Siemens 6ED1052-1FB08-0BA2 (LOGOTIPO!230RCE V8.4) Cenários de aplicação
Key characteristics: Direct 230 V AC supply, saídas de relé, on-board display, Ethernet (MQTT / Modbus-TCP / embedded web pages), multiplexable 0-10 V analog inputs. Suitable for small-I/O-count logic control with 220 V supply and remote monitoring requirements. Programmed via graphical function-block editor without complex Programação CLP. Native I/O: 8 DE / 4 FAZER; expandable with LOGO!8-series expansion modules.
Full Designation: LOGOTIPO! 230RCE Logic Controller Base Module, com display, Ethernet, Saída de relé, 115-230 V AC/DC Supply
- Model Code Decoding
| Segmento de código | Descrição |
| 6ED1052 | LOGOTIPO! base main unit series |
| 1 | With display; 0 = without display |
| FB | Tipo de fonte de alimentação: FB = 115‑230 V AC/DC, Saída de relé(R) |
| 8 | Hardware version 08 (LOGOTIPO! 8 hardware platform) |
| 0BA2 | Firmware version: V8.4 (supports MQTT, Web‑Server, Micro‑SD Card) |
- Especificações elétricas principais
| Item | Parâmetro |
| Tensão de alimentação | 100‑253 V AC/DC (nominal 115/230 V), 47‑63 Hz |
| Digital Inputs DI | 8‑channel (I1‑I8); I1/I2/I7/I8 are multiplexable for 0‑10 V analog inputs |
| Digital Outputs DO | 4‑channel relay outputs Q1‑Q4 |
| Carga resistiva: 10 A per channel; Carga indutiva: 3 A per channel | |
| ⚠️ Outputs have no built‑in short‑circuit protection; external fuses are mandatory | |
| Capacidade do Programa | Máx.. 400 function blocks; Real‑time clock backup 480 h for retaining timer parameters upon power loss |
| Interface de comunicação | 1×RJ45 Ethernet; Suporta: LOGOTIPO! internal protocol, Modbus‑TCP, MQTT, built‑in Web‑Server, registro de dados, custom web pages |
| Armazenar | Micro‑SD card slot (program backup, firmware upgrade) |
| Software de programação | LOGOTIPO! Soft Comfort V8.4 or higher |
| Montagem | 35 mm DIN‑rail mounting |
| Dimensões Gerais | W71.5 × H90 × D60 mm, IP20 |
| Ambient Operating Temperature | ‑20 ℃ ~ +55 ℃; Armazenar: ‑40 ℃ ~ +70 ℃ |
| Certificações | CE, UL, FM, RoHS |
- Hardware & Notas de fiação
- Input terminals I1-I8 are universal AC/DC inputs matched to the 115-230 V supply rating. When I1/I2/I7/I8 are software-enabled as 0-10 V AI, these terminals shall receive voltage signals and must NOT be connected to high-voltage mains.
- Relay outputs are potential-free contacts; common terminals can be wired to circuits of different voltage levels. Para cargas indutivas (contatores, válvulas solenóides), RC snubber circuits must be connected in parallel.
- LAN port: For programming, remote web-based monitoring, MQTT cloud uplink; built-in web pages are accessible directly via web browser.
- SD-Card: Importar / export programs & logs, perform firmware upgrade.
⚠️ Critical Prohibitions
Do not exceed ratings: 10 A resistive / 3 A inductive for relay outputs. Do not drive high-power motors directly. External fuses are required.
When channels are multiplexed for analog input (0-10 V), applying AC230 V will destroy input circuitry.
Classificação IP20: For cabinet-mount use only. Not for outdoor installation, condensing or corrosive environments.
- Compatible Replacement Options
– Direct drop-in replacement: `6ED1052-1FB08-0BA2` (LOGOTIPO! V8.4, current order reference)
– Legacy compatible variant: `6ED1052-1FB08-0BA1` (V8.3, identical pin-out, backward-compatible program; older firmware lacks MQTT features)
Observação: LOGOTIPO!8.x (0BA8) base units are NOT compatible with legacy 0BA7 / 0BA6 expansion modules. Use LOGO!8-series expansions only (por exemplo. 6ED1055-1FB00-0BA2).
- Cenários típicos de aplicação
Automação predial: controle de iluminação, fã & pump management, AVAC, auxiliary access-control logic; stand-alone simple machine control; agricultural irrigation; interlock logic for packaging machinery; IoT edge data acquisition, MQTT uplink to SCADA / cloud platforms.
