C2000 Mais (C2000) Alto desempenho Vector Inverter
✅ Explicação do código do modelo
VFD: Unidade de frequência variável
2800: Rated motor power 280kW
C: C2000 series
4: 3-phase 460V class (widely used for 380~480V power grids in domestic projects)
3: 3-saída de fase
UM: Código da versão (air-cooled, built-in DC reactor, sem unidade de frenagem embutida, sem filtro EMC integrado)
-00: Standard version suffix
📌 Core Electrical Specifications
Rated applicable motor: 280kW (375HP)
Entrada: 3-fase CA 380–480V, 50/60Hz
Serviço Pesado (alta definição) corrente de saída nominal: 550UM; Severe Heavy-duty (SHD): 460UM
Capacidade de sobrecarga (Serviço Pesado): 150% for 60s; 180% por 3s; Severe Heavy Duty mode: 150% for 60s, 200% por 3s
Classe de proteção: IP00 (cabinet-mounted type, must be installed inside an electrical control cabinet)
Integrado: Reator CC (padrão, harmonic suppression), CLP integrado (10K etapas), Torque seguro STO desativado
Not built-in: Braking chopper, Filtro EMC; braking unit and filter must be externally fitted
Control algorithm: FOC Field-Oriented Vector Control. Supports induction motor / motor síncrono de ímã permanente / synchronous reluctance motor, with PG encoder closed-loop and PG-less open-loop vector control.
🧩 Hardware & Estrutura
Frame code: H1, cabinet-type high-power unit
Método de resfriamento: Resfriamento por ar forçado
Comunicação: Modbus integrado; optional expansion cards: PROFINET, Ethernet/IP, CANopen, etc..
E/S: Muti-function digital input/output, analog 4–20mA / 0–10V; supports multi-speed, PID, master-slave parallel drive
🛠️ Cenários típicos de aplicação
Heavy constant-torque loads:
Large extruders, moinhos de bolas, equipamento de elevação, grandes trituradores
Grandes fãs & bombas de água, compressores, laminadores, main belt conveyors
Multi-motor synchronization, master-slave parallel drive
⚠️ Seleção & Pontos-chave de instalação
- This 460V model can be directly applied to domestic 380V power grids. Distinguish between heavy duty / light duty during selection. For 280kW heavy-duty loads, selection must be based on 550A current rating instead of power only.
- IP00 rating: Never install exposed outside cabinet. For dusty or humid sites, use independent air-conditioned control cabinets.
- Nenhuma unidade de frenagem integrada: External braking unit + braking resistor are mandatory for high-inertia or fast-stop applications.
- Standard DC reactor reduces line-side harmonics; an external EMC filter is required if EMC compliance is needed.
- Supports motor auto-tuning (stationary / rotating identification); parameter identification is required for permanent magnet motors.
🔁 Alternatives / Comparação de séries
Mesma série: C2000 Plus VFD2800C43A-00 (modelo atual)
Fluid dedicated alternative: CP2000 VFD2800CP43A (fã & pump variable torque, classificação atual diferente)
Versão refrigerada a líquido: C2000-R water-cooled model for high-dust and high-temperature environments
Alternativas domésticas: Inovação MD880, Invt GD800 series 280kW heavy-duty vector inverters
🚨 Common Fault Troubleshooting (C2000 High-power Models)
OCC: Curto-circuito de saída, quebra de terra do cabo, IGBT damage. For high-power units, prioritize checking output contactors and motor insulation.
AV: Excessive regenerative energy, missing braking unit; deceleration time is too short.
OL: Sobrecarga do motor, current transformer drift, inaccurate auto-tuning parameters.
OH: Blocked air duct, aged cooling fan, poor cabinet heat dissipation (highly frequent for high-power cabinet models).
LF: Output phase loss, loose cable terminals, enrolamento do motor quebrado.
