Danfoss VZH117AGANA is a 2nd-generation variable speed scroll compressor with a displacement of 116.9 cm³. It adopts IPM Interior Permanent Magnet synchronous motor, designed for R410A refrigerant systems. Faixa de tensão nominal: 380-480V/3PH/50-60Hz, cooling capacity: aprox.. 8~11 tons of refrigeration. Its core advantages include high efficiency across full speed range (≥92%), wide frequency adjustment (25-100Hz), precise temperature control (±0,5°C) and low vibration & baixo ruído. It is ideally applied to commercial air conditioners, precision air conditioners, heat pump systems and combined parallel systems, which can effectively boost system energy efficiency (energy saving over 30%) and reduce operating costs.
- Definição de código de modelo
| Seção | Código | Significado |
| Código da série | VZH | Danfoss 2nd-gen Variable Speed High-efficiency Scroll Compressor |
| Displacement | 117 | Nominal displacement 116.9 cm³ |
| Voltage Code | G | 380-480V 3-phase 50/60Hz; Code J: 200-240V |
| Configuração | UM | Single unit; B: Parallel connection, brazed joint with oil sight glass |
| Tipo de motor | N | Built-in IPM motor, no internal motor protection (protected by inverter) |
| Refrigerant | UM | Exclusive for R410A, matched with POE 160SZ refrigeration oil |
Pedido nº.: 120G0014 (single package)
- Main Technical Specifications
| Categoria | Item | Valor | Remark |
| Basic Info | Refrigerant | R410A | Not applicable for other refrigerants |
| Tipo de motor | Built-in IPM motor | Efficiency ≥92% full speed range | |
| Capacity Control | Inverter-driven | Matched with Danfoss CDS303 dedicated inverter | |
| Faixa de frequência | 25-100Hz (1500-6000rpm) | Base speed 3000rpm@50Hz, 3600rpm@60Hz | |
| Desempenho | Displacement | 116.9 cm³ | Standard working condition |
| Cooling Capacity@50Hz | 27.9kW (8.0TR) | ARI standard condition | |
| Cooling Capacity@60Hz | 37.9kW (10.8TR) | ARI standard condition | |
| Rated Load Ampere (RLA) | 44UM | 380V 50Hz | |
| Max Trip Current (MMT) | 55UM | Inverter protection setting | |
| Elétrica | Fonte de energia | 380-480V 3PH 50/60Hz | Working voltage: 342-528V |
| Resistência da bobina | 0.08Ω @25℃ | Phase-to-phase resistance | |
| Classe de Proteção | IP54 (with cable gland) | Terminal box protection standard | |
| Mecânico | Suction Pipe Size | 1 3/8 in ODF | Brazed connection |
| Discharge Pipe Size | 7/8 in ODF | Brazed connection | |
| Overall Height | 542milímetros | Including valves | |
| Outer Diameter | 243milímetros | Shell outer size | |
| Peso líquido | 64.922kg | Excluding package | |
| Oil Charge Volume | 3.6eu | POE 160SZ refrigeration oil | |
| Pressão | Max High Side Working Pressure | 48.7bar | Operating pressure |
| Max Low Side Working Pressure | 33.3bar | Operating pressure | |
| High Side Test Pressure | 45bar | Hydraulic test pressure | |
| Low Side Test Pressure | 33.3bar | Hydraulic test pressure | |
| Temperatura | Max Discharge Temperature | 150℃ | Discharge temperature limit |
| Max Suction Temperature | 55℃ | Suction temperature limit | |
| Min Ambient Temperature | -35℃ | Common limit for high & low side | |
| Certificação | CE Certificate | Sim | Comply with EU standards |
| UL Certificate | Sim | Comply with US standards | |
| UKCA Certificate | Sim | Comply with UK standards | |
| Conformidade com RoHS | Sim (partial exemption) | Meet EU & China RoHS requirements |
- Full VZH Series Model List (R410A)
| Displacement | Voltage Code | Tipo | Modelo | Número do pedido |
| 88Cm³ | G | Single | VZH088AGANA | 120G0078 |
| G | Parallel | VZH088BGANA | 120G0079 | |
| J. | Single | VZH088AJANA | 120G0080 | |
| J. | Parallel | VZH088BJANA | 120G0081 | |
| 117Cm³ | G | Single | VZH117AGANA | 120G0014 |
| G | Parallel | VZH117BGANA | 120G0083 | |
| J. | Single | VZH117AJANA | 120G0084 | |
| J. | Parallel | VZH117BJANA | 120G0085 | |
| 170Cm³ | G | Single | VZH170AGANA | 120G0086 |
| G | Parallel | VZH170BGANA | 120G0087 | |
| J. | Single | VZH170AJANA | 120G0088 | |
| J. | Parallel | VZH170BJANA | 120G0089 |
Modelos Especiais:
VZH117CGANA (industrial package, 120G0226)
VZH117CJDMA (compatible with R452B/R454B, 120G0327)
- Substituição & Modelos Equivalentes
4.1 Internal Danfoss Replacement
| Modelo Antigo | Novo modelo | Replacement Description |
| VSH117AGANA (fixed speed) | VZH117AGANA | Variable speed upgrade, efficiency improved over 30%, temp control accuracy ±0.5℃ |
| 1st-gen VZH117AGANA | 2nd-gen VZH117AGANA | Optimized motor design, wider operating range, higher IPM efficiency |
4.2 Cross-brand Equivalent
| Modelo Antigo | Novo modelo | Replacement Description |
| VSH117AGANA (fixed speed) | VZH117AGANA | Variable speed upgrade, efficiency improved over 30%, temp control accuracy ±0.5℃ |
| 1st-gen VZH117AGANA | 2nd-gen VZH117AGANA | Optimized motor design, wider operating range, higher IPM efficiency |
