Atuador elétrico de passo Danfoss ICAD600A 027H9065

Posicionamento do produto:Stepper electric actuator (power head) for Danfoss ICM motorized valves in refrigeration systems, old A-series, obsolete ✅ Basic Information Model:ICAD600A, Order code 027H9065 Brand:Danfoss (Refrigeration segment) Compatible valve bodies:ICM20 / ICM25 / ICM32 motorized regulating valves, also capable of driving CVE pilot valves Construction:Stepper motor driven, with valve position feedback, local keypad & mostrar, ...

  • Detalhes do produto

Posicionamento do produto:Passo a passo electric actuator (power head) para Danfoss ICM motorized válvulas in refrigeration systems, old A-series, obsoleto

✅ Informações Básicas

Modelo:ICAD600A, Order code 027H9065

Marca:Danfoss (Refrigeration segment)

Compatible valve bodies:ICM20 / ICM25 / ICM32 motorized regulating valves, also capable of driving CVE pilot valves

Construção:Stepper motor driven, with valve position feedback, local keypad & mostrar, manual override function

Origem:Polônia

📌 Especificações elétricas principais

Fonte de energia:24Em DC (+10% / -15%), DC power only

Max current:1.2 UM

Control signals:

Entrada analógica:0/4-20 mA, 0/2-10 Em DC

Saída analógica:0/4-20 mA (feedback da posição da válvula)

3-channel NPN digital outputs (valve position status, falta, etc.)

Passive dry contact digital input

Classe de proteção:IP67

Temperatura ambiente:-30 ℃ ~ +50 ℃

Habitação:Aluminum body + PBT top cover, net weight approx. 1.2 kg

Connectors:M12 circular connector (4-pin power + 8-pin signal). Pre-assembled cables available as options: 027H0426 (1.5eu), 027H0438 (3eu), 027H0427 (10eu), 027H0435 (15eu)

🧩 Control Modes

  1. Analog modulation:Continuous regulation via EKC347 level controller or PLC with 4-20mA / 0-10Saída V
  2. Digital position control
  3. Local panel manual open, close and calibration
  4. Compatible with ICAD-UPS power-fail hold module for safe position protection upon power loss

🔁 Opções de substituição (Seção principal)

Factory successor:ICAD600B (Número do pedido. 027H0485). Mechanically interchangeable, upgraded with OLED screen, Bluetooth APP and RS485 communication. No entanto, wiring logic and parameter programming need verification and adaptation; direct blind replacement is not permitted.

Similar obsolete parts within the same series:027H9075 (ICAD600A, identical hardware to 027H9065, only version/config difference, also obsolete)

⚠️ Fault & Notas de manutenção

Falhas comuns:Loss of communication, valve position non-following, parada do motor, blank display, entrada de água & oxidation at M12 connectors

Calibração:Full zero & full stroke auto-calibration must be performed after replacement or disassembly

Importante:24V AC must NOT be applied directly. A dedicated isolated 24V DC power supply is required; voltage drop shall be calculated for long wiring runs

📎 Application Scope

Industrial ammonia refrigeration, CO₂ transcritical systems, large fluorinated refrigerant chiller packages, used for continuous regulation of liquid level, pressure and superheat (pump recirculation, evaporator, condenser, economizer circuits)

📋 Supporting Documentation

Manuals:AI000086409336 (General ICAD600/900 manual), AN000086415021 (Fiação & commissioning manual)

ICAD600A (027H9065) → ICAD600B (027H0485) Retrofit Checklist

Conclusão central:Mecanicamente compatível, fits directly on existing ICM20/25/32 valve bodies. But M12 pin assignment, parameter menu and fault logic differ; the old cable cannot be plugged in and powered up directly.

  1. Lista de materiais
CategoriaItemObservações
Unidade principalICAD600B, Número do pedido. 027H0485Replaces 027H9065, compatible with ICM20/25/32
Optional pre-made cable027H0426 (1.5eu) / 027H0438 (3eu) / 027H0427 (10eu)B-series dedicated M12 power + M12 signal cable. Old A-series cables have different pinouts and reuse is not recommended
UPS power-fail hold027H0388 ICAD UPS moduleCompatible with A & B; B has revised logic for UPS detection pin
ConsumíveisMolycote 55 graxa, O-ringsFor valve stem magnetic coupling seal; lubrication mandatory after disassembly to prevent water ingress failure
Ferramentas2.5mm hex key, chave dinamométrica, multímetro, fita isolanteInstallation torque: 3N caminho m, tighten diagonally and evenly
  1. Mechanical Retrofit (Low Risk)

✅ Compatibility:Valve seat, magnetic coupling and mounting screw positions match completely; no modification to valve body or bracket required