- Conteúdo do pacote
Main unit ×1
Printed quick-start manual ×1
❗ Excluded: Cabo Ethernet, SD-card, external fuses, expansion modules (order separately).
5.1 Building HVAC (Primary Use-Case)
- Controle do ventilador: Exaustores, fresh-air supply-fan interlocks; scheduled start-stop, differential-pressure trigger, alarme de falha; web-based remote status visualization.
- Controle da bomba: Domestic-water / circulation pumps with duty-standby automatic change-over, overload alarm, water-level interlocking.
- Lighting-control system
– Scheduled lighting for workshops, underground car-parks and public corridors; PIR trigger, holiday calendar scheduling.
– Fire-alarm interlock for lighting cut-off; upload lighting status via Ethernet to central control room.
- Air-handling unit & damper control: Damper actuators, heater simple logic; 0-10 V channels acquire temperature / humidity transmitters for basic closed-loop regulation.
- Cooling-tower & roof ventilation: Local logic plus remote web monitoring; MQTT data upload to building BA-system.
Vantagens: No separate 24 V power supply required for 230 V operation; built-in web-server removes need for dedicated SCADA for browser-based supervision.
5.2 Stand-alone Simple Machine Control
For low-I/O machinery where full-scale PLC is not justified
- Packaging auxiliary equipment: Conveyor start-stop interlocks, silo level detection, indicadores de alarme, timed discharging cycles.
- Injection-molding auxiliary & cooling units: Cooling-fan / circulation-pump logic; 0-10 V temperature acquisition, fault-alarm output.
- Air-compressor auxiliary control: Exhaust-fan, timed solenoid drain valve, aggregated fault-signal output.
- Gate / roller-shutter / lifting-door logic: Limit-switch monitoring, interlocks, atraso de tempo, manual-auto mode switching.
⚠️ Limitation: Máx.. 3 A inductive rating for relay contacts; use intermediate relays for large contactor coils. Not applicable for high-speed pulse-based motion control.
5.3 Agricultura & Tratamento de Água
- Greenhouse simplified automation: Fã & shade-blind actuation; 0-10 V temperature-humidity acquisition; timed irrigation solenoids; MQTT upload to IoT platform.
- Small-scale wastewater / reclaimed-water equipment: Pump rotation scheduling, high-low level interlocks, timed chemical-dosing, alarm outputs.
- Fountains & water-feature installations: Cyclic multi-pump sequencing, fault-alarm logic.
5.4 Electrical Cabinet & LV Panel Auxiliary Logic
- Low-voltage switchgear auxiliary logic: Bus-coupler interlocking, cabinet cooling-fan control, cabinet-door status acquisition, collective fault-alarm output.
- VP / energy-storage auxiliary cabinets: Cabinet-heater / dehumidifier & cooling-fan temperature-driven / timed control; alarm telemetry over Ethernet.
- UPS emergency-power auxiliary logic: Mains-failure detection, switching logic, audible-visual alarm outputs.
5.5 IoT Edge Acquisition (V8.4-Exclusive MQTT Feature)
Core enhancement versus older V8.3 (-0BA1 firmware):
- Acquire digital status and 0-10 V analog measurements; transmit via MQTT to private / public cloud servers (por exemplo. Alibaba Cloud).
- Operate as Modbus-TCP slave for connection to HMI / host supervisory systems. Built-in web-server for PC / mobile-browser status access without dedicated software.
- Micro-SD-card data logging: record temperature, runtime timestamps; export CSV files for maintenance review.
❌ Non-Applicable Scenarios (Selection Pitfalls)
- High-speed counting, pulse-output, servo motion control: Not supported by LOGO!.
- Large I/O quantity: Native 8DI /4DO; maximum expandable to 24DI /16DO. For larger systems select S7-1200 PLC.
- Frequent switching of heavy inductive loads: Limited mechanical relay contact life; use transistor-output variants for high-cycle applications.
- Hazardous / explosive-risk zones: IP20 unit must be installed inside certified explosion-proof enclosures; cannot be mounted directly in Zone1/Zone2.
- High-precision PID closed-loop control: Only basic PID function-block available; use standard PLC for demanding closed-loop performance.
