Série: TeSys Deca (TeSys D) 3-pole AC Contactor
Explicação do código do modelo
LC1D: TeSys D standard contactor series
115: AC-3 rated current 115A @ 440V
F: Coil voltage code → 110V AC
7: 50/60Hz universal frequency
Parâmetros elétricos principais
Principais contatos: 3P, 3 Normalmente aberto (3NÃO)
AC-3 (motor duty): 115A ≤440V; suitable for 55kW motor at 400V
AC-1 (carga resistiva): Conventional thermal current Ith=200A (≤60℃)
Bobina: AC110V, 50/60Hz
Contatos auxiliares integrados: 1NÃO + 1NC
Tensão nominal suportável de impulso Uimp: 8kV; Categorias de utilização: AC-3 / AC-3e / AC-1 / AC-4
Short-time making capacity: 1260A @440V
SCCR short-circuit withstand rating: up to 100kA
Mecânico & Especificações Ambientais
Dimensão geral: H158mm × W120mm × D136mm; Net weight 2.5kg
Front face protection: IP20
Temperatura ambiente: -40℃ ~ +60 ℃; derating required from 60℃ to 70℃
Maximum installation altitude: 3000eu
Padrões: IEC60947-4-1, CCC, CE, UL, CSA certifications
Frequência máxima de operação: 2400 ciclos/hora
Fim da vida & Informações de substituição
This model is scheduled for discontinuation (last supply date: 31-Dec-2026)
Official recommended upgraded replacements:
LC1D115AEHE: 48–130V AC/DC wide-voltage coil, Everlink terminal, montagem compatível
LC1D115AKUE: 100–250V AC/DC wide-voltage version
Observação: Replacement models adopt wide AC/DC coils with the same logic as original 110VAC coil. Terminal hole layout and DIN rail mounting are fully compatible, direct cabinet retrofit is available.
Acessórios compatíveis
Relé de sobrecarga térmica: LRD43 series (for 115A range)
Bloco de contato auxiliar: LA1DN (for extra auxiliary contacts)
Supressor de surto: LA4DA coil suppressor (for AC coil)
Intertravamento mecânico: LA9D11502 (para circuito de reversão)
Aplicações Típicas
Start/stop control for 3-phase motors such as fans, bombas de água, air compressors and belt conveyors; widely used in HVAC, panel assembly and automated production lines.
Application Cases of LC1D115F7 (115UM, AC110V Coil)
Basic capability: Máx.. 55kW 3-phase squirrel-cage motor under AC-3 @400V; control circuit AC110V, contatos auxiliares 1NO + 1NC integrados. Suitable for DOL direct-on-line, estrela-delta, forward-reversing and MCC motor control circuits. Widely used in panel assemblies, AVAC, tratamento de água, compressores de ar e linhas transportadoras. The most typical configuration uses 110V isolation transformer secondary as control power supply.
Caso 1: DOL Starter Cabinet for Chiller Compressor (Central Air Conditioning Host)
Carregar: 55kW screw compressor motor, 400V trifásico
Circuit configuration: Disjuntor + LC1D115F7 + LRD43 thermal relay; PLC sends 110VAC control signal to energize contactor coil
Lógica de controle: PLC sequential control (start oil pump and cooling water pump first, then host compressor); thermal relay fault feedback to PLC; local manual / remote auto switch
Selection reason: Secondary control of chiller cabinet uniformly adopts AC110V, perfectly matching F coil; compressor operates with low switching frequency, sufficient electrical life; CCC+CE, meets MEP acceptance requirements
Accessory used: LA4DA coil surge suppressor (to suppress back EMF from compressor startup)
Caso 2: Municipal / Plant Fire Main Pump (Partida Estrela-Delta)
Carregar: 55kW fire sprinkler pump / hydrant pump
Circuit configuration: 3 pcs LC1D115F7 for star-delta starter (main contactor, contator estrela, contator delta), with timer, mechanical interlock and fire alarm terminal block
