Siemens 7MF1567-3CB00-3AA1 Gauge Pressure Transmitter - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

 Siemens 7MF1567-3CB00-3AA1 Gauge Pressure Transmitter - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

elétrica/

Siemens 7MF1567-3CB00-3AA1 Gauge Pressure Transmitter

7MF1567: SITRANS P220 series, full stainless steel welded structure, dedicated for high pressure and refrigerant service, piezoresistive gauge pressure transmitter 3CB00: Measuring range: 0 … 16 bar (gauge) Overpressure limit: 40 bar Burst pressure: aprox.. 80 bar 3AA1: Saída: 4–20 mA 2-wire system Process connection: 1/2″-14 NPT internal thread (widely used in North America, different ...

  • Detalhes do produto

7MF1567: SITRANS P220 series, full stainless steel welded structure, dedicated for high pressure and refrigerant service, piezoresistive gauge pressure transmitter

3CB00:

Measuring range: 0 … 16 bar (gauge)

Overpressure limit: 40 bar

Burst pressure: aprox.. 80 bar

3AA1:

Saída: 4–20 mA 2-wire system

Process connection: 1/2″-14 NPT internal thread (widely used in North America, different from G1/2external thread of 1AA1)

Conexão elétrica: M16 connector (DIN EN 175301-803-A)

Explosion protection: Non-explosion-proof (tipo padrão)

  1. Parâmetros técnicos principais (2026 Official Manual)
  2. Medição & Desempenho

Measured variable: Gauge pressure

Measuring range: 0–16 bar

Precisão: ±0.25% FS (típico), máx.. ±0.5% FS

Non-linearity: ≤0.25% FS

Repetibilidade: ≤0.1% FS

Tempo de resposta: <5 EM (T99)

Long-term stability: 0.25% FS per year

  1. Especificações Elétricas

Output signal: 4–20 mA 2-wire

Fonte de energia: DC 7–33 V (24 VDC recommended)

Capacidade de carga: R ≤ (U-10 V) / 0.02 UM

Máx.. load resistance at 24 V: aprox.. 700 Oh

  1. Faixa de temperatura

Medium temperature: -30 … +120 ℃

Temperatura ambiente: -25 … +85 ℃

Temperatura de armazenamento: -40 … +100 ℃

  1. Mechanical Structure & Material

Wetted & non-wetted parts: Full stainless steel (1.4435/316eu), gasket-free fully welded design, ideal for high pressure and refrigerant media

Process connection: 1/2″-14 NPT internal thread

Conexão elétrica: M16 connector, IP65 protection grade

Peso: aprox.. 0.2 kg

Origem: Suíça (CH)

III. Wiring Instruction (M16 Connector, 4–20 mA 2-wire)

Pin definition (Standard EN 175301-803-A):

Alfinete 1 (+): 24 VCC positivo

Alfinete 2 (-): 4–20 mA signal return (connect to PLC AI positive terminal)

Alfinete 3: Spare

Educação Física: Earth connection (housing grounding)

Notas de fiação:

2-wire design: Power positive shares line with signal negative

Shielded cable single-ended grounding (control cabinet side only)

Recommended cable: 0.5–1.5 mm² shielded twisted pair cable

  1. Instalação & Diretrizes de Operação
  2. Installation position: Vertical or horizontal mounting available; keep away from severe vibration
  3. Sealing treatment: Use PTFE tape or matched sealant for NPT thread connection
  4. Zero point calibration:

Output shall be 4.00 mA under zero pressure condition

Adjust zero trim screw at connector side if necessary

  1. Applicable media:

✅ Gas, liquid, steam, refrigerants (R134a, R410A etc.)

✅ Slightly corrosive media (compatible with stainless steel)

❌ Strong corrosive fluid (concentrated acid, strong alkali), high abrasion slurry

  1. Common Alternative & Modelos semelhantes (Faixa & Connection Comparison)
Model No.Faixa (bar)Process Connection
7MF1567-3CA00-3AA10–101/2″ NPT Internal
7MF1567-3CB00-3AA10–161/2″ NPT Internal
7MF1567-3CD00-3AA10–251/2″ NPT Internal
7MF1567-3CE00-3AA10–401/2″ NPT Internal
7MF1567-3CB00-1AA10–16G1/2External (BSP)
  1. Solução de problemas comuns
  2. Fixo 4 mA output

Abnormal power supply (abaixo 7 V)

Open circuit in signal loop

  1. Fixo 20 mA output

Over-range pressure (exceed 16 bar)

Diaphragm damage

  1. Signal drift & unstable reading

Poor grounding or electromagnetic interference

Sharp temperature fluctuation

Excessive installation stress

VII. Order Information & Lead Time (2026 Referência)

Production status: Active in production

Standard delivery time: 1 working day (European warehouse)

Reference price: About CNY 700–900 (tax included, 1-5 peças)

Falhas Comuns, Causes and Quick Solutions for Siemens 7MF1567-3CB00-3AA1 (P220) Pressure Transmitter

  1. No output, zero current (0mA)
  2. Insufficient supply voltage

Causa: Voltage lower than 7VDC, large line voltage drop

Solução: Measure terminal voltage, keep stable at 20~26VDC

  1. Reverse positive and negative wiring

2-wire system rarely burns out device but causes no signal

Solução: Swap wiring of pin 1 e alfinete 2

  1. Broken cable or loose terminal connection

Solução: Conduct continuity test and fasten M16 connector

  1. Internal circuit damage of transmitter

Fenómeno: No response after power-on, invalid after power replacement

  1. Constant 4mA minimum output without change
  2. Actual pressure is zero under normal static status
  3. Blocked pressure tapping pipeline

