Basler Electric BE2000E Digital Excitation Voltage Regulator - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

Basler Electric BE2000E Digital Excitation Voltage Regulator - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

PLC/

Basler Electric BE2000E Digital Excitation Voltage Regulator

Brand: Basler Electric (USA) Description: Microprocessor-based digital automatic voltage regulator for brushless synchronous generator excitation control Core replacement model: Marathon DVR2000E/DVR2000EC, pin and footprint compatible, plug-and-play retrofit ✅ Four Control Modes AVR Automatic Voltage Regulation (Default):Maintains constant generator terminal voltage, accuracy ±0.25% (at rated power factor and constant frequency) FCR Field Current Regulation:Manual excitation current ...

  • Product Details

Brand: Basler Electric (USA)

Description: Microprocessor-based digital automatic voltage regulator for brushless synchronous generator excitation control

Core replacement model: Marathon DVR2000E/DVR2000EC, pin and footprint compatible, plug-and-play retrofit

✅ Four Control Modes

  1. AVR Automatic Voltage Regulation (Default):Maintains constant generator terminal voltage, accuracy ±0.25% (at rated power factor and constant frequency)
  2. FCR Field Current Regulation:Manual excitation current control for commissioning and AVR fault backup, adjustable from 0~3Adc
  3. PF Power Factor Regulation:For grid paralleling, constant power factor control
  4. VAR Reactive Power Regulation:For grid paralleling, constant reactive power output control

📌 Key Electrical Specifications

Excitation Output (PWM): 75 Vdc/3 Adc continuous; Forcing 150 Vdc /7.5 Adc for 10s (at 200Vac input)

Minimum Excitation Winding Resistance: ≥18 Ω (critical selection parameter)

PMG Power Supply: 180–240 Vac, 200–360 Hz, 350 VA

Voltage Sensing: Single-phase/three-phase RMS sensing, supports 120/240/480/600Vac

Current Sensing: Single-phase CT, max 5A AC, for reactive droop, PF/VAR control

Communication: Rear RS232 DB9 port, configuration software BESTCOMS™ BE2000E (V2.02.01) for parameter setup, waveform recording and parameter backup

Interfaces: 4 digital inputs, 1 common alarm relay output; front panel HMI + LED status indicators, local parameter modification

🛡️ Protection & Function List

Soft Voltage Ramp: 1–120s adjustable, suppress voltage surge during startup

OEL Over Excitation Limit + Over Excitation Shutdown

V/Hz (Volts/Hertz) Limiting, Under-frequency Load Shedding

Generator Overvoltage Shutdown, Loss-of-Sensing Protection

Regulator Internal Over-temperature Protection

Excitation Crowbar Protection Circuit

Paralleling Functions: Reactive Droop Compensation, Reactive Differential Compensation for multi-generator parallel operation

High THD tolerance design, suitable for non-linear harmonic loads

📎 Supporting Documents (Basler Official)

BE2000E Bulletin Rev11

Instruction Manual Rev G

BESTCOMS Configuration Software

Generator Paralleling Technical White Paper

🧩 Typical Applications

Industrial diesel/gas brushless synchronous generator sets, standby power supplies, continuous-duty power stations, multi-unit grid paralleling projects. Widely used for retrofit replacement of original Marathon generators.

Basler BE2000E Fault Tree (OEL/OV/SENSE LOSS/OVERTEMP)

General Pre-rules: After fault latch-up, power off for ≥60 seconds to reset. Use BESTCOMS software first to capture fault snapshots, waveform records and real-time readings (excitation current, excitation voltage, terminal sensing voltage). Distinguish between Limit Alarm (LIMIT) and Shutdown Trip (SHUTDOWN). For grid-tied generators, de-parallel and shed loads before troubleshooting to avoid secondary accidents.

Protection Action Logic: Alarm relay AL1/AL2 closes; after trip, regulator reduces excitation, Crowbar circuit activates and voltage regulation output ceases.

  1. OEL Over Excitation Alarm/Over Excitation Shutdown

Symptoms: OEL LED flashes; BESTCOMS shows excitation current out of limit. Two statuses: OEL Limit (current limiting, no trip), OEL Shutdown (timeout latch-up)

OEL Alarm ON

Step 1: Verify generator operating condition

✅ Generator overload, heavy inductive load, excessive reactive power → Shed load, verify rated excitation current of generator

✅ Grid paralleling: Excessive PF/VAR setpoint, unbalanced reactive power sharing, incorrect droop setting → Switch to local AVR mode, check PF/VAR setting, CT wiring and CT ratio

✅ Low frequency/V/Hz action raises excitation (speed drop) → Check prime mover speed and governor

Step 2: Parameter check via BESTCOMS

OEL current threshold set too low → Re-set according to rated excitation winding current

OEL delay time set too short → Typical 5~10s; short-duration forcing is permitted, avoid 0s instant trip