Características: Many fire control cabinets adopt AC110V secondary circuit, F7 coil is a direct match; auxiliary contacts feed running and fault status to fire alarm host; thermal relay is required for overload protection (fire code allows overload alarm without immediate shutdown)
Observações: 3 contactors with same rating 115A for star-delta circuit; LA9D11502 mechanical interlock is mandatory to prevent short circuit between star and delta states
Caso 3: Screw Air Compressor Control Cabinet (55kW)
Carregar: 55motor principal kW do compressor de ar de parafuso, auto start/stop by pressure
Circuito: Pressostato / CLP + LC1D115F7 + relé térmico; compressor built-in 110V control transformer
Condição operacional: Partida-parada intermitente, normally <600 ciclos/hora, well within rated 2400 ciclos/hora; Dever AC-3
Extra function: Auxiliary contacts connected to compressor controller for running status and fault upload to upper system
Caso 4: Water Treatment Plant – Circulating Pump / Sewage Lift Pump
Carregar: 55kW large-flow centrifugal pump, sludge return pump
Esquema: DOL direct start; duty-standby interlock circuit (2 pcs LC1D115F7 plus LA9D11502 mechanical interlock)
Controlar: Auto switching via level / transmissor de pressão + CLP; standby pump auto start upon main pump fault; control power AC110V
Environment note: Pump room is humid, dehumidifier fitted inside cabinet; contactor IP20 suitable for cabinet mounting
Caso 5: Heavy-duty Belt Conveyor in Factory
Carregar: 55kW main drive motor for belt conveyor, começo pesado
Esquema: DOL or star-delta; some with forward-reversing function (2 pcs LC1D115F7 + intertravamento mecânico)
Condição operacional: Heavy inrush current at startup; derating assessment required for AC-4 duty (corrida frequente & invertendo); soft starter is recommended for priority while contactor serves as output switch
Sinal: Auxiliary contacts send belt running and fault alarm to SCADA
Caso 6: MCC Motor Control Center Drawout Unit
Cenário: MCC cabinet drawer circuit in chemical plant, power plant and building material plant
Configuração: Standard motor starter drawer unit, disjuntor + LC1D115F7 + relé térmico; secondary 110V control supply
Vantagem: Standardized TeSys D series, mature interface for MCC drawer; auxiliary contacts for drawer position and running feedback; easy plug-and-play maintenance
Caso 7: High-power Heating Circuit for Resistive Load (Não motorizado)
Carregar: 3-phase heating elements, large electric oven, Ith=200A under AC-1
Descrição: Higher allowable current 200A for AC-1 resistive load than motor duty. Suitable for main circuit of large hot-air furnace and heat-treatment oven; PLC or temperature controller outputs 110V control signal for coil driving
Observação: Arc extinguishing characteristic differs between resistive and motor loads. Not suitable for frequent switching of high-power heating loads.
Seleção Suplementar & Notas de Operação (for F7 coil)
- Coil rated AC110V, DO NOT connect directly to 220V. Control transformer is required inside cabinet to output AC110V
- This model is at end-of-life phase. New projects prefer replacement model LC1D115AEHE (48–130V AC/DC wide voltage, compatible with 110VAC)
- For frequent start-stop, jogging and reversing (AC-4) aplicações, select one higher current rating or adopt soft starter to reduce contact erosion
- Thermal relay LRD43 series must be fitted for overload protection of all motor circuits
Schneider TeSys D LC1D 3-pole Contactor Order List (Standard 3P, 1NO+1NC Auxiliary, Terminal de parafuso)
Regra de nomenclatura:
LC1D + Classificação atual + Código da bobina
Coil suffix:
7 = AC 50/60Hz (most common in China)
5=50Hz, 6=60Hz
D=DC coil
B=24V, E=48V, F=110V, M=220V, P=230V, Q=380V, V=400V
