Gateway Ethernet COMSOFT FNL-RS485

Gateway Ethernet COMSOFT FNL-RS485

COMSOFT FNL-RS485 Ethernet Gateway

  1. Basic Model Definition

Marca: COMSOFT, Alemanha (Original manufacturer of industrial fieldbus protocol gateways)

FNL: Fieldbus Network Link Fieldbus Gateway

RS485: DB9 connector for PROFIBUS DP (Not a standard Modbus-RS485 serial server)

Posicionamento do produto: DIN-rail mounted protocol conversion gateway between Ethernet TCP/IP and PROFIBUS DP

  1. Interfaces de Hardware & Pin Definitions

2.1 Front Panel Interface Layout

  1. RJ45 10/100M Ethernet Port (ETH)
  2. DB9 Male PROFIBUS DP RS485 Bus Port
  3. Terminal Block DC24V Power Supply
  4. RS232 Service Port (For configuration and firmware upgrade)
  5. Indicadores de status: PWR, ETH LINK, BUS, ERR

2.2 Standard PROFIBUS DB9 Pinout

Pino Não.SinalDescrição
3B (Rx/Tx-)Data Negative
8UM (Rx/Tx+)Data Positive
65Em DCPower supply for bus terminating resistor
50VIsolated Ground

2.3 Power Specifications

DC 24V ±20%, power consumption ≤3W, proteção contra polaridade reversa; DIN35 snap-on rail mounting.

  1. Core Protocol Functions (Two Operation Modes)

Mode 1: Gateway as PROFIBUS DP Master (Class1/Class2)

Host computers, PLCs or touch panels on the Ethernet side read all I/O data of DP slaves via Modbus TCP.

Supports complete DP/DPV1 protocols with baud rates ranging from 9.6 kbps para 12 Mbps

A single DP bus supports up to 32 slave devices, compatible with inverters, encoders, remote I/O modules and transmitters

Automatically maps DP input/output areas to Modbus TCP holding registers without manual offset conversion

Supports FDT/DTM device diagnosis and reading of DP slave fault codes

Mode 2: Gateway as PROFIBUS DP Slave

Siemens S7-300/400/1500 DP master PLCs connect to Ethernet Modbus TCP devices (IoT platforms, SCADA systems, host computers) via the FNL gateway.

Three Communication Services on the Ethernet Side

  1. Modbus TCP Slave (Mais comumente usado): Third-party systems directly read and write PROFIBUS data
  2. Transparent TCP Socket Transmission: Secondary development with C/Python/LabVIEW to send and receive raw PROFIBUS messages
  3. Web Configuration Page: Modify IP address, bus parameters, I/O mapping and perform fault diagnosis via web browser
  4. Key Electrical & Especificações Ambientais
ItemEspecificação Técnica
Isolamento ElétricoGalvanic isolation between Ethernet and PROFIBUS to resist interference from inverters
Ethernet10/100M Base-T, DHCP/IP estático, auto MDI/MDI-X
Temperatura operacionalIndustrial wide temperature range: -20℃ ~ +70 ℃
Terminating Resistor120Ω resistor must be enabled at both ends of the DP bus (via DIP switch on DP connector)
CertificaçõesCE, UL industrial certifications
Código HS853810 (Electrical control components)
  1. Supporting Configuration Software – CONFIGURATOR II
  2. Windows compatible (Win7/10/11, .NET Framework required)
  3. Principais Funções:

Scan all FNL gateways in local area network and modify IP addresses

Import GSD files to construct PROFIBUS bus topology

Configure DP master/slave mode, baud rate and cycle time

Visual mapping between DP I/O areas and Modbus TCP registers

Online diagnosis of bus faults, offline slaves and communication error counters

  1. Supporting FDT DTM: Integrate with TIA Portal, EPLAN and Anybus toolchains for device asset management
  2. Typical Application Topologies

Cenário 1: Retrofit for Host Computers Without PROFIBUS Cards

computador / SCADA Software (Modbus TCP) → Switch → FNL-RS485 (DP Master) → PROFIBUS DP Inverters / Módulos de E/S

Cenário 2: Siemens DP PLC Connecting to IoT Platforms

S7-300 DP Master → FNL-RS485 (DP Slave) → Ethernet → Industrial Gateway / Cloud Platform

Cenário 3: LabVIEW Automated Testing

LabVIEW TCP Socket → FNL Gateway → PROFIBUS Test Bench Equipment

  1. Matriz de solução de problemas
Fenômeno de falhaCausa raizSolução
PWR indicator offSubtensão / reversed polarity of 24V power supplySwap positive and negative power lines; measure actual voltage ≥19V
Flashing BUS indicator & intermittent communicationReversed A/B wiring; no terminating resistor on busSwap Pin 3 e fixar 8 of DB9 connector; enable 120Ω resistors at both bus ends
Gateway undetected by PCMismatched IP subnet; damaged Ethernet cableSet static IP on PC within the same subnet; replace cable and restart gateway
Failed Modbus TCP data readingIncorrect I/O mapping address; offline DP slaveVerify I/O mapping in software; troubleshoot DP bus power supply section by section
Steady red ERR indicatorShort circuit on DP bus; inconsistent baud rates among devicesDisconnect bus for sectional troubleshooting; unify baud rate for all devices
  1. Model Differentiation Within the Same Series
  2. FNL-RS485: General-purpose gateway for conversion between Ethernet and PROFIBUS DP (RS485)
  3. FNL-PA: Gateway for conversion between Ethernet and PROFIBUS PA (Intrinsically safe fieldbus)
  4. FNL Proxy PN/PB: Conversion gateway between PROFINET IO and PROFIBUS DP
  5. Domestic Compatible Alternative Solutions
  6. Anybus AB7000 Series (Ethernet to PROFIBUS DP Gateway)
  7. Hongke HK-PB-ETH Economical DP-to-Ethernet Gateway