Status: Active (In Production)
Model Definition: LOGO!8 series expansion module DM16 230R; 16 I/O points (8DI+8DO), 230V class, relay output
✅ Core Specifications
Full Model Name: LOGO! DM16 230R
I/O Configuration: 8 digital inputs (DI) + 8 relay digital outputs (DO)
Power Supply: AC/DC 115…230V (47–63Hz)
Input Signal Level: AC/DC 230V signal
Logic 0: <40V AC / <30V DC
Logic 1: >79V AC / DC
Output Type: Passive relay contacts, rated 5A resistive load per channel
Mounting: Standard 35mm DIN rail
Width: 71.5 mm (4TE); Height 90mm; Depth 58mm
Protection Class: IP20
Operating Temperature: 0℃ ~ +55℃
Weight: 0.294 kg
Certifications: CE, cULus, FM
Connection: Side expansion cable directly connected to LOGO! main unit, no separate communication cable required
📌 Compatibility (Critical Note)
✅ Compatible Main Units: LOGO!8 / LOGO!8.2 (order number suffix 0BA2, 0BA3, etc.)
❌ Not compatible with older LOGO! 0BA6 / 0BA7 (different hardware interface; program incompatible)
Multiple DM modules can be expanded on one LOGO! main unit, limited by the total I/O capacity of the controller.
🧰 Typical Application Scenarios
- Electrical cabinet, HVAC, water pump & fan control: Collect 220V limit switches and pressure switches; directly drive 220V contactors, solenoid valves and indicator lamps.
- Small conveyor & packaging stand-alone machines: Expand I/O points when the main unit runs out of capacity for AC signal circuits.
- Building automation, ventilation and roller shutter control (AC signal loops).
- Retrofit projects: Existing 220V sensors and actuators without adding intermediate relay isolation.
Selection Reminder: This module is 230V voltage class. For DC24V signals, choose DM16 24R (6ED1055-1NB10-0BA2).
⚠️ Troubleshooting & Operation Guidelines
- Module no response: Check if the side expansion cable is fully latched; the module itself requires AC/DC230V power supply independent of the main unit.
- Input channel not detected: Input voltage must exceed the 79V threshold; low voltage signals cannot trigger the input; distinguish AC/DC signal types strictly.
- Damaged relay outputs: Relay contacts are easily damaged by back EMF from inductive loads (contactor coils, solenoid valves). Install RC snubber circuits in parallel with coils to extend contact life.
- Load limit: Max 5A per channel; avoid long-term full-load operation on all 8 channels simultaneously to prevent overheating.
- Passive relay output: No built-in common power on contacts; load power must be wired externally.
📎 LOGO! DM Digital Expansion Module Comparison
6ED1055-1FB10-0BA2: DM16 230R|8DI/8DO, AC/DC230V, relay output (this model)
6ED1055-1NB10-0BA2: DM16 24R|8DI/8DO, DC24V, relay output
6ED1055-1MD00-0BA2: DM16 24T|8DI/8DO, DC24V, transistor output (0.3A)
Full Model List of 6ED1055 Series (LOGO!8 Expansion Modules)
Compatible Host: LOGO!8 / 8.2 / 8.3 (suffix 0BA2/0BA3); Incompatible with legacy 0BA6/0BA7 controllers
Categories: DM digital modules, AM analog modules, TDE text display
- Digital Expansion Modules (DM Series)
(1) DM8 Series|4DI+4DO (2MW, 2 module width)
- DM8 24 (Transistor Output)
Order No.: 6ED1055-1CB00-0BA2
Spec: DC24V input, 0.3A transistor output
- DM8 24R (Relay Output)
Order No.: 6ED1055-1HB00-0BA2
Spec: DC24V input, 5A relay contact output
- DM8 12/24R (AC/DC Universal Relay)
Order No.: 6ED1055-1MB00-0BA2
Spec: DC12/24V input, 5A relay output
- DM8 230R (AC220V Relay, Small I/O Version)
Order No.: 6ED1055-1FB00-0BA2
Spec: AC/DC115~230V input, 5A relay output
(2) DM16 Series|8DI+8DO (4MW, 4 module width, including your model)
- DM16 24 (Transistor Output)
Order No.: 6ED1055-1CB10-0BA2
Spec: DC24V input, 0.3A transistor; suitable for small DC24V solenoid valves with high switching frequency
- DM16 24R (DC24V Relay Version)
Order No.: 6ED1055-1NB10-0BA2
Spec: DC24V input, 5A relay contacts; matches NPN/PNP photoelectric & proximity switches
- DM16 230R (This model, AC220V Relay)
Order No.: 6ED1055-1FB10-0BA2
Spec: AC/DC115~230V input, 5A passive relay contacts; directly connect 220V switch signals without intermediate relays
- Analog Expansion Modules (AM Series, same 6ED1055 product line)
- AM2 (2-channel Analog Input AI)
Order No.: 6ED1055-1MA00-0BA2
Signal: 0~10V / 4~20mA
- AM2 RTD (PT100/PT1000 Temperature Input)
Order No.: 6ED1055-1MD00-0BA2
- AM2 AQ (2-channel Analog Output AO)
Order No.: 6ED1055-1MM00-0BA2
Signal: 0~10V, 4~20mA
- Text Display Module (TDE)
Order No.: 6ED1055-4MH08-0BA1
Function: External text display for LOGO!8; key operation, parameter modification and alarm message display
- Model Naming Rule (6ED1055 Segment Breakdown)
6ED1055-1XX00-0BA2
1CB: DC24V transistor output
1HB: DC24V relay output
1MB: DC12/24V relay output
1FB: AC/DC230V relay output (your model)
1NB: DM16 DC24V relay
00 = DM8 (4DI/4DO); 10 = DM16 (8DI/8DO)
Suffix 0BA2: Standard revision for LOGO!8
- DM16 3-Model Selection Comparison
| Order Number | Model | Input Voltage | Output Type | Typical Application |
| 6ED1055-1CB10-0BA2 | DM16 24 | DC24V | Transistor 0.3A | Small DC solenoid valves, high-frequency switching |
| 6ED1055-1NB10-0BA2 | DM16 24R | DC24V | Relay 5A | DC24V sensors + contactors |
| 6ED1055-1FB10-0BA2 | DM16 230R | AC/DC230V | Relay 5A | 220V pushbuttons, air dampers, fan circuits |
- Version Distinction
- Suffix 0BA2 = LOGO!8 / 8.2, current production mainstream part (preferred for procurement)
- Suffix 0BA3 = LOGO!8.3 new version; hardware fully interchangeable, direct drop-in replacement
- Older 0BA0/0BA1 versions are phased out; always select 0BA2 for new projects.