Schneider LC1E1801 Contactor

Model code explanation: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contato normalmente fechado (1NC) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, totalmente compatível na montagem, terminal layout and performance. Key Specifications Main ...

  • Detalhes do produto

Model code explanation: LC1E = TeSys E series contator; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contato normalmente fechado (1NC)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, totalmente compatível na montagem, terminal layout and performance.

Especificações principais

Principais contatos: 3P, 3NÃO

AC-3 (motor duty): 18A@400V; AC-1 (carga resistiva): 25UM

Motor rating: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V

Insulation voltage Ui: 690V; Tensão suportável de impulso Uimp: 6kV

Contato auxiliar: 1NC (Normalmente fechado)

Montagem: Trilho DIN / base plate screw mounting

Dimensões gerais: W45mm × H74mm × D80mm, net weight ≈0.3kg

Classe de proteção: IP20; Temperatura operacional: -5~+55℃; No derating up to 3000m altitude

Vida mecânica: 10 milhões de operações; AC-3 electrical life: 1.2 milhões de operações; Max operating frequency: 1800 ciclos/hora

Coil suffix definitions (complete model number)

LC1E1801B5: CA24V, 50Hz

LC1E1801F5: AC110V, 50Hz

LC1E1801M5: AC220V, 50Hz (most common in China)

LC1E1801Q5: AC380V, 50Hz

Sufixo 7 = 50/60Hz universal; sufixo 6 = 60Hz only

Consumo de energia da bobina (M5 220V example)

Inrush VA: 95VA; Sealed holding VA: 8.5VA; Coil heat dissipation: 2~3W

Tensão de captação: 0.85~1.1Uc; Tensão de saída: 0.3~0.6Uc

Torque de aperto & wire gauge

Torque for main circuit and control circuit terminals: 1.2 N·m

Fio sólido: 1.5~6mm²; Fio trançado (com ponteira): 1~4mm²

Matching selection reference

Matching thermal overload relay: LRD07 / LRN07 (current range suitable for 18A)

Acessórios: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

Alternativa doméstica: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

Guia de solução de problemas

  1. Coil energized but no pull-in: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: Main contact erosion, soldagem por contato, fiação solta
  3. Buzzing / conversando: Subtensão, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Contatos principais soldados, core stuck by oil and dirt

Detailed Installation Procedure for Schneider LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Marcação de terminais: Circuito principal L1/L2/L3 (line side, incoming), T1/T2/T3 (lado da carga, outgoing); Coil A1, A2; Contato auxiliar: 95, 96 (1NC)

  1. Preparação de pré-instalação
  2. Verifique a tensão da bobina: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. Inspeção visual: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. Ferramentas: 2 chave Phillips, descascador de fios, multímetro, chave dinamométrica; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; Fio trançado com ponteira: 1~4mm²

Circuito de controle (A1/A2, contatos auxiliares): 0.75~1.5mm²

Torque de aperto: 1.2 N·m (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, mantenha longe da poeira, umidade e óleo. Mount vertically upright. Do NOT install upside down or horizontally.
  2. Consertando (2 methods: Trilho DIN / base plate screw mounting)

Método 1: 35mm montagem em trilho DIN (preferido)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. Remoção: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

Método 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (Opcional: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. Sequência de fiação (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (motor).

  1. Fiação do circuito principal

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, NC)

Terminais 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, A2 (circuito de controle)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (Bobina), 95-96 (Built-in 1NC)

  1. Inspeção pré-ligação
  2. Verificação visual: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Continuity test with multimeter:

De-energized state: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 abre.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. Comissionamento de inicialização
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

Chattering: Baixa tensão de alimentação, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. Notas de instalação & Proibições
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Common Installation Faults

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: Subtensão, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / TVS EasyPact) Series Full List

Nota importante: LC1E series fully discontinued in July 2020. Substituição direta: LC1N series, dimensões de montagem e layout de terminal idênticos.

Regra modelo: LC1E + current code + auxiliary contact code (10=1NÃO; 01= 1NC) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; BD=DC24V; 6=60Hz only

  1. 3P LC1E Contactors (AC-3 @400V)
Modelo BásicoCorrente AC-3Motor Rating @400VBuilt-in Auxiliary Contact
LC1E06106UM2.2kW1NÃO
LC1E06016UM2.2kW1NC
LC1E09109UM4kW1NÃO
LC1E09019UM4kW1NC
LC1E121012UM5.5kW1NÃO
LC1E120112UM5.5kW1NC
LC1E181018UM7.5kW1NÃO
LC1E180118UM7.5kW1NC (your referenced model)
LC1E251025UM11kW1NÃO
LC1E250125UM11kW1NC
LC1E321032UM15kW1NÃO
LC1E320132UM15kW1NC
LC1E381038UM18.5kW1NÃO
LC1E380138UM18.5kW1NC
LC1E401140UM18.5kW1NÃO+1NC
LC1E501150UM22kW1NÃO+1NC
LC1E651165UM30kW1NÃO+1NC
LC1E801180UM37kW1NÃO+1NC
LC1E951195UM45kW1NÃO+1NC
LC1E120120UM55kWNo built-in, add auxiliary block separately
LC1E160160UM75kWNo built-in, add auxiliary block separately
LC1E200200UM90kWNo built-in, add auxiliary block separately
LC1E300300UM160kWNo built-in, add auxiliary block separately

Example complete model: LC1E1801M7 = 18A, 1NC, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1A

LRE06N: 1~1,6A

LRE07N: 1.6~2,5A

LRE08N: 2.5~4A

LRE09N: 4~6A

LRE10N: 6~10A

LRE12N: 10~16A

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80A

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1NÃO / 1NC, stackable)
  3. LAEM1: Módulo de intertravamento mecânico (for two contactor interlocking)
  4. LA9D: Supressor de surto de bobina (Rede RC / varistor, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (atraso de ativação / atraso de desligamento)
  7. 2P / 4P LC1E (single phase, iluminação & carga resistiva, Dever AC-1)

LC1E0920: 2Pergunta 9A

LC1E2520: 2P 25A

LC1E0940: 4Pergunta 9A

LC1E2540: 4P 25A

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95