Sensor de pressão de uso geral OMRON E8EB-10C - Contator,disjuntor,sensor,Codificador,CLP,Conversor

Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Sensor de pressão de uso geral OMRON E8EB-10C - Contator,disjuntor,sensor,Codificador,CLP,Conversor

CLP/

Sensor de pressão de uso geral OMRON E8EB-10C

Tipo de produto: Integrated Pressure Sensor (Pressostato) | Status: Discontinued by Manufacturer Omron E8EB series integrated pressure sensor with analog + switching output, positive pressure type, Saída NPN. ✅ Core Specifications Pressure Range: 0~1 MPa (0~10 kgf/cm², 0~142 psi) Fonte de energia: DC24V Switch Output: Coletor aberto NPN; Máx.. corrente de carga 80 mA, Máx.. voltage DC30V ...

  • Detalhes do produto

Tipo de produto: Integrado Sensor de pressão (Pressostato) | Status: Descontinuado pelo fabricante

Omron E8EB series integrated pressure sensor with analog + switching output, positive pressure type, Saída NPN.

✅ Especificações principais

Faixa de pressão: 0~1 MPa (0~10 kgf/cm², 0~142 psi)

Fonte de energia: CC24V

Saída do interruptor: Coletor aberto NPN; Máx.. corrente de carga 80 mA, Máx.. voltage DC30V

Linear Analog Output: 1~5 V, Output impedance 20Ω, Mínimo. load resistance 10 kΩ

Tempo de resposta: ≤5 ms

Consumo Atual: 20 mA

Pressure Port: RC(PT)1/4

Classe de Proteção: IP54

Temperatura operacional: -10℃~+55℃ (sem glacê); Armazenar: -25℃~70℃

Indicador: LED vermelho (lights up when output is ON)

Cabo: Fio condutor padrão de 2m

Mídia: Dry air, non-corrosive gas (Not suitable for corrosive liquid)

📌 Explicação do código do modelo (E8EB Series)

E8EB = Series Code

10 = Range 0~1MPa

C = NPN output; Suffix B = PNP (Model E8EB-10B)

01 = 0~0.1MPa; N0 = Vacuum type

🔁 Official Replacement Model: E8F2-B10C

ItemE8EB-10C (Modelo Antigo)E8F2-B10C (Substituição)
Faixa de pressão0~1MPa0~1MPa
SaídaColetor aberto NPN + 1~5V linear analogNPN, dual independent switch outputs + 1~5V linear analog
Consumo Atual20mA70mA
Corrente de carga80mA30mA
AjustePotentiometer adjustment, no digital displayVisor digital + bar graph, one-touch teaching setup
Dimensões de montagemDifferent footprint and mounting holesCannot be plug-and-play; bracket and piping need modification

⚠️ Aviso importante: Direct plug-in replacement is NOT feasible. Capacidade de carga, current draw and mounting dimensions differ; PLC wiring logic must be verified.

🧾 Pin Assignment (4-Core Cable)

Marrom: CC24V+

Azul: 0V (GND)

Branco: ON/OFF Switch Output (NPN)

Preto: 1~5V Linear Analog Output

🛠️ Troubleshooting Checklist

  1. Sem saída: Check 24V supply and blue wire ground; confirm pressure exceeds set threshold
  2. Abnormal analog signal: Load resistance ≥10kΩ; low-resistance loads are prohibited
  3. LED não acende: Pressure not reaching actuation point, or incorrect hysteresis setting
  4. Desvio de sinal: Water/oil contamination in air source, out-of-range temperature, or pressure surge exceeding full scale

📎 Supplementary Information

Usado / second-hand units are still available on the aftermarket; no brand-new original stock

Referência do Código HS: 90262090 (Gas pressure measuring sensor)

Modelos Alternativos: E8F2 series, E8CC series digital pressure sensors

E8EB-10C → E8F2-B10C Retrofit Wiring List (4-core old → 5-core new)

E8EB: 4-essencial; E8F2-B10C: 5-essencial (dual switch outputs + 1~5V analog), NPN, 0~1MPa, CC24V

Goal: Retain the original circuit: 1 switch signal + 1~5V analog; leave the second output unused and insulated.

