Schneider ATV650D30N4 Variable Speed Drive

(Altivar Process ATV650) Model code explanation: ATV650 = Altivar Process IP55 wall-mounted drive; D30 = 30 kW normal duty rating; N4 = 3-phase 380~480V, without integrated input disconnect switch (version with switch carries suffix E: ATV650D30N4E) ✅ Core Electrical Specifications Rated power: 30 kW normal duty / 22 kW heavy duty (40HP / 25HP) Fornecer: ...

  • Detalhes do produto

(Altivar Process ATV650)

Model code explanation: ATV650 = Altivar Process IP55 wall-mounted dirigir; D30 = 30 kW normal duty rating; N4 = 3-phase 380~480V, without integrated input disconnect switch (version with switch carries suffix E: ATV650D30N4E)

✅ Core Electrical Specifications
Potência nominal: 30 kW normal duty / 22 kW heavy duty (40HP / 25HP)
Fornecer: 3-phase 380…480V, 50/60 Hz
Corrente de saída, dever normal: 61.5 UM; heavy duty current: 39.2 UM (4 kHz carrier frequency)
Tamanho do quadro: Frame B (Frame B covers 30~45 kW range)
Enclosure rating: IP55, wall-mounted design for local field installation, no additional control cabinet required
Resfriamento: Resfriamento por ar forçado
Motores compatíveis: Asynchronous motors, synchronous reluctance motors
Filtro EMC integrado: Classe C2 (motor cable ≤50 m), Classe C3 (motor cable ≤150 m)

✅ Interfaces & Comunicação
Integrated Dual-port Ethernet (Modbus TCP) + Modbus RS485
E/S digitais: 8 DE, 3 configurable relay outputs
E/S analógica: IA / AO; on-board process PID, flow estimation, energy metering dashboard
Expansão: Supports Profibus-DP, Profinet, EtherNet/IP communication option cards
Acessórios padrão: Chinese graphic keypad, QR code for maintenance access, equipment asset monitoring, drift alarm, Parar&Go energy-saving function

✅ Aplicações típicas
Water supply pumps, wastewater pumps, Ventiladores HVAC, torres de resfriamento, chemical fluid handling, air compressors and other process fluid loads. Focused on energy saving, asset management and predictive maintenance; suitable for dusty, humid field environments (IP55)

✅ Cross-series Comparison & Substituições
1. ATV650D30N4E: Mesma classificação de potência, with integrated load disconnect switch
2. ATV630D30N4: Mesma classificação de potência, IP20 cabinet-mounted bare drive (no outer enclosure)
3. Substituição de atualização: ATV660D30N4; para cargas de impacto pesadas, select ATV950

✅ Important Notes
IP55 units have stricter heat dissipation requirements; reserve vertical ventilation clearance above and below when wall mounting
Dual rating mode (Dever normal / Serviço Pesado) can be switched in parameter group 5.2
Commissioning software: SoMove, firmware version V4.6IE47

ATV650 (Altivar Process ATV600 Series) Fault Code List
1. Fornecer & Input Side Faults
1. IPF / IPL Input phase loss / 3-desequilíbrio de fase
Causa: Fase de entrada ausente, fusível queimado, severe 3-phase voltage unbalance, 3-phase detection enabled incorrectly for single-phase supply
Remédio: Check incoming circuit breaker / fusíveis; set IPL to nO to disable phase loss detection if running on single-phase supply

2. OVF DC bus overvoltage
Causa: Mains voltage too high, deceleration time too short, regenerative energy from high-inertia loads
Remédio: Aumentar o tempo de desaceleração; fit braking resistor; activate adaptive deceleration brA

3. ObF Overvoltage stall (trip due to excessive DC bus voltage)
Causa: Desaceleração rápida, high load inertia, excessive regenerative energy
Remédio: Prolongue o tempo de desaceleração; enable stall prevention; instalar unidade de freio + resistor

