ABB E1N16-R1600-PR121-LSI

ABB SACE Emax E1 Series Fixed-type Air Circuit Breaker, rated current 1600A, equipped with PR121/P microprocessor-based electronic trip unit and three-stage LSI protection function. Model Code Definition Segment Code Description E1N E1N Series identifier for ABB SACE Emax E1 fixed ACB; E1=series code, N=fixed mounting, B=draw-out mounting 16 16 Incoming frame current rating: 1600Um quadro ...

  • Detalhes do produto

ABB SACE Emax E1 Series Fixed-type Disjuntor de ar, rated current 1600A, equipped with PR121/P microprocessor-based electronic trip unit and three-stage LSI protection function.

  1. Definição de código de modelo
SegmentoCódigoDescrição
E1NE1NSeries identifier for ABB SACE Emax E1 fixed ACB; E1=series code, N=fixed mounting, B=draw-out mounting
1616Incoming frame current rating: 1600A frame size (8=800A, 10=1000A, 12=1250A, 16=1600A)
R1600R1600Rated current code: In=1600A (R800=800A, R1000=1000A, R1250=1250A, R1600=1600A)
PR121PR121Trip unit model: ABB PR121/P basic microprocessor trip unit supporting LI/LSI protection
LSILSIProtection type for three-stage protection: L=Long time delay (sobrecarga), S=Short time delay (curto-circuito), I=Instantaneous (curto-circuito)

 

  1. Core Technical Specification Table
CategoriaParâmetros detalhadosPadrões & Certificações
Avaliações básicas• Product Series: SACE Emax E1CEI 60947-2
• Device Type: Disjuntor de ar (ACB)GB 14048.2
• Montagem: Tipo fixoCCC, CE, UL, CSA Approved
• Pólos: Optional 3P/4P
• Frame Current (Eu): 1600UM
• Rated Current (Em): 1600UM
• Trip Unit: PR121/P-LSI (3-proteção de palco)
• Rated Operational Voltage (Ué): 690V e, 50/60Hz
• Rated Insulation Voltage (interface do usuário): 1000V e
• Rated Impulse Withstand Voltage (Um): 12kV
• Ultimate Short-circuit Breaking Capacity (UTI): 50kA@415V AC, 42kA@690 Vca
• Rated Service Short-circuit Breaking Capacity (CIs): 50kA@415V AC (100% de UTI)
Mecânico & Desempenho Elétrico• Mechanical Endurance: 10,000 operaçõesCEI 60947-1
• Electrical Endurance: 500 operations at rated short-circuit breaking capacity
• Control Supply Voltage: 220V CA/CC (padrão), optional 110V/400V
• Operação: Motor spring charging + motor closing/tripping, manual emergency operation available
• Auxiliary Contacts: Padrão 2NO+2NC, expandable up to 10NO+10NC
• Wiring Capacity: Copper busbar 10×100mm², cable up to 300mm²
• Tightening Torque for Bolts: 50N·m
Physical Dimension• Montagem: Montagem vertical (padrão), optional horizontal mountingCEI 60529
• Overall Size(L×A×P): 296×302×418mm (3P fixed version)
• Peso: Approx.45kg (3P)
• Ingress Protection: IP30 for bare breaker, IP40 with enclosure
Condições ambientais• Operating Temp: -5°C ~ +40°C (desclassificação necessária acima de 40°C)CEI 60068-1
• Storage Temp: -25°C ~ +70°C
• Relative Humidity: 95% @25°C, sem condensação
• Pollution Degree: Aula 3
• Altitude: ≤2000m (derating required over 2000m elevation)
Eco & Sustainability• Compliant with EU RoHS DirectiveABB Green Product Certification
• PFOS/PFOA free construction
• Recyclable material ratio ≥90%
• Low power consumption: Control circuit ≤15W
  1. Full Part Number List (E1N Series, 1600A Frame Size)
Número da peça.DescriçãoCorrente nominalTipo de proteção
1SDA055782R1E1N1600 R800 PR121/P-LI800UMLI (2-estágio: Long Delay + Instantâneo)
1SDA055783R1E1N1600 R1000 PR121/P-LI1000UMLI
1SDA055784R1E1N1600 R1600 PR121/P-LI1600UMLI
1SDA055785R1E1N1600 R800 PR121/P-LSI800UMLSI (3-estágio: Long+Short+Instantaneous)
1SDA055786R1E1N1600 R1600 PR121/P-LSI1600UMLSI
1SDA055787R1E1N1600 R800 PR123/P-LSIG800UMLSIG (4-estágio + Earth Fault protection)
1SDA055788R1E1N1600 R1600 PR123/P-LSIG1600UMLSIG

Full Series Coverage: Frame ratings 800A/1000A/1250A/1600A; Fixo(N)/Extração(B) montagem; LI/LSI/LSIG protection; 3P & 4P configurations available.

