Relé de estado sólido OMRON G3PA-240B-VD

The Omron G3PA series single-phase solid state relay (RSS) with integrated heat sink, zero-crossing turn-on, Montagem em trilho DIN, directly driven by PLC DC signals. Widely used for non-contact switching control of heating elements, fans and lamp loads. Nota importante: Este modelo foi descontinuado. Only stock units are available or alternative models should be selected. Modelo ...

  • Detalhes do produto

O Omron G3PA series single-phase solid state relay (RSS) with integrated heat sink, zero-crossing turn-on, Montagem em trilho DIN, directly driven by CLP DC signals. Widely used for non-contact switching control of heating elements, fans and lamp loads.

Nota importante: Este modelo foi descontinuado. Only stock units are available or alternative models should be selected.

  1. Definição de código de modelo

G3PA: Nome da série, solid state relay with integrated heat sink

2: Monofásico, AC24~240V output specification

40: Rated load current 40A

B: Built-in heat sink

VD: DC5~24V DC input control, opto-triac isolation, zero-crossing turn-on

  1. Especificações elétricas principais

✅ Input Side (Control Terminals +A1, -A2)

Tensão de controle: DC5~24V, operating range DC4~30V

Maximum input current: 7mA (directly drivable by PLC output point)

Operating voltage ≤DC4V; Reset voltage ≥DC1V

Isolamento: Opto-triac isolation

✅ Output Side (Load Terminals 1, 2)

Rated load voltage: AC24~240V, operating range AC19~264V (50/60Hz)

Rated load current: 40A @40℃; derate to 36A for dense side-by-side mounting

Surge withstand current: 440UM (60Hz, 1 ciclo)

Eu não: 1260 A²s

On-state voltage drop: ≤1.6V RMS

Switching characteristic: Zero-cross turn-on, reduces switching surge

Operate / release time: Within half cycle of load power supply +1ms

✅ Environmental & Mecânico

Temperatura operacional: -30℃ ~ +80 ℃ (sem condensação)

Montagem: Montagem em trilho DIN ou parafuso; screw type terminals

Dimensões: W47 × H100 × D100 mm

Dielectric strength between input and output: AC4000V

  1. Cenários típicos de aplicação

Controle de temperatura: Heating tubes, ceramic heaters, infrared heating (mais comum)

Iluminação: High power lamp banks, halogen lamps

Motores: Small single-phase fans (resistivo / weakly inductive load preferred)

Observação: Inductive loads and loads with large starting inrush current require additional varistor and RC snubber protection.

  1. Diretrizes de fiação
  2. +A1, -A2: DC control signal, good polarity tolerance. It is recommended to connect PLC positive output to A1.
  3. Terminais 1, 2: Connected in series to AC load circuit, L/N non-polarity.
  4. Circuito amortecedor RC + varistor connected in parallel at output terminals for inductive loads.
  5. Derate current and reserve heat dissipation clearance when multiple SSRs are installed side by side on DIN rail.
  6. Replacement Models for Discontinued Product
  7. Upward replacement within same series: CEO do G3PA-260B (60UM, DC5~24V input). Same pin layout with higher capacity.
  8. New generation alternative: G3PE series G3PE-245B, 45A DC control, Montagem em trilho DIN, substituição direta.
  9. Domestic compatible SSR: 40A solid state relay, DC5-24V input, AC240V, zero-cross type with integrated heat sink.
  10. Solução de problemas comuns
  11. Input LED does not light: Check PLC output voltage and broken wiring; insufficient input current to drive SSR.
  12. LED lights but load does not turn on: Terminais de saída soltos, broken load; internal triac damage.
  13. Load remains energized after control signal removed: SSR short-circuit failure (common for heating loads), usually caused by overheating or surge breakdown.
  14. Acionamento falso frequente: Control cable runs in parallel with power cable causing interference; connect 1000pF anti-interference capacitor at input side.
  15. Notas de seleção
  16. Cargas resistivas: Derate to 0.7 times rated current for selection.
  17. Heating loads have low cold resistance with large starting inrush current, é necessária margem atual suficiente.
  18. Further derate when ambient temperature >40℃ or densely mounted.
  19. Solid state relay has no mechanical contacts, cannot serve as safety disconnect switch. Circuit breaker must be fitted on main circuit.

