Schneider RM17TG00 Phase Sequence & Relé de monitoramento de perda de fase

RM17: Harmony RM17 series three-phase monitoring relay TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions) 00: 1 contato de mudança (1C/O) versão; RM17TG20 in the same series is the 2C/O dual-contact model ✅ Core Functions Monitors three phases L1/L2/L3: Erro de sequência de fase (fase reversa, motor reverse rotation protection) Fase ...

  • Detalhes do produto

RM17: Harmony RM17 series three-phase monitoring relay

TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)

00: 1 contato de mudança (1C/O) versão; RM17TG20 in the same series is the 2C/O dual-contact model

✅ Funções principais

Monitors three phases L1/L2/L3:

  1. Erro de sequência de fase (fase reversa, motor reverse rotation protection)
  2. Falha de perda de fase (loss of two or more phases; single-phase weak voltage drop will NOT trigger)

Autoalimentado, energized directly from L1/L2/L3, no additional auxiliary fonte de energia obrigatório

📋 Key Technical Specifications

ItemParâmetro
Monitoring Voltage Range208~480 VAC (operating limit 183~528VAC)
Freqüência50/60Hz ±10%
Contatos de saída1C/O (1 Normalmente aberto + 1 Normalmente fechado)
Corrente de contato nominal5A @250VAC, max.1250VA
Power-up Start Delay≤650ms
Fault Response Time≤130ms
Consumo de energia≤22VA @400VAC 50Hz
Montagem35mm trilho DIN, width 17.5mm (1 módulo)
IndicadorLED amarelo: ON under normal condition, OFF in fault state
CertificaçõesCE, Categoria de sobretensão III, IEC60255

🔌 Terminal Wiring Definition

Upper terminals: L1, L2, L3 → Connect to three-phase power supply

Lower contact terminals:

11: Comum

14: Normalmente aberto (NÃO) (closed in normal state, aberto sob falha)

12: Normalmente fechado (NC) (aberto em estado normal, closed under fault)

With correct three-phase supply and proper phase sequence: relé energiza, LED LIGADO; Perda de fase / reversed phase → relay de-energizes, LED DESLIGADO

🛠️ Cenários típicos de aplicação

Hoisting equipment, elevadores, linhas transportadoras, water pump sets, preventing motor reverse rotation

Compressores de ar, chiller unit three-phase power protection

Portable equipment power access detection, emergency power switching judgment

⚠️ Troubleshooting Points

  1. LED apagado: No power on three-phase incoming lines or loose wiring;
  2. LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
  3. Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & proteção contra subtensão, select RM17TE series.

🧩 Same-series Comparison & Referência de substituição

RM17TG00: 1C/O, sequência de fase + perda de fase

RM17TG20: 2C/O dual changeover contacts, sequência de fase + perda de fase

RM17TE00: With voltage unbalance, sobretensão, subtensão, phase loss and phase sequence (full-featured model)

📌 Notes

No potentiometer for threshold adjustment, fixed logic without adjustment knobs;

For three-phase 3-wire system only;

Dry contact output for PLC DI or contactor coil interlock circuit.

Schneider RM17TG20 Troubleshooting Document

Aplicável: RM17TG00 / RM17TG20 three-phase phase sequence & phase loss relay

Precauções de segurança: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.

Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. Estado normal: yellow LED ON, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized

  1. Pre-check Preparation
  2. Ferramentas: Multímetro digital, cross screwdriver, luvas isolantes
  3. Confirmação do modelo: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
  4. System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
  5. Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
  6. Troubleshooting by Fault Symptom

Sintoma 1: Yellow LED completely off after power-up, relay contacts no action

Descrição: No indicator light after energizing, contatos 11/14 e 21/24 fail to close

  1. Desligar, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
  2. Ligar, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter

Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage

No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit

  1. LED still OFF with all three-phase voltages normal:

Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals

Inspect module appearance: Carcaça rachada, burn marks or carbonized terminals → internal damage, replace relay directly

Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective

Sintoma 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)

Most frequent on-site fault: Reversed phase sequence

  1. Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
  2. Desligar, swap any two incoming L phases (por exemplo. L1 e L3)
  3. Re-energize and observe LED:

LED ON and contacts close: Fault resolved, root cause reversed phase sequence

LED still OFF after twice phase swap: proceed to next step

  1. Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
  2. Still invalid: Relay internal failure, replace for test

Sintoma 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)

Power monitoring circuit healthy, fault lies in secondary dry contact circuit

RM17TG20 has two independent changeover contact sets: 11/12/14 e 21/22/24, both act synchronously

  1. Power off and verify contact wiring:

11, 21: Common terminals

14, 24: Normalmente aberto (NÃO) (closed when energized; aberto sob falha)

12, 22: Normalmente fechado (NC) (open when energized; closed under fault)

  1. Ligar (relay normal state, LED LIGADO), measure continuity with multimeter:

11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open

  1. Manually create fault (reverse phase sequence), LED DESLIGADO:

11 & 14, 21 & 24: abrir; 11 & 12, 21 & 22: conduta

  1. Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
  2. Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse

Sintoma 4: Random false tripping during motor operation (LED DESLIGADO, protection trip)

  1. Monitor three-phase voltage, focus on voltage dip during motor starting:

⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection

  1. Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
  2. Check power cables: Danos no cabo, earth fault or risk of phase-to-phase short circuit
  3. EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
  4. Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
  5. Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged

Sintoma 5: Relay does not alarm with single-phase cut-off (protection no action)

This is NOT a fault, it is inherent design limitation!

RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection

If single-phase loss, voltage unbalance, sobretensão & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay

III. Quick Self-check Procedure (On-site Maintenance Checklist)

✅ Step1: Desligar, inspect appearance and wiring (terminais, marcas de queimadura, frouxidão)

✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages

✅ Step3: Observe LED status to locate fault domain (fonte de energia / sequência de fase / relay itself)

✅ Step4: Power off and swap two L phases to verify reversed phase sequence

✅ Step5: Power off and test continuity of two contact sets to confirm switching logic

✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring

  1. Equívocos comuns
  2. ❌ Equívoco: Relay should protect on single-phase loss

✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.

  1. ❌ Equívoco: Front panel adjustment knobs are available for threshold setting

✅ Note: RM17TG has no potentiometer, threshold fixed.

  1. ❌ Equívoco: Two contact sets can act independently

✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.

  1. ❌ Equívoco: Can be used in 3P4W system (com fio neutro)

✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.

  1. Replacement Criteria (Replace relay if any condition met)
  2. L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
  3. Two contact sets act asynchronously, contacts burnt or fail to switch
  4. Housing or terminals show black burn marks, bulging or carbonization
  5. Fault eliminated after installing new relay under same power condition
  6. Recomendação de manutenção
  7. Periodic inspection: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
  8. Ambient condition: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
  9. Limpeza: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
  10. Vida útil: Mechanical life of contacts >10 milhões de ciclos; electrical life approx.100,000 cycles at 5A@250VAC

Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35mm trilho DIN, 17.5mm 1-module width)

All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system

  1. RM17TG (Modelo básico: sequência de fase + phase loss only, no adjustment knobs, fixed threshold)
ModeloContatosFaixa de tensãoFunções principaisAplicação Típica
RM17TG001C/O (1 changeover)208~480VACErro de sequência de fase, ≥2 phases loss protection; No unbalance / sobre&subtensãoSingle interlock, water pump and general motor protection
RM17TG202C/O (2 independent changeover)208~440 VCAErro de sequência de fase, ≥2 phases loss protection; No unbalance / sobre&subtensãoHardware interlock + PLC alarm, hoisting, elevador

TG Series Features: Sem potenciômetro, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm

  1. RM17TT / ENFRENTANDO / TU / O (Multi-function adjustable type, transparent cover with adjustment knobs)
ModeloContatosFaixa de tensãoFunções de monitoramento
RM17TT001C/O208~480VACPerda de fase + sequência de fase; rated voltage selectable, atraso ajustável; No voltage unbalance, sobre/subtensãoBasic adjustable phase sequence & perda de fase, suitable for multi-voltage site
RM17TA001C/O208~480VACPerda de fase + sequência de fase + three-phase voltage unbalance; unbalance threshold & atraso ajustável; No over/undervoltageMotor winding protection, detect three-phase asymmetry
RM17TU001C/O208~480VACPerda de fase + sequência de fase + undervoltage monitoring; undervoltage threshold & atraso ajustável; No overvoltage, no unbalancePower supply drop monitoring, generator set, incoming power supervision
RM17TE001C/O208~480VACFunções completas: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurementRefrigerador, compressor de ar, UPS switching, full protection requirement

III. RM17 Series Single-phase / DC Voltage Monitoring (Mesma série, non three-phase)

ModeloTipoMonitoring RangeContatos
RM17UAS14Tensão CC9~15VDC1C/O
RM17UAS16CA/CC Universal20~80V AC/DC1C/O
RM17UAS15CA/CC Universal65~260V AC/DC1C/O
RM17UBE SeriesSingle-phase AC Over & Subtensão24~240 VCA1C/O
RM17UB310Single-phase Voltage Monitoring200~240 VCA1C/O
  1. Model Suffix Coding Definition (RM17Txx00)

TG: Tipo básico, fixed threshold, no adjustment knob, sequência de fase + perda de fase

TT: Adjustable basic model, sequência de fase + perda de fase, voltage range selectable

ENFRENTANDO: T + Asymmetry voltage unbalance detection

TU: T + Undervoltage monitoring

O: Total full functions (sequência de fase, perda de fase, desequilíbrio, sobretensão, subtensão)

00: 1C/O output

20: 2C/O dual independent changeover contacts (only available for TG series)

  1. Tabela de seleção rápida (Three-phase models)
ExigênciaModelo recomendado
Only phase sequence+phase loss, single contact output, 480V applicationRM17TG00
Phase sequence+phase loss, dual independent dry contacts for interlock + alarmeRM17TG20
Phase loss+phase sequence, multi-voltage option, delay requiredRM17TT00
Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection)RM17TA00
Phase loss+phase sequence+undervoltage monitoringRM17TU00
Proteção total: phase loss+phase sequence+unbalance+overvoltage+undervoltageRM17TE00
  1. Common General Specifications
  2. Montagem: 35mm trilho DIN, 1 módulo (17.5milímetros);
  3. Lógica de Saída: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
  4. Fonte de energia: Self-powered directly from L1/L2/L3, sem fio neutro, three-phase 3-wire system only;
  5. Tempo de resposta: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
  6. Avaliação de contato: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads

VII. Substituição & Upgrade Reference

RM17TG00 ↔ RM17TG20: função idêntica, only contact quantity differs

RM17TT00 → RM17TA00: add voltage unbalance detection

RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring

Legacy RM22TG series is substitute series (mesma função, different form factor)