  1. Equivalente entre marcas & Opções de substituição

4.1 In-brand ABB Replacement

Modelo originalModelo AlternativoSpecification Difference
E1N16-R1600-PR121-LSIE1B16-R1600-PR121-LSIDraw-out type for convenient maintenance, replaceable without power shutdown
E1N16-R1600-PR121-LSIE1N16-R1600-PR123-LSIGUpgraded to 4-stage LSIG with additional earth-fault(G) proteção
E1N16-R1600-PR121-LSIE2N16-R1600-PR121-LSIE2 higher-grade series, breaking capacity raised to 65kA@415V AC

4.2 Cross-Brand Comparison Chart

ABBSchneider ElétricaSiemensCHINT
E1N16-R1600-PR121-LSIMT16H1600 3P 5.03WL1116-3BB36-4AA0NA1-1600-1600M/3P
Quebrando Capacidade:50kA@415VQuebrando Capacidade:50kA@415VQuebrando Capacidade:50kA@415VQuebrando Capacidade:50kA@415V
LSI three-stage protectionLSI three-stage protectionLSI three-stage protectionLSI three-stage protection
PR121/P trip unitMicrológico 5.0 trip unit3WL electronic trip unitNA1 electronic trip unit
  1. Escopo de aplicação & Practical Cases

5.1 Recommended Application Fields

Setor IndustrialUso típicoVantagens de seleção
Distribuição de energia industrialMain incoming feeder of factory, proteção secundária do transformador, large MCC50kA alta capacidade de interrupção, precise LSI selective coordination for complicated industrial environment
Edifícios ComerciaisMain distribution panel for shopping mall, hotel & office towerSpace-saving fixed mounting, motorized operation for remote control & fácil manutenção
Centro de dadosUPS output & main power distribution for server roomLow power loss design, alta confiabilidade, capable of ATS interlock for redundant power supply
Infraestrutura CríticaMain protection for airport, metrô, hospital vital loadsWide working voltage to resist grid fluctuation, fast fault isolation to minimize blackout range
Nova Indústria de EnergiaLV side of step-up transformer in PV plant, combiner cabinet for energy storageExcellent harmonic withstand, customizable inverse-time protection curve matching new-energy characteristics

 

5.2 Aplicativos não recomendados

Circuitos CC: Select dedicated Emax DC series (e.g.E1N-DC)

Installation above 2000m altitude without current derating

Frequently switching loads: Adopt contactor + thermal overload relay combination instead

Severe environment with Pollution Degree 4: Extra enclosure protection required

5.3 Casos de aplicação típicos

Case1: Main Distribution for Automobile Manufacturing Plant

Aplicativo: Secondary-side main protection for 10kV/0.4kV factory transformer (1600UM)

Configuração: E1N16-R1600-PR121-LSI 3P fixed type with PR121/P-LSI trip unit

Desempenho: Realizes long-delay overload, short-delay & proteção instantânea contra curto-circuito; forms selective coordination with downstream MCCB to limit fault outage area and improve power supply reliability.

Case2: UPS Output Distribution in Large-scale Data Center

Aplicativo: Main protection for 2000kVA UPS outgoing terminal

Configuração: E1N16-R1600-PR121-LSI 4P fixed type plus communication module for remote monitoring

Vantagem: Low power consumption reduces UPS loading; optimized protection curve avoids unintended UPS tripping under short-circuit; communication function enables early fault alert & remote diagnosis.

  1. Common Troubleshooting Guide
Fenômeno de falhaRoot CausesRemedial Actions
Failed motor closing1.Abnormal control supply1.Measure input control voltage
2.Uncompleted spring charging2.Await automatic charging or manual charge
3.Bloqueio não liberado3.Check rack position & cabinet door interlock
4.Faulty closing coil4.Test coil resistance and replace defective component
Abnormal trip unit display1.Failed internal power module1.Check auxiliary supply for trip unit
2.Broken CT wiring2.Tighten or repair open-circuited CT connections
3.Trip unit program error3.Power cycle trip unit; contact ABB service if fault persists
Unintentional frequent tripping1.Overload or downstream short-circuit1.Measure load current and clear short fault
2.Incorrect protection setting parameters2.Re-calibrate protection setting for selective coordination
3.Temperatura ambiente excessivamente alta3.Improve cabinet ventilation & ambient cooling
4.Trip unit malfunction4.Verify trip performance or replace trip unit
Stiff manual operation1.Mechanism jamming by foreign matter1.Clean internal mechanism and reassemble
2.Fatigued operation springs2.Inspect charging/closing spring condition
3.Insufficient lubrication3.Apply specified lubricant per service manual

 

  1. Conformidade de Remessa Aérea & Certificações

7.1 Air Transport Regulation Compliance

Product Property: No built-in lithium battery/supercapacitor, classified as general electrical equipment

Shipping Classification: Non-dangerous goods compliant with IATA DGR regulations

Embalagem: Standard wooden case with inner cushion padding against mechanical damage

Transport Note: Precision device; avoid severe shock & vibration during transit

7.2 Main Certifications List

CertificaçãoCertificado Não.Valid Market
CCC2.02101E+15Mainland China
CE0123/CEUE & EEE
ULE250000América do Norte
CSA250000Canadá
RoHSComply with Directive 2011/65/EUGlobal environmental restriction of hazardous substances
  1. Regras de seleção rápida & Summary Tips

Regras de seleção rápida

  1. Frame Current Identification: Digit “16” =1600A frame; 8=800A,10=1000A,12=1250A
  2. Rated Current Lookup: Rxxx = nominal In; R800=800A, R1000=1000A, R1250=1250A, R1600=1600A
  3. Protection Code Definition: LI=2-stage, LSI=3-stage, LSIG=4-stage with earth fault
  4. Mounting Code: N = tipo fixo, B=Draw-out type
  5. Grau de Capacidade de Quebra: E1=50kA@415V; E2=65kA@415V