  1. Wire Color Matching Table
E8EB-10C (Velho, 4-Essencial)FunçãoE8F2-B10C (Novo, 5-Essencial)FunçãoConnection Plan
MarromCC24V+MarromCC24V+✅ Direct connection
Azul0V GNDAzul0V GND✅ Direct connection
BrancoSwitch Output OUT1 (NPN)Branco (SAÍDA1)Saída do interruptor 1 (NPN)✅ Connect to original PLC input point (keep original pressure signal logic)
Preto1~5V Analog SignalCinza1~5V Analog Output✅ Original black wire → new grey wire
-N / DBranco (SAÍDA2)Independent Switch Output 2 (NPN)⚠️ Leave unused, wrap with insulation; short-circuit strictly forbidden

Lembrete crítico: The analog output on E8F2 is the grey wire NOT the white wire, this is the most common wiring mistake. If analog signal is not required, insulate the grey wire separately.

  1. Wiring Procedure
  2. Cut off all power; confirm PLC and sensor power circuits are fully de-energized
  3. Disconnect old sensor terminals and record Brown/Blue/White/Black channel mapping
  4. Circuito de energia: Brown to Brown, Blue to Blue (Alimentação DC24V)
  5. Switch signal: Original white wire → E8F2 OUT1 white wire (match original PLC logic)
  6. Sinal analógico: Original black (1~5V) → E8F2 grey wire
  7. E8F2 OUT2 white wire: Seal with heat-shrink tube/insulation tape, keep isolated
  8. Inspect wiring for short circuits and exposed copper before powering on.
  9. Parameter Differences & PLC Program Verification Checklist (Obrigatório)
ItemE8EB-10CE8F2-B10CRetrofit Risk Point
Current Draw20mA70mARecheck 24V power supply capacity; insufficient margin will cause voltage drop
Switch Load Capacity80mA30mAPLC digital input is fine; if the original circuit drives a relay directly, the relay cannot be reused; reduzir a corrente de carga
Thread PortRC(PT)1/4R(PT)1/8Must install reducing adapter; cannot thread directly
MontagemOriginal bracket28painel mm / E89-F3 bracketHole positions do not match; new holes or adapter plate required
Método de configuraçãoPotentiometer adjustmentMenu / teaching setupPressure setpoints and hysteresis must be reconfigured; old potentiometer values are invalid
Canais de saídaSingle switchTwo independent switchesProgram only uses OUT1; disable OUT2
  1. Power-On Commissioning Sequence
  2. No-load power-on first; confirm E8F2 digital display lights up normally
  3. Entrar no cardápio: Set actuation mode, pressure setpoint and hysteresis to match the original E8EB values
  4. Pressurize and test: Verify OUT1 triggers PLC input correctly
  5. Analog test: 0MPa ≈1V, 1MPa≈5V; confirm linear reading on PLC analog channel
  6. Stabilize signal: Enable anti-chatter filter to prevent false triggering caused by air pressure fluctuation.
  7. Solução rápida de problemas

No analog reading: Grey wire disconnected or misconnected to OUT2 white wire

Cannot drive load: Load current exceeds 30mA rating

Nenhuma ação de comutação: Parameters not reconfigured; factory default values differ from old sensor

Vazamento de ar: Thread mismatch; missing reducing adapter

Full Commissioning Procedure: E8EB-10C Upgrade to E8F2-B10C (Match Original System Logic)

Objetivo: OUT1 replaces the old E8EB switch point; grey wire 1~5V analog keeps the original PLC analog channel; OUT2 remains unused.

Botões: DEFINIR (Confirm/Enter), Up ▲, Down ▼; Press and hold SET for 2s to enter main menu; short press SET for pressure setting.

Etapa 1: Verificação pré-energia (Prevent PLC Input Burnout)

  1. Verifique a fiação: Marrom=24V+, Azul=0V, White=OUT1, Grey=Analog, OUT2 white wire fully insulated
  2. Load check: E8F2 NPN output max. 30mA. Do not drive relays directly. Add an intermediate relay if the old circuit had a relay load
  3. Piping: Install PT1/8 to PT1/4 reducing adapter with thread sealant; test for air leakage before commissioning
  4. Air source: Use dry compressed air free of excessive water and oil; working pressure cannot exceed 1MPa full scale
  5. Lado do CLP: Analog input impedance ≥10kΩ; low-resistance loads are prohibited.

Etapa 2: No-Load Power On & Redefinição zero (Zero Pressure Condition)

  1. Power the sensor alone, without air pressure applied, wait for display stabilization
  2. Zero point reset (zero pressure calibration): Press ▲+▼ simultaneously to reset zero reading

Observação: Zero reset must be done at zero pressure; calibration under pressure will lead to permanent drift.