⚠️ Operating Procedure

  1. Manually set valve to mid-position first (to prevent valve stem detachment after actuator removal)
  2. Loosen the 3 fixing hex screws and lift the old ICAD600A vertically
  3. Inspect magnetic coupling and O-rings on valve body for damage, ice buildup or heavy contamination; remove old grease residue
  4. Apply Molycote 55 to O-ring groove and O-ring, align magnetic coupling and lower ICAD600B vertically
  5. Tighten the 3 screws diagonally at a controlled torque of 3N·m; avoid one-sided over-tightening
  6. Verify housing sealing surface is fully seated without warping

Pontos de risco:Misaligned magnetic coupling or missing grease → water ingress, magnetic coupling slip and valve position drift later

  1. Electrical Retrofit (Crítico! Pinout Incompatibility, Highest Risk Area)

ICAD600A:M12 power 3-pin; M12 signal 7-pin

ICAD600B:M12 power 4-pin; M12 signal 8-pin; independent 4-pin M12 RS485 port exclusive to B-series

4-pin M12 Power Connector (B)

Pin I Black:Fail-safe 19-24V DC (UPS backup power, opcional)

Pin II White:Main 24V DC+

Pin III Brown:24Em DC(GND)

Pin IV Blue:UPS status feedback signal (Not available on A-series)

8-pin M12 Signal Connector (B)

Pin A Black:Common terminal for fault output (NPN)

Pin B Brown:Fully open limit output

Pin C Red:Fully closed limit output

Pin D Orange:Signal GND

Pin E Yellow:Entrada analógica (0/4-20mA /0/2-10V)

Pin F Pink:Analog feedback output (valve position 0/4-20mA)

Pin G Grey:Digital input DI (Habilitar / Safety close)

Pin H Violet:Reservado

Comparison with A: Wire color sequence for digital outputs and analog input differs. Direct plug-in of old cable will burn signal channels or trigger faults.

✅ Two implementation options:

Opção 1: Purchase factory pre-assembled B-series cables, re-terminate wiring at cabinet terminals one-to-one (Recommended for reliable site performance)

Opção 2: Rewire existing cable, re-crimp M12 contacts according to above definition and apply clear marking

Power requirement remains 24VDC SELV isolated power supply, max 1.2A, same as A-series; 24V AC is not supported.

  1. Hospedar / Controller Program Modification (EKC347 / CLP)
  2. Analog control loop (4-20mA control)

Control signal range: 0/4-20mA, 0-10V definition unchanged. B internal input resistance differs; range setting on PLC/EKC side can stay, but valve position feedback reading calibration is recommended.

UM: Valve feedback 4-20mA; B also 4-20mA with improved load capacity up to 500Ω

  1. Digital position signals (Full open, Full close, Falta)

All three are NPN open-collector outputs with identical function definition. Common terminal pin has changed; PLC input common point wiring must be adjusted accordingly.

  1. Existing EKC347 parameters:

Superaquecimento, liquid level setpoints and PID gains can be retained

Valve body model must be reselected inside B actuator (parameter i26). B will automatically calibrate stroke

  1. RS485 (New for B): Not required if original system has no bus. If bus communication is planned later, Modbus mapping and terminating resistor need to be added.
  2. Comissionamento & Calibration Procedure (Obrigatório, Skipping Causes Position Error)
  3. Double-check wiring, power on without load first, check OLED screen (B uses OLED, A uses segment LCD)
  4. Entrar no menu de parâmetros, set valve body type: ICM20/25/32 (i26) → trigger automatic stroke calibration
  5. Calibration sequence: Auto full close → full open → full close, zero and full stroke recorded
  6. Manual mode test: Abrir / close via local panel, confirm smooth movement without sticking
  7. Auto mode: Apply 4mA / 20mA reference signal, verify linear tracking of valve position feedback
  8. Simulação de falhas: Signal loss, perda de energia, check fault output and UPS safe position logic
  9. Save parameters and back up configuration (B supports Bluetooth APP commissioning via Danfoss BT tool)

Importante:A-series fault code list cannot be used for B; B alarm system is revised and some alarm definitions are different.

  1. Risk Checklist & Evitar armadilhas
  2. ❌ Plug old A cable directly into B: Pin misalignment → burnt analog channels, power short circuit, A1/A2 alarms
  3. ❌ Skip calibration before commissioning: Deriva zero, incomplete closure or incomplete opening
  4. ❌ Omit Molycote 55 aplicativo: Magnetic coupling water ingress, slip and position loss at low temperature
  5. ❌ Ignore blue UPS pin: Continuous UPS fault alarm on B if blue wire is not connected when UPS module is fitted
  6. ❌ Torque over 3N·m: Housing deformation and seal failure
  7. Acceptance Test Items

Estático: Valve position 0%, 50%, 100%, feedback error ≤±2%

Dinâmico: Step response test, no oscillation or sticking

Fault conditions: Quebra de fio, perda de energia, parar; controller receives fault signal correctly

Proteção ambiental: IP67, proper connector sealing, no condensation ingress in humid conditions

Recurring Faults after ICAD600A (027H9065) → ICAD600B (027H0485) Substituição, Causas & Solução de problemas

Premissa: Most issues originate from incorrect pin wiring, missing calibration, UPS logic difference, impedância / load mismatch. Mechanical seizure of valve body is a pre-existing condition, not a new fault introduced by replacement.

