Brand: Telemecanique Sensors (formerly Schneider OsiSense XM series, now part of YAGEO)
Type: Diaphragm type, adjustable differential pressure switch with dual setpoints, local scale indicator, 1 changeover contact (1CO)
✅ Pressure Specifications
Rising pressure setting range: 0.7~10 bar
Falling pressure reset range: 0.13~9.15 bar
Minimum differential: 0.57 bar; maximum differential: 7.5 bar
Instantaneous overload pressure: 22.5 bar; continuous maximum working pressure: 12.5 bar
Burst pressure: 45 bar
Sensing element: Diaphragm; wetted materials: FPM/FKM fluoroelastomer + zinc alloy
Compatible media: Compressed air, clean water, hydraulic oil; medium temperature: 0~70 ℃
✅ Process & Electrical Connection
Process connection: G1/4 internal thread (ISO228)
Electrical entry: Pg13.5 cable gland, cable OD 9–13 mm; screw terminals, wire size 0.5~2.5 mm²
Contact: 1CO (13-14-11-12) silver contact, snap-action
Contact rating: AC-15 120V/3A; 240V/1.5A; DC-13 250V/0.1A
Insulation voltage Ui: 500V(IEC); impulse withstand voltage Uimp: 6 kV
Protection class: IP66
Repeatability: ±2%; maximum switching frequency: 120 cycles/min
Mechanical service life: 5 million cycles
Ambient temperature: -25~70 ℃; storage temperature: -40~70 ℃
✅ Dimensions & Weight
Width 35 mm × Height 113 mm × Depth 75 mm; net weight 0.705 kg; mounting in any orientation
✅ Approvals & Standards
CE, UL508, CSA, IEC60947-5-1; marine classification approval; origin: Czech Republic / Morocco; warranty: 18 months
✅ Typical Applications
Air compressors, hydraulic power packs, water supply pumps, lubrication systems, HVAC, general industrial pressure start/stop, high/low pressure interlock protection
✅ Cross-Series Replacement Reference
XMLB shares the same platform with XMLA/XMLC/XMLD. Please distinguish pressure ranges (0.25/10/16/25 bar), contact quantity and indicator versions. Legacy models XM2JM, XMJ can be replaced with XMLB.
Telemecanique XMLB010A2S11 Pressure Switch Installation Manual
Applicable series: XMLA / XMLB / XMLC / XMLD same-platform electromechanical pressure switches. Model: XMLB010A2S11, 10 bar range, adjustable differential, 1CO changeover contact, G1/4 internal thread, Pg13.5 gland, IP66
⚠️ Precautionary Safety Warnings (Read First)
- Do NOT disassemble, wire or adjust under pressure or live power. Depressurize the system and isolate control power before any work.
- Approved media: Compressed air, clean water, standard hydraulic oil. Strong corrosive media or high-temperature media are prohibited (max medium temperature 70 ℃).
- Pressure must not exceed instantaneous overload 22.5 bar or burst pressure 45 bar. Overpressure will permanently damage the diaphragm and void protection function.
- Contacts are designed for control circuits only. Do not switch main motor power directly. AC-15 120V 3A / 240V 1.5A, DC-13 250V 0.1A.
- IP66 rated. For outdoor installation, avoid direct sunlight and continuous heavy spray. Tighten the cable gland fully for sealing.
- Commissioning, calibration and maintenance must be performed by qualified pneumatic/hydraulic and low-voltage electrical personnel.
- Unpacking Inspection
Verify model: XMLB010A2S11
Check housing and thread for cracks or damage; confirm scale plate intact, gland and sealing washer supplied
Accessories: Unit only, fitted with Pg13.5 cable gland; no adapter included
Cross-check nameplate: 0.7~10 bar range, 1CO contact, G1/4 ISO228 internal process thread
- Mechanical Installation
2.1 Mounting Requirements
Mounting orientation: Any position (XMLB has no mandatory upright requirement). Prioritize easy visibility of the scale.
Keep away from high heat sources and heavy vibration (excessive vibration causes false tripping and shortens service life).