4. UVF DC bus undervoltage
Causa: Mains dip, momentary power loss, loose incoming connections, contactor chatter
Remédio: Verifique a fonte de alimentação; extend undervoltage delay; improve wiring connections

5. PHF Supply phase sequence error
Remédio: Swap any two incoming phases L1/L2/L3

2. Saída & Motor Side Faults
1. OCF Output overcurrent
Causa: Motor locked rotor, shorted output cable, quebra de isolamento do motor, rapid acceleration/deceleration
Remédio: Disconnect motor and run no-load test; reduce acceleration/deceleration ramps; test cable insulation to earth with megger

2. SCF Output short-circuit / falha de terra
Causa: Damaged motor cable shorted to earth, motor winding earth fault, failed drive IGBT
Remédio: Disconnect motor and test drive output separately; measure motor winding insulation to earth

3. OPF2 / OPF Output phase loss (perda de fase do motor)
Causa: Loose motor terminals, open output contactor, small motor running at light load
Remédio: Tighten motor wiring; disable OPL phase loss detection if an output contactor is used; disable phase loss protection for small motors

4. OLF Motor thermal overload
Causa: Continuous overloading, rotor bloqueado, motor thermal current ITH parameter set too low
Remédio: Reduza a carga; adjust motor thermal current ITH; wait for motor to cool before reset

5. OLC Drive hardware current limit overload
Remédio: Reduza a carga; check output for short circuits; lower carrier frequency

6. OTF1 / OTF2 Motor PTC thermistor overheat
Causa: Motor winding overtemperature, broken or shorted PTC probe
Remédio: Check motor temperature; measure PTC resistance; disable this protection if no temperature probe is fitted

3. Drive Overheating Faults
1. OHF Drive heatsink overtemperature (common fault)
Causa: Ventilador de resfriamento com falha, clogged filter, insufficient mounting clearance, alta temperatura ambiente, heavy dust accumulation
Remédio: Clean air filter; check cooling fan; set fan permanent ON mode; maintain vertical ventilation clearance; monitor heatsink temperature parameter THD

2. OHFd DC reactor overtemperature
Remédio: Reduza a carga; improve enclosure ventilation

4. Braking Circuit Faults
1. bUF Braking circuit fault
Causa: Open braking resistor, failed braking IGBT, fiação solta
Remédio: Check braking resistor resistance and connections; test braking unit at no load

2. bOF Braking resistor overload
Remédio: Select higher resistance braking resistor; prolongar o tempo de desaceleração

5. Safety Circuit Faults (Torque seguro STO desativado)
1. SAFF STO safety circuit fault
Causa: Mismatched timing between STOA and STOB (time difference >1 é), broken wiring, internal hardware fault
Remédio: Check both STO wiring paths; ensure STOA and STOB switch simultaneously; both paths must be shorted together for bypass

2. SdF Safety function active (normal stop, not a hardware fault)
Status: STO terminals open, drive locked; reset only after restoring STO wiring

6. Comunicação & Analog Signal Faults
1. CnF1~CnF4 Communication link fault (Modbus TCP / RS485)
Causa: Damaged Ethernet cable, incorrect termination resistor, Conflito de endereço IP, electrical noise interference
Remédio: Inspect cables; use shielded communication cable; verify IP settings; reduce baud rate

2. AIF Analog input wire break (4–20 mA current signal)
Causa: Broken sensor cable, circuito aberto, signal below 4 mA
Remédio: Check transmitter and signal wiring; lower wire-break threshold if required

3. AOF Analog output fault

7. Falhas internas de hardware (InF series, generally hardware damage)
1. InF8 Internal power supply fault (power board supply abnormal)
Remédio: Full power cycle; repeated fault = replace power board

2. InFL (InF21) Real-time clock fault, keypad communication failure
Remédio: Remove keypad, remove battery and re-power; replace keypad; if fault persists, replace control board