Motor Auto-tuning Parameter List (VFD2800C43A C2000)
Applicable for Induction Motor (EU SOU); 05-00=1 Rotating Auto-tuning (Recommended when motor can be decoupled and rotated); 05-00=2 Stationary Auto-tuning (Used if motor cannot rotate)
Pre-requisite Nameplate Parameters Entry
| Parâmetro | Descrição | Value to Enter |
| 01-01 | Frequência nominal do motor | Motor nameplate Hz |
| 01-02 | Tensão nominal do motor | Motor nameplate V |
| 05-01 | Corrente nominal do motor | Motor nameplate A |
| 05-02 | Potência nominal do motor | Motor nameplate kW |
| 05-03 | Velocidade nominal do motor | Motor nameplate rpm |
| 05-04 | Número de pólos do motor | Pole count from motor nameplate |
Auto-tuning Mode Selection (05-00)
05-00=1: Rotating Auto-tuning (Dinâmico) [Preferido]
Decouple the motor from mechanical load; the shaft will rotate during operation. Automatically measures Rs, Rr, Lm, leakage inductance and no-load current. Highest vector control accuracy, suitable for extruders, moinhos de bolas, hoists and other heavy-duty equipment.
05-00=2: Stationary Auto-tuning
Used when the motor is coupled to load and cannot rotate. Only measures stator resistance Rs. Lower control accuracy than rotating auto-tuning; for emergency use only.
PM Permanent Magnet Motor: 05-00=4; Synchronous Reluctance Motor: 05-00=11
Auto-tuning Operation Steps
- Safety check: Desconecte a carga mecânica, ensure free rotation with no jamming, release brake, keep personnel away from drive shaft. For 280kW high-power units, verify output cable and motor insulation.
- Enter the above nameplate parameters.
- 00-10 Modo de controle: PG-less vector = 2; PG closed-loop =3.
- Set 05-00=1 (Rotating Auto-tuning).
- Press RUN on keypad; panel displays TUNE and auto-executes. Auto-tuning completes when TUNE disappears.
- Verify calculated results and check identified parameters:
05-05: Motor no-load current
05-06: Stator resistance Rs
05-07: Rotor resistance Rr
05-08: Magnetizing inductance Lm
05-09: Leakage inductance Lx
- Salvar parâmetros, power cycle the drive.
⚠️ Notes for failed rotating auto-tuning: Motor not decoupled, brake not released, overlong cables, mau isolamento, incorrect nameplate entries.
Master-Slave Parallel Drive Commissioning Steps (C2000 Multi-drive Parallel, Fiber Optic Parallel Scheme, VFD2800C43A)
Aplicativo: Dual / multi-motor coaxial drive (cinto, rolling mill, extrusora). Fiber optic parallel option card (acessório) supports torque sharing. Master receives speed command, slaves follow torque distribution.
Regra: Motor parameters and protection settings must be identical for master and slave drives. Only the master sends speed commands; slaves receive fiber synchronization signals.
Hardware Preparation
- Install C2000 fiber optic parallel communication card for each inverter; connect master to slave via fiber patch cords in daisy chain topology for multi-drive systems.
- Complete individual motor auto-tuning for each drive first (commission each unit standalone before parallel operation).
- Output contactors of master and slave must close simultaneously; asynchronous closing is forbidden.
- Fonte de energia: Separate incoming power or common DC bus. For common bus scheme, pay attention to DC bus voltage balancing.
Configuração de parâmetros
Mestre
- 00-62 = 1 (Master mode)
- 00-10 = 0 【Speed control mode, parallel function only supports speed mode】
- 00-17 Carrier frequency: ≤6kHz recommended for high power
- 00-64 = 8 (bit3=1, enable parallel start)
- Grupo 05 motor parameters filled according to motor nameplate; standalone auto-tuning completed
- Acceleration / tempo de desaceleração 01-12/01-13 set to match mechanical inertia
- Protection parameters (sobrecarga, sobrecorrente, sobretensão) identical to slave drives
- 00-62 = 2 (Slave mode)
- Grupo 05 parâmetros do motor, protection parameters and carrier frequency must match master exactly
- Command source: 00-21 = 6 (Fiber parallel command)
- Frequency reference: 00-20 = 9 (Fiber parallel reference)
- 11-00 =9 Enable master-slave torque distribution
Step-by-step Commissioning Procedure
- Individual commissioning: Master and slave run separately with decoupled load, complete auto-tuning, test no-load operation and confirm no faults and normal current.
- Desligar, wire fiber links, check firmware version of fiber card (view via 00-63).
- Input all master/slave parameters, power cycle all inverters.
- No-load linkage test: Run command to master, slaves start synchronously. Control no-load current difference within 5%.