It is recommended to fit an isolation valve + drain valve at the tapping point for future calibration and replacement without full system shutdown.
Tapping point: Take pressure from the side wall of pipe runs. Avoid high points (air accumulation) and low points (sediment build-up).
2.2 Thread Connection (G1/4 Internal BSP)
- Clean male thread, remove burrs and metal debris to prevent particles entering the diaphragm chamber.
- Sealing: Use PTFE tape only on the male thread. Do not push tape residue into the switch internal thread as debris may jam the diaphragm.
- Tightening: Use a spanner on the bottom hexagonal process base only. Never clamp the plastic housing — this will damage the internal mechanism.
- Torque moderately until leak-tight; do not force over-tightening.
Optional accessory: G1/4 to NPT1/4 adapter for NPT piping systems.
2.3 Piping Recommendations
Keep impulse tubing short and large bore to reduce response lag. Long tubing may cause slow response and chattering.
Install a pre-filter for media with solids to protect the FKM fluoroelastomer diaphragm.
Drain water-filled systems in cold environments to prevent freezing; ice expansion ruptures the diaphragm.
- Electrical Wiring
3.1 Cable Specification
Cable outer diameter: 9~13 mm (matches Pg13.5 gland)
Conductor cross-section: 0.5~2.5 mm² (AWG20~AWG14); ferrules are recommended for stranded conductors.
3.2 Terminal Definition (1CO dry contact)
| Terminal | Definition | Description |
| 11 | COM | Common |
| 12 | NC | Normally closed: Conducts below set pressure, opens at trip pressure |
| 14 | NO | Normally open: Closes at trip pressure, opens at low pressure |
Marking 13: Some versions mark 13 alongside 14 for the same NO circuit; follow housing marking.
3.3 Wiring Procedure
- Isolate power, remove top cover screws and open the lid.
- Loosen Pg13.5 gland nut, feed cable through and strip to suitable length.
- Insert wires into terminals and tighten screws securely to avoid loose connections.
- Route cables clear of the internal spring adjustment assembly. Refit cover and tighten screws evenly.
- Tighten gland and compress rubber seal to maintain IP66 integrity. Poor gland sealing causes water ingress and failure.
Wiring note: This is a passive dry contact. No supply voltage is carried by the switch. PLC or relay control power must be supplied externally.
- Pressure Setting & Calibration (XMLB dual setpoint: trip point + differential)
XMLB operation: Two adjustment screws: high setpoint (trip pressure) and differential (hysteresis). The low reset point is not independently adjusted.
Specification range for this model:
Rising trip pressure: 0.7~10 bar
Falling reset pressure: 0.13~9.15 bar
Minimum differential 0.57 bar, maximum differential 7.5 bar
Calibration Steps
- Fully depressurize the line.
- Open the front scale cover to access the two adjustment screws with graduated scale.
- Connect a reference pressure gauge (accuracy ≥0.5 class). The built-in scale is only for rough setting.
- Raise pressure slowly while monitoring the reference gauge:
Main adjustment screw: Sets trip pressure. At this pressure, contact state reverses (NO closes, NC opens).
Differential screw: Sets the pressure gap between trip and reset. Larger differential means greater pressure drop before reset.
- Cycle pressure up and down 2–3 times to confirm stable trip and reset points with no drift.
- Refit protective cover after setting to prevent accidental adjustment. Record values and apply identification label.
✅ Typical example (pump start-stop):
Start at 3 bar, stop at 5 bar → differential = 2 bar. Pump stops at 5 bar, restarts at 3 bar.
Note: The built-in scale is approximate. Safety interlock applications must be calibrated against a certified reference gauge; accuracy ±2%.
- Commissioning Check
- Confirm no leakage, secure wiring and intact housing sealing.
- Ramp pressure slowly through working range and verify contact switching matches settings.
- Complete multiple cycles to confirm no chattering or rapid cycling.
- Verify contact load stays within rated limits; fit fuse protection for control circuits.
- Record: trip pressure, reset pressure, media, ambient temperature and calibration date.
- Maintenance
- Routine inspection: Leakage, cable damage, gland water ingress and housing corrosion.