  1. Falhas de inicialização (Alarm at power-up, sem exibição, cyclic reboot)
  2. Blank OLED, no illumination

Causa: Wrong M12 power pin assignment, reversed 24VDC polarity, capacidade de energia insuficiente, queda excessiva de tensão, entrada de água & oxidation at M12 plug

Solução de problemas: Measure Pin II(+) & III(-) with multimeter; confirm DC24V not AC24V; measure voltage at actuator end for long cable runs

  1. Cyclic reboot & flashing screen after power-up

Causa: Blue UPS Pin IV left floating without connection; old A-type UPS module mismatched; high ripple power supply

Remédio: Disable UPS detection in menu if UPS module is not used; do not leave pin floating and tolerate constant alarm

  1. Power fault alarm immediately after energization (B exclusive alarm)

Causa: Forced reuse of old cable, cross connection between power and signal lines, internal short in connector

  1. Calibration Related Faults (Most frequent after swap)
  2. Auto-calibration aborted, stops mid-cycle, stroke error alarm

Triggers:

Misaligned magnetic coupling, coupling slip, O-ring binding; valve stem offset during assembly

Contamination, ice plug or spool seizure in valve body (A may tolerate marginal friction while B has tighter detection)

Incorrect mounting torque (over-tightened coupling or insufficient torque leading to slip)

Wrong valve body selection at parameter i26 (selected larger ICM size)

Sintoma: Calibration halts halfway and cannot complete full close → full open travel

  1. Calibration successful, but valve fails to close tight / viagem excessiva / cannot reach full open

Causa: Spool was not set to mid-position before calibration; worn seat, foreign debris, abnormal magnetic coupling gap

Recurso: 4mA command does not correspond to 0% feedback, 20mA cannot reach 100%

  1. Control Signal Loop Faults (4-20mA / 0-10V)
  2. Control signal applied, valve stationary, position reading fixed

Causa: Wrong connection at analog input Pin E; signal GND not common with controller GND; signal type mismatch (menu set for voltage while current signal is applied, ou vice-versa)

Key note: B input impedance differs from A; verify drive capability of EKC347 or PLC analog output

  1. Inaccurate / drifting feedback, feedback inconsistent with actual valve position

Causa: Wrong wiring at feedback Pin F; feedback loop overloaded resistance, loose GND connection, incomplete calibration

Sintoma: Controller reading differs from local actuator display

  1. Oscilação da válvula, small continuous hunting

Causa: PID parameters inherited from A; B stepper response speed differs; poor shielding earthing causing interference; signal cable routed together with power cable

Observação: PID tuned for A often oscillates directly on B and requires fine adjustment

  1. Digital Output Faults (Full Open / Full Close / Fault NPN)
  2. PLC fails to receive full-open / full-close signal or signal stays permanently ON

Causa: UM & B have different common terminal definition for digital outputs. Reused old cable leads to wrong common connection; reversed external supply for NPN loop

Critical point: B’s three DO channels share Pin A (fault common), which is completely different from A

  1. Persistent fault output with normal valve operation

High incidence: UPS detection enabled without UPS module fitted, B interprets status as UPS fault; UPS function not disabled in menu

  1. UPS Power-Fail Hold Specific Faults (with 027H0388 fitted)
  2. Fails to move to safe position on power loss or constant UPS alarm at startup

Causa: B blue Pin IV on power plug is UPS status feedback, which does not exist on A; legacy UPS wiring incompatible; aged UPS battery

Armadilha: A UPS only required power feed; B requires both power and status feedback wire otherwise permanent alarm

  1. Falhas de comunicação (Modbus RS485, New for B)
  2. No Modbus data read, intermittent communication

Causa: Wrong wiring on 4-pin M12 communication port; faltando resistor de terminação; endereço duplicado; taxa de transmissão incompatível; poor shield earthing

Dica: Bus port can be left unconnected if unused for analog control; avoid accidental signal connection to this port

  1. Baixa temperatura / Site Environmental Faults (Common for NH₃ & CO₂ transcritical systems)
  2. Random position loss and slip at low temperature without fixed alarm

Causa: Molycote 55 grease not applied during assembly; missing or damaged O-ring, moisture entering magnetic coupling and freezing

Recurso: Calibration passes at ambient temperature, random drift when cooled, temporary recovery after reboot

