC (50/60Hz)

📋 Core Electrical Specifications

ItemModel & ratingRemarks
Soft starter rated current840AIn-Line
Recommended ABB MCCBT7S 1000 PR231/P-LI 3PIn=1000A, LI trip (long delay + instantaneous short circuit); rated for 690V
Trip settingLong delay: 1.0×In; Instantaneous short circuit: 8~10×InDo NOT use long delay for motor overload protection; motor overload is handled by PSTX internal electronic protection. Instantaneous threshold must avoid startup inrush.
Breaking capacityS=50kA@400VUpgrade to T7H / T7V (70/100kA) if short-circuit current at switchgear inlet is high
ApplicationPumps, fans, general conveyors, most industrial projectsEasy commissioning, provides isolation & disconnection, standard cabinet solution

⚙️ Standard Feature List

  1. Starting modes: Voltage ramp, torque ramp, current limiting, kickstart + ramp
  2. Stopping modes: Soft stop, pump stop (water hammer protection), dynamic braking, static braking
  3. Built-in bypass contactor: Bypasses SCRs at full speed to reduce heat and power loss; no external bypass cabinet required
  4. Protection functions: Motor overload, phase loss, phase sequence, overvoltage/undervoltage, earth fault, PT100 temperature sensing, SCR fault, overheat, locked rotor
  5. Special application functions: Fire mode (protections suppressed), jog mode, pipe cleaning, motor preheating, limp mode (degraded start with single SCR fault), sequential starting
  6. Communication: Standard Modbus RTU; optional Anybus modules for Profinet, EtherNet/IP, Modbus TCP, Profibus-DP
  7. IO & outputs: 3 programmable digital inputs, relay outputs (run / torque reached / event), 1 analog output (current / voltage / power factor selectable)
  8. HMI: Detachable graphic LCD panel, 17-language support; panel can be remotely mounted

🧰 Wiring Methods

In-Line: Standard connection, soft starter in series with main circuit, rated current 840A; most common selection

Inside-Delta: Installed in the branches of motor delta windings; same unit can drive larger motors. Note: Branch current = line current ÷ √3

📌 Selection Reference & Replacements

Adjacent models in the same series: PSTX720-690-70 (720A / 400V=400kW), PSTX1050-690-70 (1050A / 400V=560kW)

Legacy replacement: PST, PSS, PSR series are phased out; PSTX is the main upgraded model for new projects

Competitor equivalents: Schneider ATS480, Allen-Bradley SMC Flex / SMC-50, Siemens 3RW55

📎 Suitable Loads

Water pumps, fans, compressors, crushers, conveyors and large motors. Widely used in water supply, wastewater, HVAC, mining and cement industries. Fire pump applications are supported natively (built-in fire mode).

⚠️ Important Notes

  1. Derating calculation is mandatory for ambient temperature up to 60℃, altitude>1000m or frequent starting (>3 starts/hour)
  2. Built-in bypass version does not need an extra bypass contactor, but short-circuit protection (circuit breaker / fuse) on the incoming side is mandatory
  3. The panel can be removed and mounted separately on the cabinet door for convenient commissioning and maintenance

Control Modes of Soft Starters

Two categories: Command source control modes (3 standard modes for PSTX) and starting curve control modes (SCR voltage regulation logic)

  1. Command Source Control Modes (3 standard for ABB PSTX840-690-70, only one active at a time)
  2. Local HMI panel control

Detachable LCD panel mounted on the unit; can be removed for door mounting. Start, stop, reset and parameter modification via panel. Highest priority, overrides terminal and communication commands.

  1. Hardwired DI terminal control (dry contact, factory default)

2-wire (level): Continuous closed RUN contact = run; open = stop. Suitable for PLC dry contacts or remote pushbuttons.

3-wire (pulse): Normally closed stop, momentary pulse start, consistent with traditional relay circuits.

PSTX has dedicated start/stop terminals plus 3 programmable DIs for fault reset, mode switching, fire mode activation, etc.

Switch via Local/Remote button on panel or parameter setting. Emergency stop terminals are independent and not affected by control source selection.

  1. Fieldbus communication control (PLC / DCS / SCADA)

Standard: Modbus RTU (RS485)

Optional Anybus modules: Profinet, EtherNet/IP, Modbus TCP, Profibus-DP

Functions: Remote start/stop, fault reset, read current/voltage/status, online parameter editing

  1. Starting Curve Control Modes (voltage regulation strategies supported by PSTX)
  2. Voltage ramp start (most common: fans, general conveyors)

Starts from initial voltage and rises linearly to full voltage over set time; gentle impact, current rises naturally with load.

  1. Current limiting start (pumps, compressors, weak power grids)

Starting current is clamped at a preset multiplier (typically 3~4×In) to avoid high inrush for grids with limited capacity.

  1. Torque ramp start (heavy-duty loads: crushers, high static friction loads)

Directly controls output torque instead of only voltage; smooth torque during startup, reduces slipping risk.