- Calibration interval: 6–12 months for standard air compressor / water pump service; quarterly calibration for safety interlock duty.
- Cleaning: Wipe housing externally only. Do NOT disassemble the process chamber. Diaphragm removal destroys sealing and accuracy.
- Long-term shutdown: Depressurize and drain the chamber. Drain water circuits to prevent corrosion and freezing.
- Mechanical life: 5 million cycles. Replace at end of life.
- Fault Troubleshooting Table
| Symptom | Probable Cause | Remedy |
| Switch does not actuate at set pressure | Diaphragm jammed by debris; differential set too large; broken wiring | Depressurize, inspect or replace unit; reset differential; check wiring |
| Rapid cycling / chattering | Differential set too small; pressure pulsation in piping | Increase differential; fit snubber or accumulator |
| Trip pressure drifts out of tolerance | Overpressure shock; diaphragm aging; excessive vibration | Replace switch; add vibration dampening and surge protection |
| Water ingress / internal corrosion | Loose gland, missing cover gasket | Reseal assembly; replace unit if sealing parts are damaged |
| Leakage at thread | PTFE tape misapplied; cracked base from over-tightening | Re-seal thread; replace unit if base is cracked |
Telemecanique XMLB Series Electromechanical Pressure Switch – Fault Troubleshooting Guide
For XMLB010A2S11, diaphragm type, adjustable differential, dry contact. Always depressurize and isolate power before troubleshooting; test contacts with multimeter continuity mode.
| Fault Symptom | Root Cause | Inspection Steps | Corrective Action |
| No switching when pressure reaches setpoint | 1. Tapping port / impulse line blocked by sludge, scale or debris2. Diaphragm jammed or ruptured3. Setpoint higher than system working pressure4. Internal adjustment thread stripped or spring seized5. Failed microswitch | 1. Depressurize and inspect tapping port2. Use reference gauge to confirm actual system pressure3. Test COM-NO / COM-NC continuity with multimeter | 1. Clear impulse line and add inlet filter2. Reduce trip setpoint and lock screw3. Replace complete unit if diaphragm or internal mechanism is damaged (diaphragm chamber not serviceable on site) |
| Switch fails to reset below reset pressure, contact stays latched | 1. Excessive differential setting2. Contact welded / stuck (inductive load without surge suppression)3. Jammed mechanical linkage or fatigued spring4. Trapped pressure in piping, no pressure relief | 1. Test continuity after full depressurization2. Check differential scale and verify relief valve operation | 1. Reduce differential within published range2. Replace switch; add intermediate relay and RC snubber for inductive loads3. Clear piping to enable free pressure relief |
| Rapid cycling / chattering | 1. Differential (hysteresis) set too low2. Pulsating pressure from pump / compressor3. Insufficient accumulator volume or failed bladder4. Tapping point located in turbulent flow zone | 1. Observe pressure gauge for small fluctuations2. Check current differential setting | 1. Increase differential (XMLB max differential 7.5 bar)2. Fit pressure snubber or buffer tank on impulse line3. Relocate tapping point to straight pipe side wall |
| Trip pressure inconsistent, drifting between cycles | 1. Spring fatigue from repeated pressure shock2. Permanent diaphragm deformation by overpressure3. Extreme temperature or continuous vibration4. Relying only on built-in scale without reference gauge calibration | 1. Compare trip/reset points over multiple cycles against certified gauge2. Check history of exceeding 22.5 bar instantaneous overload | 1. Recalibrate and log values with reference gauge2. Add vibration bracket and heat shielding3. Replace unit if drift persists |