- Cenários de aplicação & Industry Cases
5.1 Aplicativos recomendados
| Aplicativo | Typical Working Condition | Principais vantagens |
| Commercial Air Conditioner | Rooftop unit, modular chiller, resfriador de água | Wide frequency range, high part-load efficiency |
| Precision Air Conditioner | Centro de dados, laboratory, equipamento médico | High temperature control accuracy, low vibration & barulho |
| Heat Pump System | Commercial heat pump, hot water unit | High pressure ratio design, excellent low-temperature heating performance |
| Process Cooling | Industrial equipment cooling, food processing | Stable output, adapt to harsh working conditions |
| Combined Parallel System | VZH117 + SH161/SH184 | Energy saving over 30%, adapt to large load fluctuation |
| Marca | Modelo Equivalente | Vantagens |
| Copeland | ZPV114KCE-TFD-420 | Higher IPM motor efficiency, superior oil management system |
| Emerson | Copeland Scroll Variable Speed | Higher integration of Danfoss CDS303 inverter, more complete protection functions |
| Mitsubishi Elétrica | EHV117 | Stronger parallel connection capability, support mixed parallel of VZH & SH series |
5.2 Not Recommended Applications
Household air conditioners (excessive power for residential use)
Systems using chlorine-containing refrigerants (only R410A applicable)
Oil-free lubrication systems (POE oil lubrication required)
Ultra-high pressure working conditions (exceeding 48.7bar high-side limit)
5.3 Practical Cases
Caso 1: Precision Air Conditioner Renovation for Data Center
Original system: Fixed-speed compressor, high power consumption, large temperature fluctuation
Solução: VZH117AGANA + CDS303 dedicated inverter
Effect: Energy consumption reduced by 35%, temperature fluctuation controlled within ±0.3℃, annual electricity cost saved about 120,000 RMB
Caso 2: Rooftop Unit Project for Commercial Complex
Demanda: 24-hour continuous operation with wide load fluctuation (10%-100%)
Solução: Parallel system composed of 4 sets VZH117AGANA compressors
Effect: Part-load efficiency increased by 40%, starting current reduced by 70%, vida útil mais longa
- Air Shipment Compliance & Certification Guide
6.1 Air Transport Confirmation
| Item | Status | Explicação |
| Built-in Lithium Battery | Não | Equipped with permanent magnet motor only |
| Dangerous Goods Classification | Non-dangerous goods | Comply with IATA DGR Class 9 regulation |
| Transport Restriction | No special restriction | Shipped as general cargo |
| Packaging Standard | Single / Industrial package | Follow standard Danfoss packaging specification |
6.2 Documentos de Certificação
CE Certificate: Available on Danfoss official product page
UL Certificate: Apply via Danfoss global product store
Manufacturer Declaration: Including RoHS, REACH compliance statement
- Selection Rules
- Capacity matching: VZH117AGANA equals 8-11TR, suitable for 1000-2000㎡ commercial space
- Voltage selection: G code for 380-480V, J code for 200-240V
- System matching: Must use original Danfoss CDS303 inverter
- Lubrication rule: Only original POE 160SZ refrigeration oil is allowed
- Installation standard: Suction pipe 1 3/8 polegada, discharge pipe 7/8 polegada, brazed connection
- Acessórios correspondentes
| Acessório | Modelo | Função |
| Inversor | CDS303 18.5kW | Dedicated drive with full protection |
| Installation Kit | 120Z0066 | Rubber pad, bolts and gaskets |
| Oil Separator | Special model | Necessary for long pipeline system (>10eu) |
| Discharge Temperature Protector | 7750009 | Prevent over-high discharge temperature |
| Oil Sight Glass | 8156019 | Real-time oil level observation |
Falhas Comuns & Troubleshooting for Danfoss VZH117AGANA Variable Speed Scroll Compressor
- Failure to Start & Inverter Alarm
Sintoma: No operation after power on, inverter alarms overcurrent, perda de fase, overload or undervoltage
Causas
- 3-phase power phase loss, unstable low voltage
- Wrong inverter parameter setting
- Internal scroll seizure or bearing stuck
- Loose main circuit wiring, poor contactor performance
- Damaged inverter power module
Soluções
- Measure actual 3-phase voltage, keep stable voltage at 360~420V
- Reset standard parameters: 4-pole motor, rated current 44A
- Manually rotate fan wheel, disassemble and repair if stuck
- Fasten all wiring terminals, replace aging contactors
- Repair or replace original Danfoss CDS302/CDS303 inverter
- Excessive Operating Current & Frequent Overload Protection
Sintoma: Running current far exceeds 44A, easy to trip under high frequency
Causas
- Overcharged refrigerant leads to excessive system load
- Dirty condenser causes poor heat dissipation and high high-side pressure
- Excessively high ambient temperature
- Long-term full-load high-frequency operation
- Liquid slugging increases operating resistance
Soluções