Improper soft-start setting, startup surge triggers OEL → Extend soft ramp time

Step 3: Hardware circuit measurement (power off and locked out, test excitation winding)

Partial short/turn-to-turn short in excitation winding → Winding resistance far below nameplate minimum value; shorted winding causes high excitation current and repeated OEL

Loose excitation terminals, damaged insulation, earth leakage → Insulation resistance test

Abnormally high PMG supply voltage → Measure PMG input 180–240Vac, troubleshoot PMG if out of range

Step 4: Regulator hardware check

Excitation PWM power transistor breakdown/shorted → Continuous high excitation current and OEL latch-up

Replace BE2000E and re-test; if OEL recurs after replacement → Fault in exciter assembly

Note: OEL is rotor protection. Repeated OEL events will burn excitation rotor

  1. OV Generator Overvoltage Alarm

Symptoms: OV LED ON; fixed 0.75s trip delay; threshold default 105~120% rated voltage, software configurable

OV Alarm ON

Step 1: Distinguish true overvoltage vs false sensing alarm

Measure generator terminal voltage with multimeter and compare with BESTCOMS reading

Measured voltage actually high: True overvoltage

Measured voltage normal, software reads high: Sensing circuit fault, refer to SENSE LOSS branch

Step 2: Troubleshoot true overvoltage

Overvoltage at no-load startup: High voltage setpoint, excessive PID gain, failed soft ramp

Voltage overshoot after sudden load rejection: Mismatched PID (P/I/D), excessive transient gain

Prime mover speed runaway (governor failure) → Rectify diesel/gas engine governor first

Grid-tied unit: Voltage spike when reactive power is removed during de-paralleling

Step 3: Hardware inspection

Failed excitation Crowbar circuit, unable to discharge excitation energy

BE2000E power output transistor shorted, excitation uncontrolled

Excessive PMG supply voltage, excitation drive overflow

Reset: Power off for 1 minute after OV latch-up. Do NOT repeatedly start the unit with recurring OV, risk of downstream equipment breakdown

  1. SENSE LOSS Loss of Sensing

Symptoms: SENSE LOSS LED flashes; protection logic: configurable delay (0–25s) before trip, regulator de-excites to prevent catastrophic overvoltage caused by uncontrolled excitation without valid sensing

SENSE LOSS Alarm ON

Step 1: Power off, inspect voltage sensing circuit (most frequent fault point)

Broken sensing wire, loose terminal, blown fuse, tripped circuit breaker

Wrong phase sequence, reversed single-phase sensing wiring (BE2000E supports single/three-phase sensing; hardware wiring must match software mode)

Failed PT voltage transformer, PT ratio mismatch with setting, PT secondary open circuit

Sensing cable earth fault, short circuit, insulation damage

Step 2: Verify configuration in BESTCOMS

Wrong sensing mode: three-phase hardware with single-phase software setting, or vice versa

Rated voltage setting mismatched with PT secondary output (e.g. 480V generator set as 600V)

LOS delay set too short, normal voltage fluctuation triggers trip

Step 3: Noise and grounding issues

Poor regulator grounding, routed together with power cables, heavy harmonic interference causes intermittent sensing dropout

Extreme high THD from rectifier loads; although the unit is THD tolerant, severe distortion can still trigger loss of sensing

Step 4: Regulator hardware judgment

Normal voltage present at sensing terminals but no reading in software → Internal sensing board damage on BE2000E

SENSE LOSS persists after regulator replacement → Fault in generator PT/secondary circuit

Critical Warning: Do NOT bypass SENSE LOSS protection for startup, risk of runaway overvoltage and equipment damage

  1. OVERTEMP Regulator Over Temperature

Symptoms: OVERTEMP LED flashes; internal temperature sensor triggers over-temperature trip latch-up, protects IGBT/PWM power stage

OVERTEMP Alarm ON

Step 1: Ambient and heat dissipation (most common cause)

Enclosed cabinet, poor ventilation, high ambient temperature, direct sunlight

Heatsink clogged with dust and grease, airflow blocked by cables

Nearby heat sources (VFD, contactors) heating the AVR

Step 2: Continuous high excitation under load

Long-term high reactive power, continuous OEL limiting, power devices run hot

Low excitation winding resistance, excitation current constantly near 3A rating

Frequent excitation forcing (150V/7.5A 10s forcing cycle)

Step 3: Power supply and wiring

Sustained high PMG supply voltage, increased power stage loss and heat

Loose excitation output terminals, contact resistance heat conducted to regulator

Poor grounding, common-mode interference causes abnormal heating of internal components

Step 4: Regulator hardware check

Drifted/failed internal temperature sensor (OVERTEMP alarm immediately after cold power-up)

Aged power devices, high leakage current, heat even at no-load

Action: Shut down and cool for 30min before retest; alarm triggers immediately after loading when cooled → Regulator damaged, replace