| Intermittent signal loss, unstable contact | 1. Loose terminals or oxidized conductors2. Burned / carbonized microswitch contacts3. Water ingress and terminal corrosion from loose gland4. Internal wiring loose due to vibration | 1. Isolate power, open cover and retighten terminals2. Cycle and test continuity repeatedly | 1. Retighten terminals, clean or replace oxidized conductors2. Tighten Pg13.5 gland and check seal for IP663. Replace unit if contacts are burned |
| Media leakage from switch body | 1. PTFE tape trapped inside the thread and scoring diaphragm2. Diaphragm aging / incompatibility with process fluid3. Freeze damage, overtemperature or overpressure4. Cracked base from spanner on plastic housing | 1. Identify leak location: thread joint or housing seam2. Verify process pressure and temperature are within ratings | 1. Re-seal correctly, apply tape only on male thread2. Select wetted material variant compatible with media3. Replace unit if base or diaphragm is damaged |
| Water ingress and internal rusting | 1. Missing or loose gland seal2. Aged cover gasket, unevenly tightened cover screws3. Outdoor installation with direct spray / UV exposure | 1. Open cover and inspect for standing water or oxidation | 1. Replace gasket, tighten cover screws evenly and compress gland seal2. Fit weather shield for outdoor use |
| Repeated contact burnout on power-up | 1. Direct switching of motors / contactors, exceeding contact ratingXMLB contact rating: AC-15 240V 1.5A, not for high-power loads2. Unsuppressed inductive arcing | 1. Check load current and separate control circuit from power circuit | 1. Use pressure switch to drive an intermediate relay only; relay switches the load2. Fit RC snubber across inductive coils |
✅ Standard Troubleshooting Sequence
- Process check: Confirm pressure, media and temperature are within rating; verify isolation and relief valves are open and impulse line clear
- Mechanical check: Leakage, vibration, mounting and tapping location
- Setpoint check: Verify trip and differential with certified reference gauge
- Electrical check: Isolate power, test dry contact continuity, check wiring and sealing
- Final decision: Replace complete unit if diaphragm, spring or microswitch fails. No spare internal parts are available for XMLB.
✅ Preventive Guidelines
- Install pre-filter for dirty media to protect diaphragm
- Quarterly calibration for safety interlock circuits; 6–12 months for standard compressor / water pump service
- Never apply spanner force to plastic housing; only grip the hexagonal base
- Use intermediate relay isolation for inductive loads to extend contact life
- Confirm wetted material compatibility: Standard XMLB uses FKM fluoroelastomer; special versions required for aggressive media
Telemecanique Nautilus / OsiSense XM Electromechanical Pressure Switch Series Overview
Note: XMLA / XMLB / XMLC / XMLD are current main diaphragm / piston pressure and vacuum switches. Legacy XM series (XMJ, XMG, XM2JM, XMP, FYG) are discontinued and only for cross-reference. Standard connection: G1/4 internal ISO228 thread, passive dry contact, control circuit duty, IP66
Model coding rule (XMLB010A2S11 example):
XML [Series] [Range] [Wetted Material] [Contact / Mechanism] [Electrical Entry] [Version]
S11 = Pg13.5 cable gland, screw terminals (XMLB010A2S11); S12=M20 gland; C11=DIN43650 connector
Series Comparison
| Series | Contacts | Differential | Key Feature | Typical Use |
| XMLA | 1CO | Fixed differential | Single setpoint, fixed hysteresis, cost-effective | Air compressors, simple alarm, single threshold protection |
| XMLB | 1CO | Adjustable differential | Single changeover, adjustable trip+reset, scale plate (your model) | Pump start-stop, compressor pressure regulation, lubrication & hydraulic systems |