  1. Kickstart + ramp

Short high-voltage pulse at startup to overcome static friction (viscous materials, stuck loads), then automatically switches to ramp. Not recommended for pumps.

  1. Jog mode

Low-voltage inching for rotation test and maintenance positioning.

III. Stopping Modes

Free stop: Output cut off directly, motor coasts by inertia (default)

Soft stop (voltage ramp down): Preferred for pumps to suppress water hammer

Static braking (DC braking): Fast stop for fans and high-inertia loads

Pump cleaning mode: Intermittent start-stop for pipeline flushing

  1. Quick Comparison

Terminal control: Stable & simple, widely used for local cabinet pushbuttons and standard PLC digital outputs

Communication control: Centralised monitoring, sequential start of multiple units, SCADA supervision for pump stations and factory DCS

Panel control: Commissioning, maintenance and standalone local operation

Incoming Protection Selection Table for PSTX840-690-70 (840A In-Line)

Preconditions: In-Line connection, 400V system, 40℃ ambient, normal starting. The soft starter provides built-in motor overload protection; upstream devices only perform short-circuit protection.

Coordination definitions:

Type 1 coordination: MCCB / gG general fuse. SCRs of soft starter are likely damaged after short circuit; spare replacement required. Low cost, preferred for general projects.

Type 2 coordination: Semiconductor high-speed fuse. Soft starter unit can remain usable after short circuit (only the fuse blows). For critical loads where downtime is restricted, higher cost.

  1. MCCB Solution (ABB recommended, Type1)
ItemSpecificationRemarks
Fuse rating1000A aM/gG 690VaM motor fuse preferred over gG
Fuse switch disconnectorOS800 fuse switchABB OS series
FeaturesLow cost; SCRs may fail after short circuit, soft starter inspection required after faultGeneral distribution, non-critical loads

Same T7S1000 can be used for 690V systems, confirm MCCB Ue≥690V. This table is invalid for Inside-Delta connection, branch current recalculation required.

  1. Fuse Solutions (2 options: general gG / semiconductor fast fuse)

Option A: gG general fuse (Type1, economy)

ItemSpecificationRemarks
Fuse rating1000A aM/gG 690VaM motor fuse preferred over gG
Fuse switch disconnectorOS800 fuse switchABB OS series
FeaturesLow cost; SCRs may fail after short circuit, soft starter inspection required after faultGeneral distribution, non-critical loads

Option B: Semiconductor high-speed fuse (Type2, SCR protection for critical loads)

ItemRecommended modelRemarks
Bussmann high-speed fuse170M6814690V, semiconductor grade for SCR protection; listed in PSTX datasheet
Fuse baseOS800D03PMatching fuse disconnector
FeaturesFuse blows first under short circuit to protect SCRs; only fuse replacement needed, soft starter can often resume serviceFire pumps, critical compressors, main fans with minimum downtime requirement
  1. Selection Rules & Derating Notes
  2. Altitude>1000m, ambient>40℃, frequent starting>3 times/hour: Soft starter must be derated; upstream protective devices also need downgrade verification.
  3. PSTX with built-in bypass: Extra bypass contactor is not required, yet short-circuit protection on incoming side cannot be omitted, SCRs have low short-circuit withstand capability.
  4. Do NOT rely on MCCB long delay for motor protection: PSTX integrates Class10 electronic overload, PT100, locked rotor and phase loss protection. MCCB is only for short-circuit protection and isolation.
  5. Prospective short-circuit current Icc must be lower than MCCB Icu or fuse rated breaking capacity, otherwise cabinet hazard will occur.
  6. Fire mode: Protection logic shall match fire mode settings (some protections suppressed), upstream short-circuit protection must be retained.
  7. Quick Selection Guide

Weak grid, low short-circuit current, budget limited → T7S1000 MCCB (Type1)

Critical equipment, soft starter retention required after short circuit → 170M6814 semiconductor fuse (Type2)

690V main circuit: All components voltage rating ≥690V, 400V grade MCCBs are not allowed

Inside-Delta connection: Branch current = line current/√3, this table is not applicable

  1. Optional Incoming Contactor (not mandatory)

AF1250-30 3P AC-3, 400V; used for main circuit isolation after fault for maintenance, not a compulsory soft starter component.

ABB PSTX Soft Starter List (690V, 100–250V AC control supply, suffix -70)

Built-in bypass, In-Line reference. PSTX840-690-70 is included in this table.

Model rule: PSTXcurrent-690-70; Order No. prefix: 1SFA8982

Matched power @400V: reference value under 40℃, normal start, In-Line wiring

PSTXxxx-600-70 (208–600V version, prefix 1SFA8981) is separate and not listed here.

Supplementary Remarks

  1. Suffix -70 = AC100–250V control supply; -50 = 24V DC control supply, different order numbers, rarely used.
  2. All PSTX units have built-in bypass contactor, standard Modbus RTU; Anybus communication modules optional for Profinet / EtherNet/IP etc.
  3. Inside-Delta connection: Same unit can drive larger motors, branch current = line current ÷ √3, protection selection must be recalculated.
  4. Legacy series (phase-out): PSR, PSS, PSE, old PST. Only for low-budget retrofits, not recommended for new projects.
  5. PSTB: Pre-assembled cabinet version of PSTX, not bare soft starter.