Standard General Troubleshooting Workflow for Site

  1. Lockout-tagout and isolate power; power off ≥60s to clear latched faults
  2. Power on, connect BESTCOMS, retrieve fault logs, waveform records and live measurements (excitation current, sensing voltage, internal temperature)
  3. Fault classification: Operating condition/load/governor/grid issue → Parameter setting issue → External circuit (PT, PMG, excitation winding, CT) → Confirm regulator hardware failure only at last
  4. After repair: Test no-load operation first, then apply load gradually; for grid-tied units, complete AVR regulation and droop test before paralleling

Quick Reference Cheat Sheet

OEL = Excitation current too high (rotor/excitation circuit, excess reactive load, low limit threshold)

OV = Terminal voltage too high (speed, PID tuning, shorted excitation, load rejection surge)

SENSE LOSS = Voltage sensing signal missing (PT, sensing wiring, configuration, EMI noise)

OVERTEMP = AVR overheating (poor cooling, continuous high excitation, faulty sensor/power device)

Basler Electric Digital Excitation Regulator (Digital AVR/DECS) Full Model List

/Classification: BE Series (retrofit models, mainly for Marathon replacement), DECS Series (standard digital excitation controllers, mainstream stock). Status: Active/Obsolete, description and typical application

  1. BE Series (Retrofit & Replacement Models, BE2000E belongs here)
ModelStatusBrief DescriptionRemarks
BE2000EActivePMG-fed digital AVR for brushless synchronous generatorsDirect drop-in replacement for Marathon DVR2000E / DVR2000EC; PWM output 75Vdc/3A, RS232, BESTCOMS, 4 control modes (AVR/FCR/PF/VAR)
BE300PMActivePotting compact digital AVRReplaces Marathon PM300, PMG supply, built-in OEL & under-frequency compensation, for harsh environment generators
  1. DECS Series (Basler Mainstream Digital Excitation Control for Industrial & Power Stations)

Legacy Models (Most Obsolete, Used for Retrofit)

ModelStatusBrief DescriptionRemarks
DECS-15ObsoleteEntry-level compact digital AVREarly small brushless generator sets
DECS-100ObsoleteClassic compact digital excitation controllerSub-models: A11 / A15 / B11 / B15; PMG or terminal sensing supply, widely used on diesel generators, BESTCOMS software
DECS-200ObsoleteMedium-duty excitation controllerMultiple excitation power sources, drives external power modules
DECS-200NObsoleteNegative forcing version of DECS-200For grids with severe disturbance, requires fast de-excitation
DECS-300ObsoleteMedium power station excitation controllerGrid paralleling, hydro / small turbine generator retrofit
DECS-400ObsoleteLarge static excitation master controllerHigh-power generators, legacy excitation system upgrade projects

Current Active Flagship Models (Official Website Primary Offering)

ModelStatusBrief DescriptionRemarks
DECS-150ActiveEconomical all-round digital excitation controllerSmall/medium diesel & gas generators, paralleling, integrated protection, BESTCOMSPlus, cost-effective
DECS-250ActiveHigh-performance universal digital excitation controllerPopular model; supports PSS Power System Stabilizer, programmable logic, auto PID tuning, grid-tied power stations, standby power, integrated generator protection
DECS-250EActiveDECS-250 extended versionExpanded I/O, redundant interfaces, for large generator packages
DECS-250NActiveDECS-250 negative forcing versionNegative excitation forcing, fast voltage suppression under grid disturbance
DECS-450ActiveHigh-power premium excitation controllerMedium & large steam / hydro generators, drives external power cabinets, redundant architecture, grid compliance, large power station retrofit
DECS-2100ActiveMaster excitation controller for large / megawatt-scale generatorsDrop-in replacement for GE EX2000 and similar large excitation systems, core unit for excitation cabinet packages
  1. Auxiliary Supporting Modules (Excitation Accessories, Not Standalone AVR)

VRM-2020: Remote Voltage Regulator Module (works with DGC-2020 genset controller)

ICRM-7/ICRM-15: PWM AVR excitation inrush current limiting protection module

MVC: Manual Voltage Control Unit (backup manual excitation if AVR fails)

  1. Selection Quick Guide for Replacement
  2. Direct replacement for Marathon DVR2000E → BE2000E (pin & mounting compatible, priority choice)
  3. Standard diesel generator with budget constraint → DECS-150
  4. General paralleling application requiring PSS and rich protection → DECS-250/DECS-250N
  5. Hydro/steam high-power generators, excitation cabinet packages → DECS-450/DECS-2100
  6. Retrofit of old DECS-100/200/300/400 → Upgrade to DECS-250 or DECS-450 preferentially
  7. Software Compatibility

BE2000E: BESTCOMS (legacy version, V2.02.01)

DECS150/250/450: BESTCOMSPlus (new generation software)

Prev:

Leave a Reply

Leave a message