| XMLC | 2CO | Adjustable differential | Two independent changeover contacts, dual adjustable setpoints | Separate low-pressure warning + high-pressure shutdown, interlock, pump/fan sequencing |
| XMLD | 2CO | Fixed differential | Dual independent switch elements, each with fixed hysteresis | Two independent fixed pressure thresholds, safety interlock |
| XMLAM / XMLBM | Vacuum | Fixed / Adjustable | Negative pressure vacuum switch, -1…0 bar | Vacuum handling, suction lines |
- XMLA (Fixed Differential, 1CO) Model List
| Model | Range (bar) | Remarks |
| XMLA002A2S11 | 0.25~2.5 | Low pressure air / water |
| XMLA004A2S11 | 0.4~4 | Water supply, HVAC |
| XMLA010A2S11 | 0.7~10 | General air compressor |
| XMLA020A2S11 | 1.2~20 | Hydraulic, medium pressure pneumatic |
| XMLA035A2S11 | 2.1~35 | Medium pressure hydraulic |
| XMLA070D2S11 | 4.5~70 | High pressure hydraulic |
| XMLA160D2S11 | 9~160 | High pressure hydraulic |
| XMLA300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLA500D2S11 | 30~500 | Ultra-high pressure hydraulic |
| XMLAM01V2S11 | -1~0 | Vacuum switch |
- XMLB (Adjustable Differential, 1CO, including XMLB010A2S11)
| Model | Range (bar) | Remarks |
| XMLB002A2S11 | 0.25~2.5 | Low pressure |
| XMLB004A2S11 | 0.4~4 | HVAC & water supply |
| XMLB010A2S11 | 0.7~10 | Your model, popular for compressors & pumps |
| XMLB020A2S11 | 1.2~20 | Medium pressure pneumatic / hydraulic |
| XMLB035B2S11 | 2.1~35 | Hydraulic power units |
| XMLB070D2S11 | 4.5~70 | High pressure hydraulic |
| XMLB160D2S11 | 9~160 | High pressure hydraulic |
| XMLB300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLB500D2S11 | 30~500 | Ultra-high pressure hydraulic |
| XMLBM02V2S11 | -1~0 | Adjustable vacuum switch |
- XMLC (Adjustable Differential, 2CO Dual Contacts)
| Model | Range (bar) | Remarks |
| XMLC004B2S11 | 0.4~4 | Dual signal output |
| XMLC010B2S11 | 0.7~10 | 10 bar dual contact, low / high pressure alarm |
| XMLC020B2S11 | 1.2~20 | Medium pressure dual output |
| XMLC035B2S11 | 2.1~35 | Hydraulic dual interlock |
| XMLC070D2S11 | 4.5~70 | High pressure dual contact |
| XMLC160D2S11 | 9~160 | High pressure hydraulic |
| XMLC300D2S11 | 16~300 | Heavy-duty hydraulic |
| XMLC500D2S11 | 30~500 | Ultra-high pressure hydraulic |
- XMLD (Fixed Differential, 2CO Dual Stage)
| Model | Range (bar) | Remarks |
| XMLD004B2S11 | 0.4~4 | Dual stage fixed hysteresis |
| XMLD010B2S11 | 0.7~10 | 10 bar dual stage protection |
| XMLD020B2S11 | 1.2~20 | Medium pressure dual stage |
| XMLD035B2S11 | 2.1~35 | Hydraulic safety interlock |
| XMLD070D2S11 | 4.5~70 | High pressure dual stage |
- Discontinued Legacy Models (Cross-reference only, not for new projects)
XMJ: Old single setpoint pressure switch, replaced by XMLA
XMG: Old adjustable differential switch, replaced by XMLB
XM2JM: Simple fixed differential auxiliary sensor
XMP / FYG: Old dual setpoint switch, replaced by XMLC
Most legacy XM series discontinued in 2002; stock only available in spare parts market. Prefer XMLB/XMLC for replacement.
- Electrical Suffix Cross Reference (Interchangeable for same range)
S11: Pg13.5 cable gland, screw terminals (XMLB010A2S11 standard)
S12: M20×1.5 cable gland, screw terminals
C11: DIN43650 square connector (solenoid valve style)
S13: Special extended housing version
- Wetted Material Code Definition
A: FKM fluoroelastomer (general: air, clean water, hydraulic oil, standard)
B: NBR nitrile rubber (mineral oil, not for hot water)
D: Stainless steel + FKM (hydraulic oil, elevated temperature hydraulic)
V: Vacuum grade sealing
- Quick Selection Guide
- Single trip point, fixed hysteresis → XMLA
- Adjustable start-stop differential (pump / compressor) → XMLB (XMLB010A2S11)
- Two independent alarm signals (low warning + high shutdown) → XMLC
- Two independent thresholds, no differential adjustment required → XMLD
- Negative vacuum pressure → XMLAM / XMLBM