Etapa 3: Basic Parameter Setup (Hold SET 2s to enter main menu)

  1. Unidade (unt): Select MPa (consistent with old sensor; kPa is also acceptable)
  2. Modo de operação (m-a): Select HYS (Hysteresis Mode, same as E8EB); avoid Window Mode
  3. Lógica de Saída (ope): NPN, Normalmente aberto (NÃO); output ON when pressure exceeds set value
  4. Anti-chatter Filter: Set to STND (Padrão); select longer filtering if air pulsation is severe to avoid signal chattering
  5. Salvar: Hold SET 2s to return to measurement screen.

Only configure OUT1; leave OUT2 parameters unchanged as it remains unused.

Etapa 4: Pressure Setpoint Configuration (2 Opções: Manual Input / Teaching Mode; Teaching is Recommended)

Opção A: 2-Ensino de Ponto (Best for replicating old E8EB trigger points)

  1. Short press SET to enter pressure setting → select OUT1 → select 2-point teaching
  2. Slowly raise pressure to ON actuation pressure, stabilize and press SET to save the ON point
  3. Slowly reduce pressure to OFF release pressure, stabilize and press SET to save hysteresis OFF point
  4. Hold SET to save and exit.

Exemplo: Original E8EB turns ON at 0.5MPa and OFF at 0.4MPa; teach these two pressure values directly on site.

Opção B: Manual Value Entry (If original setpoints are known)

  1. Short press SET → enter OUT1 ON value → adjust value with ▲▼
  2. Press SET to switch to OUT1 OFF value → set hysteresis (DESLIGADO < SOBRE)
  3. Press SET again to jump to OUT2; skip without modification
  4. Hold SET to save and exit.

Recommended hysteresis: Keep consistent with original setting to avoid frequent cycling; factory default hysteresis = 3%FS (30kPa for 0~1MPa range).

Etapa 5: Switch Output Test (SAÍDA1, Entrada Digital CLP)

  1. Gradually increase pressure; check E8F2 OUT1 indicator + PLC input: ON when pressure ≥ setpoint
  2. Gradually reduce pressure; input turns OFF when pressure drops below OFF threshold
  3. Repeat 3 times to confirm:

No flickering or intermittent signal

Trigger action fully consistent with the old sensor

No premature or delayed switching

Solução de problemas: Frequent chattering → increase filter time and hysteresis; no action → reverse NO/NC output logic.

Etapa 6: 1~5V Analog Channel Calibration (Grey Wire, Etapa Crítica)

Faixa: 0~1MPa = 1V ~ 5V

0MPa: Theoretical output ≈1.0V

0.5MPa: Theoretical output ≈3.0V

1.0MPa: Theoretical output ≈5.0V

Etapas de comissionamento:

  1. Zero pressure: Confirm PLC analog reading ≈1V
  2. Pressurize to 0.5MPa and cross-check reading
  3. Full scale 1MPa: Verify output ≈5.0V

⚠️ Nota importante: E8F2 analog output is pre-calibrated for linearity. No re-calibration on PLC side is required. If deviation occurs, redo zero reset first and check load resistance.

Etapa 7: Full System On-Line Test (Automatic Machine Cycle)

  1. Switch equipment to automatic mode; verify pressure interlock and alarm logic work correctly
  2. Run continuously for 5~10 minutes; confirm output stays stable under pressure fluctuation
  3. Record actuation pressure, hysteresis and filter parameters in engineering change records
  4. Add pressure buffer/throttle on the air inlet if pressure surge occurs to prevent overpressure damage.

Etapa 8: Tabela de solução de problemas de falhas

SintomaCausa raizRemédio
OUT1 never switches ONON setpoint too high; NO/NC logic reversedRecheck set value; modify ope output mode
Switch signal flickers continuouslyAir source pulsation; tempo de filtro muito curtoExtend response filter; increase hysteresis value
Analog signal stuck fixed at 1VGrey wire broken/disconnected; load resistance too lowInspect grey wire; ensure PLC input resistance ≥10kΩ
Zero reading drifts constantlyZero reset performed under pressure; air contains water/oilRe-zero at zero pressure; install air filter for moisture removal
Output stays permanently ON after power-upOFF value set higher than ON value (parameter reversed)Ensure OFF pressure < ON pressure
PLC input channel burned outLoad current exceeds 30mA ratingRemove direct relay drive; add intermediate relay

Full Model List of OMRON General-Purpose Gas Pressure Sensors (Pneumatic / Compressor / Vácuo, Dry Air Only)

Observação: All models are Gauge Pressure. Saída: NPN/PNP switch + 1~5V analog. Split into Discontinued Legacy Models + Official Replacement Models, suitable for spare part replacement, BOM & foreign trade.