  1. Condensation inside connector, intermittent sporadic faults

Causa: Aged old M12 connector seal; poor crimp sealing after reworking cable, IP67 rating compromised

  1. Misleading Apparent Faults (Logic Difference, Not Actual Failure)
  2. Different valve movement at identical 4mA setpoint compared with A

Not a fault: B stroke algorithm, dead band and stepper speed parameters are independent; loop matching is required

  1. Alarm codes not found in A manual

B alarm table rewritten; many A alarm IDs do not exist on B

  1. Different local keypad operation logic

Menu navigation and manual mode entry sequence changed; commissioning personnel may mistake for actuator malfunction

  1. Fast Troubleshooting Sequence (On-site Priority)
  2. Verify every M12 pin assignment (poder, sinal, UPS) first to rule out miswiring
  3. Confirm power supply: Stable 24V DC, ≥22V at actuator terminals under load
  4. Check menu settings: Tipo de sinal (atual / tensão), valve body model i26, UPS enable / disable
  5. Run a complete auto-calibration again
  6. Check common ground and shield bonding, eliminate interference
  7. Test in manual mode alone to isolate whether fault lies in actuator hardware or upstream controller signal

Danfoss ICAD Stepper Electric Actuator Full Model & Order Code List (For ICM Refrigeration Valves)

Descrição: ICAD = Stepper motor actuator for ICM / ICMTS regulating valves and CVE pilot valves. Divided into A-series (velho, obsoleto), B-series (novo, ativo), TS transcritical dedicated variant. All models run on 24V DC.

  1. Série A (Velha geração, 027H9xxxx, Obsoleto)
ModeloCódigo do pedidoCompatible ValveObservações
ICAD600A027H9065ICM20/25/32Seu modelo atual, segment LCD, no RS485, no Bluetooth
ICAD600A027H9075ICM20/25/32Same ICAD600A, version variation
ICAD600A027H9120ICM20/25/32Mesma especificação
ICAD600A-TS027H9078ICMTS20~ICMTS80CO₂ transcritical dedicated
ICAD900A027H9101Large bore ICMTSCO₂ transcritical dedicated
ICAD1200A027H9077ICM40/50/65/100/125/150High torque A version
ICAD1200A027H9122ICM40/50/65/100/125/150Same ICAD1200A
  1. B-series (Atualmente ativo, 027H04xx, OLED + Bluetooth, optional RS485 / Ethernet)

ICAD600B (For ICM20 / ICM25 / ICM32)

ModeloCódigo do pedidoConfiguração
ICAD600B027H0485Mostrar, Bluetooth, RS485 (Mais comum, direct replacement for A)
ICAD600B027H0486Mostrar, Bluetooth, Ethernet
ICAD600B027H0488Sem exibição, Bluetooth, RS485
ICAD600B027H0489Sem exibição, Bluetooth, Ethernet

ICAD1200B (For ICM40~ICM150)

ModeloCódigo do pedidoConfiguração
ICAD1200B027H0490Mostrar, Bluetooth, RS485
ICAD1200B027H0491Mostrar, Bluetooth, Ethernet
ICAD1200B027H0492Sem exibição, Bluetooth, Ethernet
ICAD1200B027H0493Sem exibição, Bluetooth, RS485

ICAD600B-TS:CO₂ transcritical dedicated, separate order family for ICMTS valve bodies

  1. Acessórios & Cable Order Codes (ICAD compatible)
DescriçãoCódigo do pedidoObservação
ICAD UPS power-fail hold module027H0388Works with A & B (B has UPS status detection pin)
Pre-assembled cable 1.5m027H0426M12 power + M12 signal, B-series only
Pre-assembled cable 3m027H0438M12 power + M12 signal
Pre-assembled cable 10m027H0427M12 power + M12 signal
Pre-assembled cable 15m027H0435M12 power + M12 signal
M12 connector spare kit027H0430Signal plug spare part
Protective dust cap027H0431Top cover protection for actuator
  1. Referência de seleção rápida

ICM20 / ICM25 / ICM32 → ICAD600A (Obsoleto) / ICAD600B (Substituição)

ICM40~ICM150 → ICAD1200A (Obsoleto) / ICAD1200B (Substituição)

ICMTS (CO₂ transcritical) → ICAD600A-TS / ICAD900A / ICAD600B-TS

  1. Notas Críticas
  2. All A-series (027H9xxx) foram descontinuados. B-series is preferred for replacement. Mechanically interchangeable, pin assignment incompatible; old cable must not be plugged directly.
  3. B-series: RS485 variant widely used for site retrofit; Ethernet variant for building automation and remote SCADA
  4. TS variants have special internal seals and firmware tuned for CO₂ transcritical operation; standard ICAD600B cannot substitute directly
  5. All ICAD actuators run on 24V DC. 24V AC supply is strictly prohibited