- Recycle redundant R410A refrigerant to standard filling quantity
- Clean condenser fins thoroughly
- Install unit away from heat source
- Set maximum speed limit on inverter
- Install gas-liquid separator to avoid liquid refrigerant return
- Excessively High Discharge Temperature (Over 135℃)
Sintoma: High temperature shutdown, sharp cooling capacity drop
Causas
- Insufficient refrigerant leads to superheated suction gas
- Abnormal expansion valve opening
- Insufficient outdoor fan speed and air volume
- System partial blockage
- Long-term low-frequency light-load operation
Soluções
- Supplement R410A refrigerant and check leakage points
- Adjust expansion valve opening matching actual load
- Repair outdoor fan to reach rated speed
- Flush pipeline to remove dirt blockage
- Adjust operating frequency range reasonably
- Abnormal Noise & Severe Vibration
Sintoma: Loud operating noise, unit shaking and pipeline resonance
Causas
- Aging shock absorption pad, uneven installation base
- No flexible vibration-absorbing pipe on suction/discharge pipeline
- Insufficient refrigeration oil causes internal wear
- Liquid slugging impact scroll components
- Loose compressor fixing bolts
Soluções
- Replace thickened shock pad and level installation base
- Install refrigeration vibration-absorbing hose on high/low pressure pipelines
- Check and replenish POE refrigeration oil regularly
- Add gas-liquid separator to avoid liquid slugging
- Fasten all fixing bolts and arrange pipelines properly
- Insufficient Cooling Capacity & Weak Frequency Rising
Sintoma: Slow cooling speed, no capacity improvement after frequency rise
Causas
- Abnormal pressure sensor signal
- Low inverter output torque parameter
- Air remaining inside system, incomplete vacuum pumping
- Internal scroll wear leads to low volumetric efficiency
- Blocked filter causes insufficient circulation flow
Soluções
- Calibrate pressure transmitter zero point and range
- Increase inverter torque gain parameter
- Re-pump deep vacuum to exhaust internal air
- Replace compressor if serious wear occurs
- Replace filter drier and dredge pipelines
- Frequent Start-Stop Cycle
Sintoma: Excessive start-stop times exceeding 12 vezes por hora
Causas
- Too narrow temperature & pressure control differential value
- Severe system pressure fluctuation
- Tensão de rede instável
- Over-low protection threshold causes false shutdown
Soluções
- Widen temperature and pressure start-stop differential range
- Stabilize system refrigerant pressure and optimize throttling control
- Install voltage stabilizer for 3-phase power supply
- Properly raise protection threshold to eliminate false protection
- Lubrication System Fault
Sintoma: Fast internal wear, short service life and frequent abnormal noise
Causas
- Failure of first oil change after 500 working hours
- Mixed use of non-specified refrigeration oil, oil deterioration
- Unbalanced oil distribution in parallel units
- Poor oil fluidity under long-term low-temperature operation
Soluções
- Strict maintenance rule: first oil change at 500h, regular change every 2000h / 1 ano
- Only use designated Danfoss POE 160SZ refrigeration oil, prohibit mineral oil mixing
- Check oil balance pipeline smoothness
- Preheat unit before loading under low ambient temperature
- Refrigerant Leakage Fault
Sintoma: Gradual system pressure drop, worse cooling effect
Causas
- Vibration crack on ODF brazed welding seam
- Loose sealing of oil balance connector
- Pinhole leakage on compressor shell
- Pipeline joint desoldering caused by thermal expansion and contraction
Soluções
- Pressurize for leakage detection and re-weld cracked joints
- Fasten oil balance connector and replace sealing gasket
- Use special leak repair agent for slight shell leakage, replace compressor for severe leakage
- Reserve expansion margin for pipelines to reduce thermal stress
- Out-of-control Variable Speed Regulation
Sintoma: Unstable rotating speed, no response to speed command
Causas
- Signal interference between inverter and main control board
- Abnormal built-in motor Hall sensor
- Inverter control board program disorder
- Grid frequency fluctuation affects variable speed output
Soluções
- Shield and ground communication wire, keep away from high-power power lines
- Inspect Hall signal of permanent magnet motor
- Restore inverter factory settings and re-match compressor parameters
- Stabilize grid power frequency
- Daily Maintenance Precautions
- Do not use non-original universal inverter, easy to burn out motor without built-in protection
- Only adopt R410A refrigerant, no alternative refrigerant allowed
- Control start-stop times ≤12 times per hour to extend service life
- POE oil has strong water absorption, complete vacuum pumping and sealing required after maintenance
- Ensure sufficient condenser heat dissipation under high temperature summer working condition