SIRIUS 3RT series 3-pole AC power contactor, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts
- Decodificação de modelo
3RT1056-6AP36
3TR: SIRIUS power contactor series
10: Contator padrão (non-safety, tipo sem reversão)
56: Frame size S6, AC-3 400V 185A
6: Coil voltage 220…240V AC/DC
UM: Conexão do barramento do circuito principal
P: Screw terminals for auxiliary contacts
36: Contatos auxiliares 2 Normalmente aberto + 2 Normalmente fechado (2NÃO+2NC)
- Especificações elétricas principais
| Item | Parâmetro |
| Número de pólos principais | 3 postes (3NÃO) |
| AC-3 (Motor load @400V) | 185UM, 90kW |
| AC-1 (Resistive load @40℃) | 215UM |
| Tensão nominal de operação Ue | Máx.. 1000V e |
| Coil control voltage Uc | 220~240V CA/CC (Wide-range AC/DC coil) |
| Contatos auxiliares | 2NÃO + 2NC, terminais de parafuso |
| Conexão do circuito principal | Barramento |
| Tamanho do quadro | S6 |
| Grau de proteção | Front IP00; IP20 with cover installed |
| Tensão suportável de impulso | 8kV main circuit / 6kV auxiliary circuit |
| Temperatura ambiente | -25℃ ~ +60 ℃ (Derating necessário acima de 40℃) |
- Escopo de aplicação
On/off control of 3-phase motors such as fans, bombas de água e compressores
Control cabinets, ar condicionado central, industrial production lines and power cabinets
Can be matched with 3RU thermal overload relay for motor overload protection; 3RT19 surge suppressor for coil EMC interference suppression
- Modelos Alternativos
- Doméstico SIEMENS substituição: 3RT5056-6AP36
Função idêntica, current rating and coil specification. Made in China, direct replacement for 3RT1056-6AP36 with identical mounting dimensions, officially recommended replacement model
- Upgraded model in same series: 3RT1064-6AP36 (AC-3 225A, 110kW)
- Downsized model in same series: 3RT1055-6AP36 (AC-3 150A, 75kW)
Observação: 3RT1056 manufactured in Germany; 3RT5056 manufactured domestically. Fully compatible in electrical performance and mounting hole layout, direct interchangeable in projects.
- Instalação & Diretrizes de Manutenção
- Instalação: Montagem vertical, tilt ≤ ±5°. Heat dissipation clearance required. S6 frame generates considerable heat; derating is required for multiple units mounted side-by-side inside cabinet.
- Circuito principal: Conexão de barramento, tighten to specified torque per datasheet to prevent overheating and contact burning.
- Bobina: Wide-range AC/DC coil, compatible for AC and DC control. 3RT19 surge suppression module is recommended in parallel to reduce interference to PLC digital outputs.
- Contact life: Under AC-3 motor duty, mechanical life approx. 10 milhões de operações; electrical life depends on breaking current.
- Solução de problemas
Coil energized but no pull-in: Medir a tensão da bobina, check coil open circuit or mechanical jamming
Pull-in but no continuity on main circuit: Loose busbar or burned main contacts
Chattering / ruído anormal: Baixa tensão da bobina, accumulated dust on iron core, fadiga da primavera
- Código HS Aduaneiro
85364900 (Electromagnetic contactor)
- Optional Spare Parts & Acessórios
Relé de sobrecarga térmica: 3RU2156 series (for 90kW motor)
Supressor de surto: 3RT1955-1CD00 (RC circuit), 3RT1955-1DG00 (Varistor)
Bloco de contato auxiliar: 3RH1951 (for extra auxiliary contacts)
Arc shield & main contact repair kit: 3RT1956 contact assembly
Tabela de comparação: SIEMENS 3RT1056-6AP36 VS 3RT5056-6AP36
Both models feature identical electrical parameters, mounting dimensions and compatible accessories for direct replacement. The core differences lie in origin, nameplate marking, lead time and applicable certifications.
| Item de comparação | 3RT1056-6AP36 (Imported Version) | 3RT5056-6AP36 (Versão Doméstica) |
| Linha de Produtos | SIRIUS 3RT1, global standard imported version | SIRIUS 3RT5, local domestic version |
| Origem | Amberg Factory, Alemanha | SIEMENS low voltage plant in China (SEAL) |
| AC-3 @400V | 185UM / 90kW | 185UM / 90kW |
| AC-1 Resistive Load | 215UM | 215UM |
| Especificação da bobina | 220~240V CA/CC | 220~240V CA/CC |
| Contatos Auxiliares | 2NÃO+2NC, terminais de parafuso | 2NÃO+2NC, terminais de parafuso |
| Conexão do Circuito Principal | Barramento | Barramento |
| Tamanho do quadro | S6 | S6 |
| Dimensão Geral / Orifícios de montagem | Idêntico, direto intercambiável | Idêntico, direto intercambiável |
| Vida Mecânica | 10 milhões de operações | 10 milhões de operações |
| Vida Elétrica AC-3 | Mesmo (depends on breaking current) | Mesmo (depends on breaking current) |
| Faixa de temperatura ambiente | -25℃ ~ +60 ℃ | -25℃ ~ +60 ℃ |
| Acessórios compatíveis | Compatibilidade total: 3RU thermal relay, 3RT19 surge suppressor, contact repair kit, bloco de contato auxiliar | 100% compatible with accessories of 3RT1056 |
| Certificações | CCC, CE, UL, CSA, suitable for overseas projects | CCC, CE; UL optional for certain batches, standard for domestic projects |
| Placa de identificação | Alemão + English marking, Fabricado na Alemanha | chinês + English marking, made in China |
| Delivery Lead Time | Longo, mostly forward order with unstable lead time | Curto, domestic stock available with fast delivery |
| Preço | Mais alto | Lower with cost advantage |
| Cenários de aplicação | Equipamento de exportação, projetos no exterior, high-end foreign-invested projects, cases requiring imported components | Domestic control cabinets, bombas de água & fãs, AVAC, general industrial automation |
| Desempenho Elétrico | Idêntico, no derating difference | Idêntico, no derating difference |
| Código HS | 85364900 | 85364900 |
| Model Naming Definition | 3RT10: Global original series | 3RT50: Domestic localized series |
Notas principais
- Intercambialidade: SIEMENS officially approves direct replacement. No modification required for cabinet cutout, barramento, secondary control loop or thermal relay selection. Electrical characteristic curve, temperature rise and contact breaking capacity are identical.
- Orientação de seleção
✅ Choose 3RT5056: Projetos nacionais, budget control, fast delivery; preferred for most domestic panel building projects.
✅ Choose 3RT1056: Máquinas de exportação, overseas site, specification explicitly requiring German origin, mandatory UL/CSA certification.
- Misconception Clarification: It is NOT a downgraded domestic variant. Same product platform and design, manufactured at different factories under identical design and test standards.
Suplementar: Shared Spare Parts List
Relé de sobrecarga térmica: 3RU2156 series
Supressor de surto: 3RT1955-1CD00 / 3RT1955-1DG00
Main contact repair kit: 3RT1956
Additional auxiliary contact block: 3RH1951
Application Scenarios for 3RT1056-6AP36 and 3RT5056-6AP36
Identical load capacity for both models, rated for 400V, 90kW 3-phase motor direct-on-line start (AC-3, 185UM). Differences are only based on project location, certification requirements and client procurement specification, NOT load capacity.
- Common Applications (Both Models Applicable)
(1) Direct-on-line Motor Starting (Main AC-3 Duty)
Bombas de água, bombas de esgoto, bombas de circulação (tratamento de água, AVAC, prédio, indústria química)
Compressores de ar, grandes fãs, exaustores de fumaça
Transportadores, misturadores, extrusoras, trituradores (comida, building material, mineração)
Chillers and large refrigeration compressors for central air conditioning
MCC motor control centre drawer units for 90kW motor circuits
(2) AC-1 Resistive Load
High-power heating elements, fornos de resistência
Main circuit switching of high-power circuits inside distribution cabinets
(3) AC-6B Capacitor Switching
Capacitor bank switching for reactive power compensation cabinet (reactor required to suppress inrush current)
Correspondência: 3RU thermal relay for motor overload protection; 2NO+2NC auxiliary contacts for PLC running feedback and fault interlock.
- Preferred Scenarios for 3RT5056-6AP36 (Domestic Local Version)
- Domestic panel projects, domestic factories, AVAC, fornecimento de água & drenagem, general factory automation
Complete CCC certification for domestic projects, sufficient stock and cost advantage, preferred by most EPC and cabinet manufacturers.
- Domestic municipal projects: Estações de tratamento de águas residuais, municipal pump stations, building HVAC cabinets
- Domestic machinery OEM: Fãs, compressores de ar, chiller units sold in domestic market
- Ordinary motor circuits in domestic power plants, metallurgy and chemical plants (no mandatory imported component requirement by client)
- Retrofit replacement for old contactors, tight budget and fast delivery required
✅ Adequado para: Domestic projects without mandatory UL/CSA certification or German origin requirement
- Preferred Scenarios for 3RT1056-6AP36 (German Imported Version)
- Máquinas de exportação & equipamento (export to Southeast Asia, Médio Oriente, Europe and other overseas sites)
Full set of international certifications CE, UL, CSA to meet overseas owner and customs requirements.
- New construction projects of foreign-invested factories where technical specification explicitly requires SIEMENS components made in Germany
- Overseas EPC projects, control cabinets exported together with equipment, certificate of origin required
- High-end pharmaceutical and semiconductor foreign projects where imported components are specified by client
- Spare part replacement for legacy equipment: Original unit fitted with 3RT1056 and client requires identical OEM spare parts
✅ Adequado para: Máquinas de exportação, projetos no exterior, client specified imported components, mandatory UL/CSA certification
- Seleção para evitar armadilhas
- Identical load rating: Both can drive 90kW motors. 3RT5056 has no limitation for heavy-duty applications; only differs in origin and certification documents.
- For domestic projects without “imported contactor” clause in specification, 3RT5056 is preferred for shorter lead time and better price.
- For export to Europe / América do Norte, select 3RT1056 and confirm in advance whether UL/CSA certificates are required.
- Heavy vibration & dusty heavy industry environments (mineração, cement plant): Both have identical mechanical life. Installation and heat dissipation requirements are the same; selection only depends on origin requirement.
- Cenários não aplicáveis
Direct-on-line starting for motor power exceeding 90kW; soft starter recommended for higher power.
Frequent jogging, frequent forward/reverse AC-4 duty (accelerated contact wear, derating evaluation required)
Safety circuits and emergency stop safety functions (SIEMENS safety contactor 3RT2 series should be adopted)
Contator,disjuntor,sensor,Codificador,CLP,Conversor