Typical System Configuration Examples
Temperature acquisition: Multiplex I1 as 0-10 V AI for connection to temperature transmitter.
Contactor driving: LOGOTIPO! relay output → intermediate relay → contactor coil.
Monitoramento remoto: RJ45 LAN to local network; access embedded web-server via browser.
I/O expansion: 6ED1055-1FB00-0BA2 (230 V relay expansion module).
Siemens 6ED1052-1FB08-0BA2 (LOGOTIPO!230RCE V8.4) Full Technical Datasheet
Full Designation: LOGOTIPO! 230RCE Logic Controller Base Module, com display, Ethernet, Saída de relé, 115-230 V AC/DC, Firmware V8.4 with MQTT support
Power Supply Ratings
| Item | Especificação |
| Tensão de alimentação | 100‑253 V AC / CC (nominal 115‑230 V AC/DC) |
| AC Frequency Range | 47‑63 Hz |
| Consumo de energia | Aprox.. 3.5 C |
| RTC Backup Duration | 480 h (20 days); retains real‑time clock and timer parameters after power loss |
I/O Terminal Specifications
| Item | Especificação |
| Digital Inputs DI | 8‑channel (I1‑I8); rated for 115‑230 V AC/DC signals. |
| I1, I2, I7, I8 software‑configurable as 0‑10 V analog inputs (IA), 10‑bit resolution | |
| Digital Outputs DO | 4‑channel potential‑free relay outputs Q1‑Q4 |
| Carga resistiva: 10 A per channel; Carga indutiva: 3 A per channel | |
| ⚠️ No built‑in short‑circuit protection; external fuses are mandatory | |
| Tipo de saída | Mechanical relay contacts; common terminals can be assigned to different voltage domains |
| Máx.. Expanded I/O | Unidade básica + LOGOTIPO!8 expansion modules: Máx.. 24DI /16DO |
Program & Memória
| Item | Especificação |
| Máx.. Function Blocks | 400 blocks (depends on block type) |
| Software de programação | LOGOTIPO! Soft Comfort V8.4 or higher |
| Storage Media | Micro‑SD card slot: program backup, firmware update, CSV‑format data log export |
| Mostrar | 6‑line backlit LCD; local push‑buttons for parameter modification & status review |
Interface de comunicação (RJ45 Ethernet 10/100 Mbit/s)
LOGOTIPO! native protocol (programação, multi-LOGO! LAN networking)
Modbus-TCP (Mestre / Escravo)
MQTT Client (V8.4 new feature, for private / public cloud connection)
Embedded Web-Server: browser-based supervision, custom web pages, registro de dados, email alarm notification
❗ Does NOT support Profinet, CANopen, KNX.
Mecânico & Montagem
| Item | Especificação |
| Montagem | 35 mm standard DIN‑rail (4‑module width) |
| Dimensões Gerais | W71.5 mm × H90 mm × D60 mm |
| Proteção de entrada | IP20 (cabinet‑installation only) |
| Peso | Aprox.. 200 g |
Condições Ambientais
| Item | Faixa |
| Temperatura ambiente operacional | ‑20 ℃ ~ +55 ℃ (inside control cabinet) |
| Armazenar & Temperatura de Transporte | ‑40 ℃ ~ +70 ℃ |
| Umidade relativa | 5 %‑95 % RH, condensation not permitted |
| Vibração & Choque | Compliant with IEC60068‑2‑6 / IEC60068‑2‑27 industrial standards |
Aprovações & EMC
Certificações: CE, UL, FM, RoHS
EMC: EN55011 Class B (residential environment), EN61000-6-2 industrial immunity
Critical Limitations (Selection Constraints)
- Relay outputs are not suitable for high-cycle switching; intermediate relays must be used for heavy loads.
- When channels are configured for 0-10 V analog input, AC230 V mains must never be connected, as input hardware will be destroyed.
- No native high-speed counter, pulse-output or motion-control functions.
- Only LOGO!8-series expansion modules (order suffix-0BA2) are compatible; legacy 0BA7 / 0BA6 expansions will not work.
- No internal short-circuit protection; external fuses are required for all relay-output circuits.
Firmware Variant Comparison
6ED1052-1FB08-0BA1: V8.3, identical hardware pin-out; no MQTT, limited web-server capability.
6ED1052-1FB08-0BA2: V8.4, adds MQTT, enhanced web-server and improved email-alarm functions; current active ordering reference.
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares