The IP8000 is a classic SMC mechanical E/P electro-pneumatic positioner (non-smart, sem HART). It is designed for linear-stroke pneumatic diaphragm actuators. It receives a 4~20mA current signal and converts it into supply air pressure to drive válvulas de controle. It replaces the older IP6000 series. The IP8100 in the same series is for rotary-stroke applications. The IP8001/IP8101 are smart versions with auto-tuning and share the same housing.
✅ Principais especificações técnicas
| Item | IP8000 (Tipo de alavanca) |
| Sinal de entrada | DC 4~20mA, Resistência de entrada: 235±15Ω |
| Supply Air Pressure | 0.14~0,7MPa |
| Applicable Stroke | 10~85mm (linear valve stem) |
| Precisão | Sensitivity ≤0.1%FS; Linearity ±1%FS; Hysteresis ≤0.75%FS; Repeatability ±0.5%FS |
| Proteção de entrada | IP65 (CEI60529) |
| Temperatura ambiente | -20~80℃ for standard model; ExdⅡBT5 explosion-proof: -20~60℃ |
| Air Ports | Rc1/4 / G1/4 / 1/4TNP; Gauge port Rc1/8 |
| Conexão Elétrica | G1/2, M20×1,5, 1/2NPT optional |
| Resistência à vibração | No resonance within 5~200Hz |
| Padrão de montagem | Compliant with NAMUR, DIN/IEC 60534-6-1 colchetes |
📌 Definição de código de modelo (IP8000-□□□)
IP8000: Lever-type mechanical electro-pneumatic positioner
- Pressure gauge specification: 0=0.3MPa, 3=1.0MPa
- Construção: Standard housing / ExdⅡBT5 explosion-proof terminal box
- Acessórios: Restrictor pilot valve, yoke linkage, extended feedback lever, etc..
- Thread type, CE marking, special custom codes (por exemplo. X310=IP66)
🛠 Working Principle & Diretrizes de instalação
- Princípio: A 4~20mA current energizes the torque motor. The nozzle-flapper amplifies the signal to control the output air pressure of the pilot valve. The feedback lever captures the actual valve stem position to form a closed loop, ensuring valve position matches the input signal.
- Key Installation Rule: No 50% sinal (12mA), the feedback lever should form a 90° right angle with the valve stem. Select the internal feedback spring according to single-acting or double-acting actuators.
- Ajuste: Mechanical Zero and Span knobs. Supports split range operation. Equipped with manual/auto switching screw for manual air supply during commissioning.
⚠️ Common Troubleshooting
- Valve fails to move
No supply air or insufficient air pressure; 4~20mA wiring reversed; nozzle/restrictor blocked by dust; torque motor damaged.
- Oscillation / Caça
Incorrect feedback lever mounting angle; unstable supply air pressure; stuck pilot valve; excessive friction of valve packing.
- Poor linearity / Deriva zero
Zero/span not calibrated; loose feedback linkage; air piping leakage; large ambient temperature variation.
- Insufficient output pressure
Válvula piloto de bloqueio de matéria estranha; vazamento no diafragma/cilindro do atuador; filtro de ar entupido.
Lembrete de manutenção: Corte o fornecimento de ar e libere totalmente a pressão antes da desmontagem. Limpe o orifício do bico com um fio fino de 0,2 mm. Aplique levemente graxa de silicone TORAY SH45 ao montar os O-rings.
📋 Seleção de modelo & Alternativas
IP8000: Mecânico, alavanca de curso linear. Para válvulas de controle convencionais, baixo custo, sem comunicação.
IP8100: Mecânico, came rotativo, para válvulas borboleta e esfera.
IP8001: Curso linear inteligente. Calibração automática, CERVO, diagnóstico de falhas, substituição de atualização para IP8000.
Alternativas domésticas: Posicionadores E/P domésticos, como Wuzhong e Chuanyi. Verifique o suporte, porta de ar e correspondência de curso.
📎 Cenários típicos de aplicação
Regulação contínua do fluxo, pressão e nível em válvulas de controle de diafragma pneumáticas lineares em produtos químicos, tratamento de água, AVAC, papel, óleo & gasodutos. Versões à prova de explosão ExdⅡBT5 estão disponíveis para áreas perigosas.
SMC IP8000 Electro-Pneumatic Valve Positioner — Application Scenarios
The IP8000 is a linear-stroke mechanical E/P positioner matching diaphragm linear pneumatic control valves. It converts 4~20mA analog signal into air pressure to drive valve stem for continuous process regulation. No HART communication.
🏭 Industry Applications
- Água / Tratamento de Águas Residuais
Inlet flow regulation, pH dosing line, controle de nível de líquido, aeration pressure regulation. Standard non-explosion model is sufficient; IP65 preferred for outdoor installation.
- AVAC & Heating Networks
Temperature control for primary/secondary side of heat exchangers, regulating steam/hot water linear control valves.
- Indústria de papel
Pulp concentration control, white water flow, steam pressure regulation. Dust-prone workshop; air filtration is mandatory to prevent nozzle blockage.
- Indústria química (Use ExdⅡBT5 explosion-proof IP8000 for hazardous zones)
Regulação contínua do fluxo, pressão e nível em tubulações de processo. Carcaça à prova de explosão necessária para áreas perigosas com solventes e hidrocarbonetos leves.
Observação: IP8000 é mecânico sem diagnóstico inteligente. Use IP8001 se HART e ajuste automático forem necessários.
- Comida & Bebida / Farmacêutico (Serviço Sanitário)
Água purificada, lavagem com regulação de água e vapor, emparelhado com válvulas de controle linear sanitárias. Prefira ar de instrumento limpo.
- Poder & Centrais Térmicas
Água de alimentação da caldeira, dessuperaquecimento e redução de pressão, controle de nível de condensado; válvulas auxiliares de controle de processo.
- Óleo & Armazenamento de gás & Transporte (Versão à prova de explosão)
Regulação de pressão e fluxo para dutos de petróleo/produto, controle de nível do tanque. Modelo Exd à prova de explosão para áreas perigosas explosivas.
✅ Tipos de válvula adequados
Ação única / válvulas de controle de diafragma pneumáticas lineares de dupla ação (melhor combinação)
Válvulas guiadas por gaiola, válvulas de assento único, válvulas de controle de gaiola
❗ Válvulas borboleta, válvulas de esfera e outras válvulas rotativas requerem IP8100, IP8000 is not applicable.
📌 Application Characteristics
Tipo de controle: Continuous modulating (not on/off valve). 4~~20mA corresponds to 0~~100% valve travel.
Air source: Limpar, seco, oil-free compressed air. Air filter regulator (AFR) must be installed upstream.
Vantagens: Estrutura simples, fácil manutenção, good anti-EMI performance. Suitable for sites without bus communication requirements and limited budget.
Limitações: Feedback mecânico, no auto-calibration. Manual zero and span adjustment required; no fault diagnosis.
❌ Cenários não recomendados
- Severe oscillation, strong corrosive gas (extra housing protection required).
- Diagnóstico remoto, HART communication, auto-tuning required → upgrade to IP8001.
- Rotary butterfly / ball valves → select IP8100.
- Poeira pesada, unpurified instrument air (high risk of nozzle clogging).
SMC IP8000 — Selection Checklist
Applicable to IP8000 linear mechanical electro-pneumatic positioner; Use IP8100 for rotary applications; IP8001 smart model has separate selection rules.
- Atuador & Valve Basic Information
| Verifique o item | Requisitos de seleção & Observações |
| Tipo de atuador | Linear stroke diaphragm pneumatic actuator (single-acting / dupla ação). Not for rotary butterfly/ball valves. |
| Valve Stem Stroke | 10~85mm; confirm actual stroke. Out-of-range travel invalid; too small stroke degrades feedback lever accuracy. |
| Actuator Action | □ Single-acting (retorno na primavera), replace internal feedback spring inside positioner |
| □ Double-acting (no spring, bidirectional air supply), replace internal feedback spring | |
| Tipo de válvula | Single-seat / cage / cage-guided modulating control valves; modulating service, not on/off valve |
| Stem Diameter & Mount Bracket | DIN/IEC 60534-6-1 / NAMUR standard. Verify feedback linkage and yoke accessories. Excessive stem wobble causes oscillation. |
- Processo & Condições Operacionais
| Verifique o item | Requisitos de seleção & Observações |
| Process Media | Água, vapor, ar, general chemical fluids. Evaluate housing protection for highly corrosive media. |
| Explosion-proof Requirement | □ Standard non-explosion (safe area) |
| □ ExdⅡBT5 explosion-proof (área perigosa, temperature limit: -20~60℃; standard model -20~80℃) | |
| Temperatura ambiente | Padrão: -20℃ ~ +80 ℃; À prova de explosão: -20℃ ~ +60 ℃. Heat insulation required for over-temperature sites. |
| Proteção de gabinete | Padrão IP65; IP66 optional (suffix X310). IP65+ recommended for outdoor, ambientes úmidos e empoeirados. |
| Vibração | No resonance from 5~200Hz. Reinforce linkage under heavy vibration to avoid continuous hunting. |
| Control Requirement | 4~20mA analog continuous modulation; No HART, no auto-tuning. Manual zero/span calibration needed. |
- Air Supply System Check (Highest Failure Source)
| Verifique o item | Requisitos de seleção & Observações |
| Supply Pressure Range | 0.14~0,7MPa. Stable pressure; pressure fluctuation easily triggers valve oscillation. |
| Air Quality | Seco, limpar, oil-free compressed air. Pre-install air filter regulator (AFR) to remove water, oil and dust. Dust environment easily clogs nozzle. |
| Air Port Thread | G1/4 / Rc1/4 / 1/4TNP; gauge port Rc1/8. Confirm thread before ordering. |
- Electrical Check
| Verifique o item | Requisitos de seleção & Observações |
| Sinal de entrada | DC 4~20mA; Resistência de entrada 23515. Match signal source load capacity. |
| Electrical Entry | G1/2 / M20*1.5 / 1/2TNP. Explosion-proof model requires explosion-proof cable gland. |
| Fiação | 2-wire 4-20mA. Polarity matters; reversed polarity causes no operation. Cabo blindado recomendado para longa distância, aterramento de extremidade única. |
- Seleção de Acessórios Auxiliares
□ Manômetro: 0=0.3MPa, 3=1.0MPa (selecione com base na faixa de pressão de saída)
□ Alavanca de feedback, yoke linkage (compatível com o curso do atuador)
□ Regulador do filtro de ar, tubulação de ar
□ Suporte de montagem e fixadores
□ Prensa-cabo à prova de explosão (obrigatório para modelos à prova de explosão)
- Critérios de exclusão (NÃO selecione IP8000 se algum se aplicar)
- Válvula rotativa (borboleta / Válvula de esfera em V) → usar IP8100
- HART communication, diagnóstico remoto, ajuste automático necessário → use IP8001
- Fonte de ar não purificado com poeira pesada, óleo e condensado
- Curso da válvula >85milímetros ou <10milímetros
- Corrosão pesada, vibração de choque forte sem medidas de proteção
- Exemplo de seleção (Referência de código de modelo)
IP8000-3 (1.0Medidor MPa) + à prova de explosão + Porta de ar G1/4 + Entrada elétrica M20
IP8000-301: 1.0Medidor MPa, habitação padrão, conjunto de alavanca padrão
- Inspeção Pré-Instalação
- Tubulação de ar totalmente purgada para remover resíduos e escória de soldagem.
- Alavanca de realimentação perto de 90° em 50% sinal (12mA).
- No leakage on actuator; packing friction shall not be excessive.
- Shielded cable grounding; separate routing from power cables to avoid VFD interference.
SMC IP8000 Electro-Pneumatic Valve Positioner — Maintenance Manual
Applicable to IP8000 mechanical linear E/P positioner; Pre-work safety: Disconnect 4~20mA signal, shut off air supply and vent pressure. Never open housing under pressure.
- Intervalos de manutenção (Diário / Trimestral / Anual)
1) Daily Routine Inspection (per shift / daily visual check)
- Check housing for air leakage, condensação, corrosion and loose fittings.
- Observe two pressure gauges for stable readings; watch for fluctuation/hunting.
- Check valve stem movement: smooth travel, sem aderência ou ruído anormal.
- Drain condensate from air filter regulator in a timely manner.
- Check mounting bracket, feedback linkage and bolts for looseness.
Warning sign: Gauge needle jumping continuously, caça à válvula → inspecione primeiro o mecanismo de feedback ou o bloqueio do bico.
2) Manutenção Trimestral (todo 3 meses)
- Inspecione o elemento filtrante do regulador do filtro de ar; substitua se estiver contaminado.
- Verifique a alavanca de feedback, eixos de garfo e pino: aplique o mínimo de graxa (NÃO lubrifique demais! O excesso de graxa retém poeira e obstrui o bocal).
- Aperte as ferragens: parafusos de montagem do posicionador, acessórios para tubos e blocos terminais.
- Teste funcional: entrada 4mA, 12mA, 20mA, registrar zero e desvio de amplitude.
- Inspecione o cabo e o prensa-cabo; garantir a vedação intacta, sem entrada de água.
3) Revisão Anual (uma vez por ano; todo 6 meses sob condições adversas)
- Desmontar unidade, limpar a carcaça interna, concentre-se no bocal, restritor de válvula flapper e piloto (ponto de falha mais alto).
- Desmonte e inspecione os anéis de vedação; substitua o kit de vedação completo se estiver envelhecido, endurecido ou rachado.
- Inspecione a bobina do motor de torque quanto a descoloração por superaquecimento; verifique a folga entre bocal e flapper.
- Recalibrar zero e span, registrar dados de calibração.
- Inspecione a tubulação de ar; substituir mangueiras envelhecidas.
- Verificação adicional para versão à prova de explosão: superfície da junta de explosão intacta, junta intacta, compatível com lacuna à prova de chamas.
Serviço severo (pó, umidade, águas residuais, papel): reduzir o intervalo de manutenção pela metade.
- Manutenção de componentes principais
✅ Bocal & Melindroso (Fonte de falha mais comum)
- Limpeza: Use fio de nylon/cobre fino de 0,2 mm para limpar suavemente o orifício do bico. Não risque a superfície do bico com fio de aço duro.
- Sopre a poeira com ar comprimido seco em baixa pressão (≤0,2 MPa). Nunca lave o interior do posicionador com líquido.
- Superfície da flapper livre de arranhões e contaminação por óleo. Arranhões causam caça contínua; substituir o conjunto bocal-flapper.
- Exigência: O ar de instrumento deve estar seco e isento de óleo. A película de óleo na aba do bico causa desvio e oscilação.
✅ Conjunto da alavanca de feedback
- Aplique apenas uma pequena quantidade de lubrificante nos eixos dos pinos e nos pivôs; sem graxa pesada.
- Verifique a ligação quanto a deformação; no sticking during stem movement.
- No 50% sinal (12mA), lever should stay near 90°. Readjust mounting if angle deviates largely.
✅ Seals (O-rings)
O-rings age and harden under large temperature fluctuation and continuous operation.
Apply thin layer of TORAY SH45 silicone grease when replacing O-rings, avoid over-application.
Prevent scratches on O-ring grooves during assembly.
✅ Electrical Section
- Inspect 4~20mA 2-wire terminals for oxidation and looseness; single-end grounding for shielded cable.
- Explosion-proof model: power cut before cover removal. Do not damage flameproof mating surface; seal gasket and cable gland must remain sealed.
- Separate signal cables from power cables to avoid VFD interference.
- Long-Term Shutdown Preservation (Out of service >1 mês)
- Shut off air supply and vent pressure; disconnect 4-20mA signal.
- Set valve to mid-position (50% abertura) to reduce long-term single-side spring stress.
- Drain condensate from air filter.
- Cover housing for dust protection to avoid dust accumulation on nozzle-flapper.
- Purge air piping and re-calibrate zero & span before recommissioning.
- Operações Proibidas (Avisos importantes)
❌ Open positioner housing under pressure or powered condition
❌ Blast nozzle-flapper assembly with high-pressure compressed air
❌ Apply large amount of grease (traps dust and clogs nozzle)
❌ Flush internal parts with liquid (only wipe housing exterior with damp cloth)
❌ Force feedback lever; may deform torque motor and cam
❌ Use instrument air with oil, water and heavy contaminants
- Post-Maintenance Verification Procedure
Follow sequence after maintenance:
- Apply air supply, verify all air joints leak-free.
- Connect 4~20mA signal generator.
- 4mA → zero calibration; 20mA → span calibration; repeat 2~3 cycles.
- Test linearity at midpoint 12mA; confirm no oscillation or lag.
- Record calibration data and file maintenance log.
- Quick Fault Reference During Maintenance
- Valve hunting / small cycling: Dirty nozzle/flapper; wrong feedback lever angle; unstable supply air.
- Deriva zero: Condensate in air; minor O-ring leakage; slight nozzle clogging.
- Insufficient output pressure: Stuck pilot valve; filtro de ar entupido.
- Large hysteresis: Pivot sticking and high friction; excessive packing friction of actuator.