Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker - Contator,disjuntor,sensor,Codificador,CLP,Conversor

Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

 Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker - Contator,disjuntor,sensor,Codificador,CLP,Conversor

disjuntor/

Siemens 3RV6011-1AA15 Motor Protection Circuit-Breaker

Nome completo do produto: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector) 3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15 Model Decoding 3RV6 0 11-1 AA 15 3RV6: SIRIUS domestic motor protection circuit-breaker 0: Motor protection application 11: Frame size S00 (Width 45 mm) 1: Standard breaking capacity AA: Thermal overload setting ...

  • Detalhes do produto

Nome completo do produto: SIRIUS 3RV6 Series Domestic Motor Protection Circuit-Breaker (Motor Starter Protector)

3RV6 = Domestic version; 3RV2 = Imported equivalent replacement model: 3RV2011-1AA15

Decodificação de modelo

3RV6 0 11-1 AA 15

3RV6: SIRIUS domestic motor protection circuit-breaker

0: Motor protection application

11: Frame size S00 (Width 45 mm)

1: Capacidade de interrupção padrão

AA: Thermal overload setting range 1.1-1.6 A

15: Built-in side auxiliary contacts 1NO+1NC (10 = without auxiliary contacts)

Parâmetros técnicos principais

ItemEspecificação
Thermal overload setting (UM)1.1 … 1.6 UM
Short‑circuit release N‑release21 UM (13×Em)
Classe de viagemCLASS 10 (Normal motor starting)
Pólos do circuito principal3P
Tensão operacional nominalAC‑690 V
Rated motor power @400V0.55 kW
Breaking capacity Icu@400V100 ka
RescisãoTerminais de parafuso
Contatos auxiliaresIntegrated side‑mounted 1NO + 1NC
Montagem35 mm DIN‑rail, or screw mounting
Dimensões geraisW45 mm × H97 mm × D91 mm
Grau de proteçãoIP20 (Front side)
Temperatura operacional‑20 … +60 ℃
HS customs code85362010

Pedido & Substituições

  1. Imported OEM replacement: 3RV2011-1AA15 (identical functions and specifications, made in Germany)
  2. Version without auxiliary contacts: 3RV6011-1AA10
  3. Domestic 3RV6 and imported 3RV2 are fully interchangeable with identical mounting dimensions and wiring.

Aplicações Típicas

Protection for small-size three-phase motors, fornecendo sobrecarga, short-circuit and phase-failure protection. Widely used in control cabinets, fãs, pumps and small conveyors. Can be combined with contactors to form a motor starting unit.

Acessórios compatíveis (S00 frame size)

Side-mount auxiliary contacts: 3RV6901-1A

Side-mount auxiliary contacts: 3RV6901-1E (already integrated in this model)

Liberação de subtensão, liberação de derivação, rotary operating handle and other expandable accessories.

Cenários de aplicação de Siemens 3RV6011-1AA15

Configuração atual: 1.1-1.6UM, compatible with 0.55kW three-phase motor at 400V, Class 10 trip characteristic, built-in 1NO+1NC auxiliary contacts, S00 frame size (45 mm largura). Fornece sobrecarga, short-circuit and phase-failure protection. Auxiliary contacts can be used for fault alarm and PLC signal feedback.

  1. Typical Motor Load Applications
  2. Pequenos fãs & cooling fan motors

Equipment cooling fans, cabinet ventilation fans, small HVAC fans. Continuous-run loads with moderate starting current. Offers phase-loss and overload protection; auxiliary contacts transmit fan fault signals.

  1. Miniature water pumps & bombas de circulação

Small process circulation pumps, bombas de água de resfriamento, laboratory pumps. Rapid thermal tripping upon pump stalling to prevent motor burnout.

  1. Small conveying & drive equipment

Mini belt conveyors, small rollers, feeding mechanisms, compact conveyor drives. For standard direct-on-line (DOL) começando. Combined with 3RT7 contactors for complete motor starter assemblies.