Definição de sufixo: C=NPN; B=PNP; A01=0~100kPa; B10=0~1MPa; AN0=Vacuum 0~-101kPa.

  1. E8EB Series (Sem exibição, ajuste do potenciômetro, DISCONTINUED)

4-core lead wire, RC1/4 thread, interruptor único + 1~5V analog; 20mA current draw, máx.. load 80mA.

ModeloFaixa de pressãoSaída
E8EB-01C0~100kPa (0.1MPa)NPN
E8EB-01B0~100kPa (0.1MPa)PNP
E8EB-10C0~1MPaNPN (Main Model in This Retrofit)
E8EB-10B0~1MPaPNP
E8EB-N0C2B0~-100kPa VacuumNPN
E8EB-N0B2B0~-100kPa VacuumPNP
  1. E8F2 Series (Visor digital, official replacement for E8EB/E8CC, DISCONTINUED)

5-cabo central, PT1/8 thread, dual independent switch outputs + 1~5V analog; 70mA power consumption; single channel max. load 30mA; one-touch teaching programming.

ModeloFaixa de pressãoSaída
E8F2-A01C0~100kPaNPN (E8EB-01C Replacement)
E8F2-A01B0~100kPaPNP
E8F2-B10C0~1MPaNPN (Direct replacement for E8EB-10C)
E8F2-B10B0~1MPaPNP
E8F2-AN0C0~-101kPa VacuumNPN
E8F2-AN0B0~-101kPa VacuumPNP
  1. E8CC Series (Slim digital type, predecessor of E8EB, DISCONTINUED)

With digital display, interruptor único + 1~5V analog; Montagem em trilho DIN; replaced by E8F2.

ModeloFaixa de pressãoSaída
E8CC-A01C0~100kPaNPN
E8CC-B10C0~1MPaNPN
E8CC-AN0C0~-101kPa VacuumNPN
  1. E8MS / E8M Split Type (Sensor Head + Controlador, DISCONTINUED)

Pure 1~5V analog signal without built-in switch; requires E8M controller for multi-channel pressure acquisition.

ModeloFaixa de pressãoTipo
E8MS-010~100kPaPositive Pressure Probe
E8MS-100~1MPaPositive Pressure Probe
E8MS-N00~-101kPa VacuumVacuum Probe
E8MS-N1-101~101kPa Compound PressureCompound Pressure Transducer
E8M-100~1MPaE8M Independent Probe
E8M-N00~-101kPa VacuumVacuum Probe
E8M-A10~1000PaMicro Differential Pressure
  1. E8AA Series (Stainless Steel Diaphragm Special Model, DISCONTINUED)

Limited use for liquid / slightly corrosive gas applications.

ModeloFaixa de pressão
E8AA-M050~500kPa
E8AA-M100~1MPa
  1. E8Y / E8Y-L Micro-Pressure Sensors (Differential Pressure for Duct & Fã, Not General Pneumatic Type)

Pa-level low pressure (200Pa ~5kPa); some models with 4-20mA output; used for air duct and filter differential pressure monitoring only.

✅ Cross Reference Table (Spare Part Replacement Priority)

Modelo AntigoSubstituição recomendadaPrincipais diferenças
E8EB-01CE8F2-A01CPT1/8 thread, saídas duplas, load current reduced to 30mA
E8EB-10CE8F2-B10CFull retrofit plan covered above
E8EB-N0C2BE8F2-AN0CVacuum pressure type
E8CC-A01CE8F2-A01CDifferent mounting footprint

📌 General Notes

  1. Mídia: Dry non-corrosive air; Not for liquid or strong corrosive gas
  2. Analog Output Standard: 1~5V (1V at zero pressure, 5V at full scale)
  3. Thread Spec: E8EB = RC1/4; E8F2 = R1/8; reducing adapter is mandatory for retrofit
  4. Fonte de energia: CC24V
  5. All listed models are discontinued; apenas estoque excedente & unidades usadas disponíveis. New projects shall select the latest OMRON E8F series.

Anterior:

Deixe uma resposta

Deixe um recado