Medium crystallization, oil dirt and impurities block pressure inlet

Solução: Purge and dredge pressure guiding pipe

  1. Diaphragm stuck by foreign objects
  2. Wrong measuring range or mismatched PLC configuration range
  3. Severe zero drift

Solução: Trim zero point on site under zero pressure

  1. Constant 20mA full-scale output
  2. Actual pressure far exceeds 16 bar full range

Solução: Reduce pressure and verify field actual pressure

  1. Pressure trapped inside pipeline unable to release
  2. Pressure diaphragm breakdown and failure

Most frequent hardware fault, replacement is required

  1. Short circuit of signal wire

Positive and negative wire short circuit leads to full current output directly

  1. Fluctuating and unstable signal reading
  2. Excessive on-site vibration (installed near pumps and fans)

Solução: Install shock-absorbing bracket and keep away from vibration sources

  1. Severe electromagnetic interference

Power cables laid together with signal cables without shielding

Solução: Single-end grounding for shielded twisted pair, separate wiring layout

  1. Pulsating medium pressure itself

Solução: Install damper and pressure stabilizing buffer tank

  1. Temperature drift caused by drastic ambient temperature change
  2. Fiação solta, water ingress and oxidation inside connector
  3. Large measurement deviation, inaccurate reading, high or low indication
  4. Uncalibrated zero point (drift after long-term operation)

Solução: Calibrate zero under zero pressure to recover accuracy

  1. Static pressure error caused by improper installation position
  2. Exceed 120℃ medium temperature damages measurement precision
  3. Sobre 40 bar overload pressure causes permanent offset
  4. Inconsistent range setting between PLC program and actual transmitter range
  5. Fault caused by water ingress and dampness
  6. Poor sealing of M16 connector leads to water penetration

Fenómeno: Random reading fluctuation, intermittent normal operation

Solução: Dry internal parts, replace waterproof connector and reapply sealing glue

  1. Rainwater and condensed water penetrate into internal structure for outdoor installation
  2. Overload resistance fault

Fenómeno: Normal supply voltage but current output insufficient

Causa: Excessive internal resistance of rear PLC module exceeding 700Ω load limit

Solução: Shorten signal cable length and reduce loop resistance

  1. Typical Vulnerable Defects Exclusive to P220 Series
  2. Excessive force during NPT thread installation squeezes internal diaphragm and causes permanent scrappage
  3. Zero drift easily occurs after long-term operation with refrigerant and low-temperature media
  4. Failure rate doubles under high-frequency vibration environment
  5. Fully welded structure disables disassembly and maintenance, direct replacement needed once damaged
  6. Three-step Quick Self-check Method
  7. Cut off power supply, stand by for 3 minutes then re-energize
  8. Release all pressure to check if output returns to 4mA
  9. Apply standard pressure to verify linear output up to 20mA

Conclusão Central

7MF1567-3CB00-3AA1 (P220) adopts factory integrated fully welded sealing structure. The diaphragm cannot be replaced separately on site. The whole transmitter must be replaced once diaphragm is damaged.

Reasons for Non-separable Diaphragm Replacement (Core Structure of P220)

Model feature: 7MF1567 is fully welded SITRANS P220 transmitter without sealing gasket or detachable pressure cover

Diaphragm structure: 316L/1.4435 diaphragm is directly welded on pressure cavity; pressure cavity and electronic chamber are integrated via laser welding or argon arc welding with no detachable bolts or clamps

Official specification: The transmitter is maintenance-free. Repair work is only available by Siemens authorized personnel and on-site disassembly is prohibited.

Typical Phenomena of Damaged Diaphragm

Fixed 20mA output (over-range or diaphragm breakdown)

Extreme zero drift unable to be calibrated

Medium leakage at thread root or housing joint

Random data fluctuation and internal corrosion caused by water ingress via M16 connector

On-site Replacement Solutions

Solução 1: Direct overall replacement (Recomendado)

Spare part model: 7MF1567-3CB00-3AA1 (same range & conexão)

Replacement steps:

  1. Cut off power, release pressure and close pressure valve
  2. Remove M16 connector
  3. Unscrew 1/2NPT thread gently with spanner (avoid squeezing new diaphragm)
  4. Wrap PTFE tape on new thread, tighten manually then turn 1/4 circle with spanner
  5. Complete wiring, power on and perform zero calibration

Solução 2: Factory return maintenance (High cost & long cycle)

Maintenance content: Replace full welded pressure module and recalibrate

Custo de manutenção: Sobre 60-80% of new product price, delivery cycle 2-4 semanas

Not cost-effective compared with direct replacement

Risks of Forced Disassembly

  1. Welded cavity cannot be opened without damage, resulting in housing deformation and diaphragm scrap
  2. Ultra-thin diaphragm (0.1-0.2milímetros) is easy to crack under prying, knocking and extrusion
  3. Siemens does not sell separate P220 diaphragm or pressure module, only complete transmitters available
  4. Disassembly will invalidate IP65 protection and explosion-proof certification, bringing potential safety hazards

Preventive Measures for Diaphragm Damage

  1. Strictly control installation torque for NPT thread, forbid excessive tightening
  2. Keep working pressure within 16 bar rated range, avoid instantaneous high pressure impact
  3. Install shock absorber when mounting near pumps and compressors to prevent fatigue crack of diaphragm
  4. Limit medium temperature below 120℃ to avoid metal creep and zero drift
  5. Apply sealing glue on M16 connector for reliable waterproof performance

Anterior:

Próximo:

Deixe uma resposta

Deixe um recado