  1. Machine-tool auxiliary drive motors

Machine-tool coolant pumps, bombas de lubrificação, small feed auxiliary motors. Compact cabinet installation; fault signals sent to PLC for equipment alarm.

  1. Small actuators for packaging & máquinas de impressão

0.55 kW three-phase drive motors for compact packaging machines, labellers and printing auxiliary equipment.

  1. Non-motor & System-level Applications
  2. Protection for small three-phase control transformers

Overload and short-circuit protection for low-inrush small-size transformers. Not suitable for transformers with high magnetizing inrush current.

Observação: Use 3RV64 series for transformers with heavy inrush to avoid nuisance tripping.

  1. Compact motor feeder circuits inside control cabinets

High-density DIN-rail layout for multi-loop small-motor cabinets. Built-in 1NO+1NC eliminates extra auxiliary contact modules; outputs trip/closed status signals to PLC and HMI.

  1. Motor protection inside standalone machines

Integrated protection for built-in machine motors. Can also serve as an isolating switch for maintenance.

  1. Industry Sectors

Automação industrial: Custom special-purpose machinery, equipamento de teste

AVAC: Unit internal small fans and circulation pumps

Máquinas-ferramentas: Coolant and lubrication pump motors

Manuseio de materiais: Mini conveying mechanisms

Laboratório & equipamento de teste: Small three-phase drive assemblies

Compact control cabinets & OEM export equipment (Domestic 3RV6, cross-compatible with imported 3RV2011-1AA15)

  1. Recommended System Configurations
  2. Direto on-line (DOL) starter: 3RV6011-1AA15 + 3RT7 contactor. Complete motor protection-starter unit. 3RA1931 bus module enables fast assembly without inter-wiring, economizando espaço no armário.
  3. Signal feedback configuration: Contato NF para alarme de falha; NO contact for closed-state feedback, connected to PLC digital input modules.
  4. Non-applicable Conditions
  5. Frequent heavy-duty starting and high-shock loads (incompatible with Class 10 trip characteristic)
  6. Motors with rated current outside 1.1-1.6 A range
  7. Transformers with high magnetizing inrush risk of unwanted tripping
  8. Outdoor environments with heavy dust or corrosive atmosphere (requires additional protective enclosure)

Rated Operational Voltage of 3RV6011-1AA15

Main-circuit rated operational voltage Ue: AC-690V (50-60 Hz)

Especificações detalhadas

  1. Common operating voltages for motors

AC400V: Standard three-phase motor operating condition, matches 0.55 kW motor

AC230V / AC500V / AC690V are permissible. Breaking capacity remains 100 kA at 690 V.

  1. Rated voltage for auxiliary contacts (1NÃO+1NC)

AC-15: Máx.. 230 V; DC-13: Máx.. 60 V

⚠️ Auxiliary contacts shall not be connected to 690 V main circuits. Reserved for low-voltage signal circuits only.

  1. Tensão nominal suportável de impulso Uimp: 6 kV

Standards reference: IEC 60947-2, IEC 60947-4-1. Domestic 3RV6 and imported 3RV2011-1AA15 share identical voltage ratings.

Overall Dimensions of Siemens 3RV6011-1AA15 (S00 Frame Size)

ItemValor
Largura L45 milímetros (DIN‑rail footprint width in cabinet)
Altura H97 milímetros
Profundidade D91 milímetros (Body depth, protrusion depth after DIN‑rail mounting)
Tamanho do quadroS00
Peso líquidoAprox.. 0.29 kg

Mounting Instructions

  1. Opções de montagem: 35 mm DIN-rail snap-on mounting, or base-plate screw fastening
  2. Orientação de montagem: Any mounting position is allowed
  3. Clearance requirements:

Folga vertical: ≥50 mm

Folga lateral: ≥30 mm

Rear clearance: 0 milímetros (flush against DIN-rail)

Imported replacement 3RV2011-1AA15 has identical dimensions for direct drop-in replacement.