⚠️ Old domestic marking for 115/150/170A: LC1D11500F7C; new import version is LC1D115F7 directly, LC1D115F7 is the model above
Status: Old LC1DxxB7/F7/M7/Q7/V7 series to be discontinued by end of 2026
New replacements: AEHE (48–130V AC/DC wide voltage), AKUE (100–250V AC/DC wide voltage)
400V AC-3 Motor Power Reference
| Modelo Básico | AC-3 Current @440V | Matched Motor @400V | Common AC Order Code (sufixo 7) | DC Order Code | Nova substituição (Everlink) |
| LC1D09 | 9UM | 4kW | LC1D09B7 / LC1D09F7 / LC1D09M7 | LC1D09BD | LC1D09AEHE |
| LC1D12 | 12UM | 5.5kW | LC1D12B7 / LC1D12F7 / LC1D12M7 | LC1D12BD | LC1D12AEHE |
| LC1D18 | 18UM | 7.5kW | LC1D18B7 / LC1D18F7 / LC1D18M7 | LC1D18BD | LC1D18AEHE |
| LC1D25 | 25UM | 11kW | LC1D25B7 / LC1D25F7 / LC1D25M7 | LC1D25BD | LC1D25AEHE |
| LC1D32 | 32UM | 15kW | LC1D32B7 / LC1D32F7 / LC1D32M7 | LC1D32BD | LC1D32AEHE |
| LC1D38 | 38UM | 18.5kW | LC1D38B7 / LC1D38F7 / LC1D38M7 | LC1D38BD | LC1D38AEHE |
| LC1D40 | 40UM | 18.5kW | LC1D40B7 / LC1D40F7 / LC1D40M7 | LC1D40BD | LC1D40AEHE |
| LC1D50 | 50UM | 22kW | LC1D50B7 / LC1D50F7 / LC1D50M7 | LC1D50BD | LC1D50AEHE |
| LC1D65 | 65UM | 30kW | LC1D65B7 / LC1D65F7 / LC1D65M7 | LC1D65BD | LC1D65AEHE |
| LC1D80 | 80UM | 37kW | LC1D80B7 / LC1D80F7 / LC1D80M7 | LC1D80BD | LC1D80AEHE |
| LC1D95 | 95UM | 45kW | LC1D95B7 / LC1D95F7 / LC1D95M7 | LC1D95BD | LC1D95AEHE |
| LC1D115 | 115UM | 55kW | LC1D115B7 / LC1D115F7 / LC1D115M7 | LC1D115BD | LC1D115AEHE / LC1D115AKUE |
| LC1D150 | 150UM | 75kW | LC1D150B7 / LC1D150F7 / LC1D150M7 | LC1D150BD | LC1D150AEHE / LC1D150AKUE |
| LC1D170 | 170UM | 90kW | LC1D170B7 / LC1D170F7 / LC1D170M7 | LC1D170BD | LC1D170AEHE / LC1D170AKUE |
| LC1D205 | 205UM | 110kW | LC1D205B7 / LC1D205F7 / LC1D205M7 | LC1D205BD | LC1D205AEHE / LC1D205AKUE |
| LC1D245 | 245UM | 132kW | LC1D245B7 / LC1D245F7 / LC1D245M7 | LC1D245BD | LC1D245AEHE / LC1D245AKUE |
| LC1D300 | 300UM | 160kW | LC1D300B7 / LC1D300F7 / LC1D300M7 | LC1D300BD | LC1D300AEHE / LC1D300AKUE |
| LC1D410 | 410UM | 220kW | LC1D410B7 / LC1D410F7 / LC1D410M7 | LC1D410BD | LC1D410AEHE / LC1D410AKUE |
| LC1D475 | 475UM | 250kW | LC1D475B7 / LC1D475F7 / LC1D475M7 | LC1D475BD | LC1D475AEHE / LC1D475AKUE |
| LC1D620 | 620UM | 315kW | LC1D620B7 / LC1D620F7 / LC1D620M7 | LC1D620BD | LC1D620AEHE / LC1D620AKUE |
Supplementary Categories
- 4-pole Versions (LC1DT: 4NO resistive; LC1Dxx8: 2NÃO+2NC)
LC1DT25 / LC1DT32 / LC1DT40 / LC1DT60A / LC1DT80A
LC1D128 / LC1D188 / LC1D258 / LC1D40008 / LC1D65008
- Reversing Contactors LC2D (Built-in mechanical interlock, equivalent to two LC1D plus interlock)
LC2D09 / LC2D12 / LC2D18 / LC2D25 / LC2D32 / LC2D38 / LC2D40 / LC2D50 / LC2D65 / LC2D80 / LC2D95 / LC2D115 / LC2D150 / LC2D170
Exemplo: LC2D115F7 (115UM, AC110V reversing contactor)
- Coil Code Quick Reference (Common for domestic projects)
B7: AC24V 50/60Hz
E7: AC48V 50/60Hz
F7: AC110V 50/60Hz (your LC1D115F7)
M7: AC220V 50/60Hz
Q7: AC380V 50/60Hz
V7: AC400V 50/60Hz
BD: CC24V
DE: DC48V
FD: CC110V
MD: CC220V
- Terminal Variant Code (placed before voltage code)
3: Terminal de gaiola de mola, por exemplo. LC1D1153F7
6: Terminal de anel (cable lug), por exemplo. LC1D1156F7
- Matched Thermal Relay Reference (for panel selection)
09~38A: LRD07…LRD35
40~95A: LRD33 series
115~170A: LRD43 series
205 e acima: LRD48 series
Important End-of-Life Notice
Old LC1DxxB7/F7/M7/Q7/V7 series last supply: 31-Dec-2026
AEHE: 48–130V AC/DC wide voltage (direct replacement for B7, E7, F7)
AKUE: 100–250V AC/DC wide voltage (direct replacement for M7, P7)
Mounting dimension, cutout and auxiliary contacts are fully compatible, no cabinet drawing modification required