- Gradual loading: Increase load step by step, monitor output current of both inverters. Alvo: Equal current sharing.
- Fine-tune torque compensation parameters (Grupo 11): Adjust 11-xx torque balance parameters when current deviation is large; avoid large modifications.
- Limit test: Full load and emergency stop test, check OV, OL faults. Confirm braking unit capacity for high inertia loads.
Common Master-Slave Parallel Issues
- Large current difference between two drives: Poor standalone auto-tuning, inconsistent motor parameters, loose fiber connectors, poor mechanical coaxiality.
- Startup jitter: Excessively high carrier frequency, reduce 00-17; acceleration/deceleration time too short.
- Fiber communication fault: Inspect fiber end face, fiber card, wiring sequence, do not swap Tx/Rx.
- Parallel function only supports speed mode, pure torque mode parallel is not supported.
Delta C2000 / C2000 Plus Full Model List [3-phase 460V VFDxxxxC43A] (Common for domestic projects, including VFD2800C43A)
Regra modelo: VFD + código de energia + C +4(460V)+3(3-saída de fase)+UM (air-cooled, built-in DC reactor, no built-in EMC, no built-in braking chopper, standard suffix -00)
Observação: C43E = same power with built-in EMC filter. Version A has no built-in EMC. D frame and above high-power models come with built-in DC reactor as standard.
✅ C2000 460V 3-phase VFDxxxxC43A Model List
| Modelo | Rated Power kW | Heavy-Duty HD Output Current A | Quadro |
| VFD007C43A | 0.75 | 2.5 | UM |
| VFD015C43A | 1.5 | 4.2 | UM |
| VFD022C43A | 2.2 | 6 | B |
| VFD037C43A | 3.7 | 8.5 | B |
| VFD055C43A | 5.5 | 13 | C |
| VFD075C43A | 7.5 | 17 | C |
| VFD110C43A | 11 | 25 | D |
| VFD150C43A | 15 | 32 | D |
| VFD185C43A | 18.5 | 38 | E |
| VFD220C43A | 22 | 45 | E |
| VFD300C43A | 30 | 60 | E |
| VFD370C43A | 37 | 72 | F |
| VFD450C43A | 45 | 91 | F |
| VFD550C43A | 55 | 110 | F |
| VFD750C43A | 75 | 150 | G |
| VFD900C43A | 90 | 180 | G |
| VFD1100C43A | 110 | 216 | G |
| VFD1320C43A | 132 | 260 | H |
| VFD1600C43A | 160 | 304 | H |
| VFD1850C43A | 185 | 370 | H |
| VFD2200C43A | 220 | 430 | H |
| VFD2800C43A | 280 | 550 | H1 |
| VFD3150C43A | 315 | 620 | H1 |
| VFD3550C43A | 355 | 680 | H1 |
| VFD4000C43A | 400 | 770 | H1 |
| VFD4500C43A | 450 | 860 | H1 |
| VFD5600C43A | 560 | 1040 | H1 |
📌 Derivative Sub-series within C2000 Family
- C2000-HS: High-speed dedicated version, max output frequency up to 1500Hz for high-speed spindles, model VFDxxxxC43A-HS
- C2000-R: Liquid water-cooled inverters for high dust and high heat environments, model VFDxxxxC43B-00R
- C2000 230V version (single/3-phase 220V): suffix C23A, rarely used for high power in China
- C2000 690V medium voltage version: suffix C63A for 690V grid, model VFDxxxxC63A
📋 Suffix Code Description (C43A models)
UM: Standard air cooling, sem filtro EMC integrado; small A/B/C frames have built-in braking chopper. D frame and above high-power models have no built-in braking unit.
E: Same power with built-in EMC filter (VFDxxxxC43E)
B: Updated hardware revision for some high-power models
-00: Standard factory version
⚠️ Selection Remarks
- Model coding note: In `VFD2800C43A`, 2800 = 280kW. The trailing two zeros are placeholders, not 2800kW, a common misinterpretation.
- Heavy-duty HD current is the core selection criterion. Do not select based purely on kW rating. For ball mills, guinchos, extrusoras, select according to heavy-duty current.
- H/H1 frame (≥132kW): IP00 cabinet installation, built-in DC reactor. Nenhuma unidade de frenagem integrada. External braking unit + resistor required for fast stop.