Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Chint NM1-800H/3300-800A MCCB - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

disjuntor/

Chint NM1-800H/3300-800A MCCB

CodeSignificado
Nm1Chint NM1 series molded case circuit breaker
800Frame current 800A
HHigh breaking capacity grade (Grade H, typically 50kA at 400V AC)
33003 postes, combined tripper (thermomagnetic tripping), no accessories
800UMRated current 800A

  • Detalhes do produto

Chint NM1-800H/3300-800A is a 3-pole, 800UM disjuntor em caixa moldada (MCCB) of the NM1 series, featuring H-grade breaking capacity and thermomagnetic tripping. It is designed for overload and short-circuit protection of power distribution lines, and suitable for industrial and large commercial power distribution trunk lines.

CodeSignificado
Nm1Chint NM1 series molded case circuit breaker
800Frame current 800A
HHigh breaking capacity grade (Grade H, typically 50kA at 400V AC)
33003 postes, combined tripper (thermomagnetic tripping), no accessories
800UMRated current 800A

Core Parameters

ParâmetroValue
Rated operating voltageAC 690V, 50Hz
Rated insulation voltage800V
Corrente nominal800UM
Capacidade de rupturaGrade H: 50o (400V e)
Pole number3P
Tripper typeTermomagnético (sobrecarga de longo prazo + short-circuit instantaneous protection)
Mounting methodTipo fixo, vertical/horizontal mounting available
Método de fiaçãoFront wiring (rear wiring and plug-in type optional)
Operation methodDirect handle operation
Executive standardGB 14048.2, CEI 60947-2, CCC certification

Cenários de aplicação

Overload and short-circuit protection for industrial power distribution trunks and power circuits in large workshops.

Protection for power distribution main trunks in commercial buildings (shopping malls, office buildings).

Protection for large motor circuits with infrequent starting.

Installation and Operation Key Points

  1. Installation shall comply with specifications; both vertical and horizontal mounting are acceptable, with secure fastening and good heat dissipation ensured.
  2. Check the specification of wiring terminals before wiring to match cables/bus bars for 800A current.
  3. Regularly inspect the action accuracy of the tripper to avoid the impact of ambient temperature on protection performance.

Cross-brand Replacement Reference

Schneider: NSX 800N/3P 800A (Verify breaking capacity and tripping curve).

ABB: Tmax T6N 800/3P 800A (Pay attention to mounting dimensions and accessory compatibility).

The core difference between Chint NM1-800H/3300-800A and NM1-800H/3200-800A lies in the tripper type and protection function; other basic parameters (frame current, capacidade de interrupção, pole number, etc.) are completely consistent.

  1. Core Difference: Meaning of “3300” e “3200” in the Model
Model PartDigital MeaningFunção de proteção
33001st digit 3 = 3 postes; 2nd digit 3 = combined tripper (thermomagnetic tripping); last two digits 00 = no accessoriesOverload long-time delay protection + short-circuit instantaneous protection
32001st digit 3 = 3 postes; 2nd digit 2 = magnetic tripper (magnetic tripping only); last two digits 00 = no accessoriesShort-circuit instantaneous protection only, no overload protection

This is the fundamental difference between the two circuit breakers, which directly determines their application scenarios and protection capabilities.

  1. Complete Parameter Comparison Table
ParâmetroNM1-800H/3300-800ANM1-800H/3200-800ARemarks
Tripper typeThermomagnetic combined trippingMagnetic trippingCore difference
Proteção contra sobrecarga Available (long-time delay)UnavailableO 3300 model achieves overload delay protection through the thermal bending of bimetallic strips
Proteção contra curto-circuitoAvailable (instantâneo)Available (instantâneo)Both realize short-circuit instantaneous tripping through electromagnetic coils
Frame current800UM800UMConsistent
Corrente nominal800UM800UMConsistent
Capacidade de rupturaGrade H (50kA@400V AC)Grade H (50kA@400V AC)Consistent
Pole number3P3PConsistent
Tensão nominalAC 690V, 50HzAC 690V, 50HzConsistent
Rated insulation voltage800V800VConsistent
Mounting methodTipo fixo (vertical/horizontal)Tipo fixo (vertical/horizontal)Consistent
Método de fiaçãoFront wiring (rear wiring, plug-in type optional)Front wiring (rear wiring, plug-in type optional)Consistent
Executive standardGB 14048.2, CEI 60947-2GB 14048.2, CEI 60947-2Consistent

III. Application Scenario Differences

ModeloCenários AplicáveisInapplicable Scenarios
3300• Industrial/commercial power distribution trunks (requiring both overload and short-circuit protection)• Special occasions requiring only short-circuit protection
• Large motor circuits (infrequent starting)• Dedicated circuits for fire-fighting equipment (3300 model with shunt trip is usually required for fire-fighting equipment)
• General lighting and power hybrid distribution systems
3200• Used as an isolating switch (needing short-circuit protection but no overload protection)• Used alone as power distribution line protection (lack of overload protection will cause line overheating and damage)
• Occasions matched with other overload protection devices (por exemplo, thermal overload relays)• Direct protection for motors (unable to prevent motor burnout due to overload)
• Special short-circuit protection for specific industrial equipment
  1. Sugestões de seleção
  2. Prioritize the 3300 modelo: Most power distribution scenarios require both overload and short-circuit protection; o 3300 model provides more comprehensive protection to avoid line overheating, equipment damage and other problems caused by overload.
  3. Select the 3200 model only under specific conditions: When the system is already equipped with other overload protection devices (por exemplo, thermal overload relays, overload alarms), o 3200 model can be used as a dedicated short-circuit protection circuit breaker to reduce costs.
  4. Observação: O 3200 model cannot be used alone for power distribution lines requiring overload protection due to the lack of overload protection, otherwise potential safety hazards may be caused.