Common Accessories Order List (for PSTX)

AccessoryOrder No.
Remote panel kit1SFA899001R1000
Profinet Anybus module1SFA899002R1000
EtherNet/IP Anybus module1SFA899003R1000

ABB PSTX Cross-Brand Equivalent Table (Built-in bypass, 690V, -70 version)

Base conditions: In-Line, 400V, Class10 normal start, built-in bypass, main circuit 208–690V, control supply 100–250V AC

⚠️ Important disclaimer: Only equivalent by current & power for selection reference, NOT 1:1 electrical interchangeable. Terminal definitions, communication protocols, fire mode logic, braking algorithm, dimensions and derating curves differ. Recheck protection, PLC programming and cabinet cutout for replacement jobs.

Competitor series:

Schneider: ATS480 (new generation, replaces ATS48)

Siemens: 3RW55 (high-performance built-in bypass model)

Allen-Bradley: SMC-Flex (built-in bypass, full high-current range; SMC-50 limited for small sizes)

ABB PSTX ModelRated Current AOrder No.Schneider ATS480Siemens 3RW55Allen‑Bradley SMC‑Flex
PSTX30-690-70301SFA898203R7000ATS480D17Y3RW5516-6HA16150-F31NBD
PSTX37-690-70371SFA898204R7000ATS480D22Y3RW5518-6HA16150-F37NBD
PSTX45-690-70451SFA898205R7000ATS480D30Y3RW5520-6HA16150-F43NBD
PSTX60-690-70601SFA898206R7000ATS480D38Y3RW5524-6HA16150-F60NBD
PSTX72-690-70721SFA898207R7000ATS480D47Y3RW5526-6HA16150-F72NBD
PSTX85-690-70851SFA898208R7000ATS480D62Y3RW5528-6HA16150-F85NBD
PSTX105-690-701051SFA898209R7000ATS480D75Y3RW5530-6HA16150-F108NBD
PSTX142-690-701421SFA898210R7000ATS480D88Y3RW5534-6HA16150-F140NBD
PSTX170-690-701701SFA898211R7000ATS480C11Y3RW5536-6HA16150-F170NBD
PSTX210-690-702101SFA898212R7000ATS480C14Y3RW5538-6HA16150-F210NBD
PSTX250-690-702501SFA898213R7000ATS480C17Y3RW5540-6HA16150-F240NBD
PSTX300-690-703001SFA898214R7000ATS480C21Y3RW5542-6HA16150-F300NBD
PSTX370-690-703701SFA898215R7000ATS480C25Y3RW5544-6HA16150-F370NBD
PSTX470-690-704701SFA898216R7000ATS480C32Y3RW5546-6HA16150-F430NBD
PSTX570-690-705701SFA898217R7000ATS480C41Y3RW5548-6HA16150-F550NBD
PSTX720-690-707201SFA898218R7000ATS480C59Y3RW5550-6HA16150-F720NBD
PSTX840-690-708401SFA898219R7000ATS480C66Y3RW5552-6HA16150-F850NBD
PSTX1050-690-7010501SFA898220R7000ATS480C81Y3RW5554-6HA16150-F1000NBD
PSTX1250-690-7012501SFA898221R7000ATS480C11Y (heavy-duty upgrade)3RW5556-6HA16150-F1250NBD

Core Series Differences (Selection Focus Points)

  1. ABB PSTX

Standard Modbus RTU; Anybus modules for Profinet/EtherNet/IP; built-in bypass; Fire Mode, limp mode, PT100 support; removable panel. Ideal for pumps, wastewater and fire pump applications.

  1. Schneider ATS480

TCS torque control, dynamic braking, pump cleaning wizard; Inside-Delta setup guide; Modbus & Profinet communication. Legacy ATS48 phased out; slightly larger footprint for same power rating.

  1. Siemens 3RW55

Native SIRIUS ecosystem, seamless integration with Siemens PLC / ET200; built-in bypass variant in part number. Preferred for full Siemens automation packages; protection logic differs from ABB.

  1. Allen-Bradley SMC-Flex

Natively compatible with Allen-Bradley Logix PLCs; built-in bypass; complete high-current range. SMC-50 limited to smaller motors, SMC-Flex for large motors.

Replacement Risk Checklist (For Foreign Trade & Retrofit Projects)

Fire pump applications: ATS480 and SMC-Flex also support fire mode, but protection suppression logic is different. PSTX parameters cannot be copied directly.

Communication: PSTX Modbus RTU register map is independent; ATS480 / 3RW55 / SMC have different register addresses and message structures.

Braking: PSTX static braking and pump stop curves differ from ATS480 TCS torque algorithm.

Inside-Delta: Each manufacturer defines derating and protection thresholds differently.

Cabinet cutout: Panel dimensions and mounting hole positions vary; cabinet modification is usually required for retrofits.