3. InF1~InF7, InF9~InF30 Other internal hardware errors
Remédio: Ciclo de energia; fault cannot be cleared → control board / power board damaged, requires repair or replacement

8. Process-specific Faults (Bombear / fluid functions exclusive to ATV650)
1. iPPF Low inlet pressure protection (dry-run / low suction protection)
Causa: Pressão de entrada insuficiente, faulty pressure transmitter, protection threshold set too high
Remédio: Check pipeline suction pressure; calibrate pressure transducer; reduce low-pressure threshold

2. HPF High pressure protection, LPF Low pressure protection, FLF Flow fault

3. DryF Dry-run protection (pump running without fluid)
Remédio: Verify pump suction availability; adjust dry-run current threshold

9. Other General Faults
1. FrF Frequency feedback fault (encoder wire break)
2. USF Motor autotune failed on power-up
3. CLF Cooling circuit fault (water-cooled versions only)
4. tJF Motor stall protection

10. Fault Reset Methods
1. Redefinição automática: Enable automatic retry via parameter Atr
2. Reinicialização manual: Assign DI terminal function rSF for remote reset; reset via keypad
3. Internal hardware faults (InF codes): Require full power cycle; some faults need board replacement

Model Prefix Rules
ATV650: Altivar Process IP55 wall-mounted variable speed drive (3-fase 380~480V)
Você: Low power range (0.75~7.5 kW); D: Medium power range (11~90 kW); C: High power floor-standing unit (110 kW and above, IP54)
N4: Without integrated disconnect switch; N4E: With integrated load disconnect switch
Enclosure rating: All wall-mounted units = IP55; floor-standing C models = IP54

Wall-mounted IP55 Full Model List (N4 without switch / N4E with switch, main domestic variants)
Frame A (0.75~22 kW)

Classificação de potênciaModel without switchModel with switch
0.75 kWATV650U07N4ATV650U07N4E
1.5 kWATV650U15N4ATV650U15N4E
2.2 kWATV650U22N4ATV650U22N4E
3 kWATV650U30N4ATV650U30N4E
4 kWATV650U40N4ATV650U40N4E
5.5 kWATV650U55N4ATV650U55N4E
7.5 kWATV650U75N4ATV650U75N4E
11 kWATV650D11N4ATV650D11N4E
15 kWATV650D15N4ATV650D15N4E
18.5 kWATV650D18N4ATV650D18N4E
22 kWATV650D22N4ATV650D22N4E

Frame B (30~45 kW, includes your D30N4)

Classificação de potênciaModel without switchModel with switch
30 kWATV650D30N4ATV650D30N4E
37 kWATV650D37N4ATV650D37N4E
45 kWATV650D45N4ATV650D45N4E

Quadro C (55~90 kW)

Classificação de potênciaModel without switchModel with switch
55 kWATV650D55N4ATV650D55N4E
75 kWATV650D75N4ATV650D75N4E
90 kWATV650D90N4ATV650D90N4E

High Power Floor-standing Units (C range, IP54, instalação vertical)
Model format: ATV650CxxN4F (all fitted with disconnect switch)
110/132/160/200/250/315 kW:
ATV650C11N4F, C13N4F, C16N4F, C20N4F, C25N4F, C31N4F

Confusable Series Comparison
1. ATV650: IP55 wall-mounted, for local field installation (the series you are using)
2. ATV630: Mesma classificação de potência, IP20 cabinet bare drive, no outer enclosure
3. ATV660: Newer generation, upgrade replacement for ATV650
4. ATV950: Acionamento para serviço pesado, for shock loads other than fans and pumps

Additional Key Information
Suffix U = low power; D = medium power; C = high power floor-standing
Suffix E = integrated load disconnect switch; no E = no switch
Standard features for all units: Dual-port Modbus TCP + RS485, built-in Class C2/C3 EMC filter, Chinese graphic keypad, Torque seguro STO desativado