OMRON G3PA-240B-VD (40A DC to AC Zero-cross SSR) Casos de aplicação típicos

Product Recap: Integrated heat sink, Montagem em trilho DIN, DC5~24V input, AC24~240V 40A, zero-cross turn-on. Directly driven by PLC, mainly suitable for resistive loads. RC+MOV snubber required for inductive loads.

Caso 1: Temperature Control System – Industrial Heating Tube Control (Mais populares)

Aplicativo

Fornos, hot presses, plastic dryers, mold temperature machines, food baking lines, single-phase 220V heating tubes, max power ~8kW (220V×40A), Regulação de potência PID por PLC + controlador de temperatura.

Configuração do sistema

  1. Controlar: Saída transistorizada DC24V do controlador de temperatura / PLC conectado a A1/A2 do G3PA; comutação zero-cross reduz a distorção harmônica da rede.
  2. Circuito principal: AC220L → terminal SSR 1; terminal 2 → tubo de aquecimento → N.
  3. Proteção: 3Disjuntor P + fusível rápido a montante; a proteção contra superaquecimento do termopar é recomendada para tubos de aquecimento.
  4. Esnobador: RC opcional para cargas resistivas; 470O varistor V é recomendado para aplicações de alta potência para absorver oscilações da rede.

Recomendação de desclassificação

Operação contínua de longo prazo: Corrente de carga controlada dentro de 28A (0.7×classificação); reduzir para 24A para instalação de várias unidades lado a lado.

Vantagens

Operação sem contato, sem erosão de contato mesmo sob comutação frequente (várias vezes por segundo), maior precisão de controle de temperatura PID.

Armadilha Comum

Os tubos de aquecimento têm grande corrente de irrupção no estado frio. Continuous full-current operation tends to break down SSR; do not treat rated 40A as continuous operating current.

Caso 2: High Power Halogen / Infrared Lamp Bank Control

Aplicativo

UV curing lamps, lâmpadas de aquecimento infravermelhas, industrial inspection light sources, infrared radiation panels for drying lines, 220V AC lamp banks.

Configuração do sistema

PLC DC24V output drives SSR; lamp load connected in parallel to SSR output terminals.

Halogen lamp has extremely low cold resistance, inrush current at switch-on can reach 8~10 times rated current.

Precauções

  1. Zero-cross G3PA is well suited for lamp loads, turn-on at voltage zero point to reduce inrush.
  2. Heavy derating is mandatory: lamp load at 0.4~0.5 times SSR rating; load ≤20A for this 40A SSR.
  3. NTC surge limiting thermistor in series is recommended.

Vantagens

Silent switching, no electric arc under frequent on/off, suitable for automated production line light sources.

Caso 3: Fãs / Small Single-phase Motors (Carga Indutiva)

Aplicativo

Air duct heating matched fans, cabinet high-power cooling fans, small conveying single-phase fans for continuous start-stop control.

This is inductive load, Amortecedor RC + MOV varistor must be installed (100Ω/2W +0.1μF/400VAC +470V varistor).

Sistema

PLC controls SSR to start/stop fan; circuit breaker fitted upstream of SSR.

Limitação

Not suitable for frequent forward/reverse rotation of motor; not applicable for high-power motors with huge starting surge.

Back EMF generated at motor power-off can easily damage SSR, RC snubber is essential.

Caso 4: Solenoid Valve Bank, AC Contactor Coil Drive (Small Inductive Load)

Aplicativo

Equipamento de embalagem, pneumatic production lines, multiple parallel AC220V solenoid coils controlled centrally by PLC.

Configuração do sistema

SSR output drives multiple parallel AC220V solenoid coils; RC+MOV conectado em paralelo aos terminais SSR.

Notas

Bobina solenóide é indutância, gera pico de alta tensão no desligamento; a corrente de carga total não pode exceder 40A.

Pequena vibração do solenóide após o desligamento do SSR pode ocorrer devido à corrente de fuga RC. Solução: conecte o resistor de sangria de 10kΩ/5W nos terminais de carga.

Caso 5: 220Rolos motorizados V AC para linhas transportadoras / Equipamento de transporte pequeno

Aplicativo

Linhas de classificação logística, linhas transportadoras de embalagens, controle start-stop de rolos motorizados monofásicos 220V.

Pontos-chave

Amortecedor RC+MOV obrigatório para carga indutiva do motor; não é adequado para jogging frequente com forte impacto, aplicável para operação de longo prazo com partida-parada de longo intervalo.

Caso 6: Circuito de aquecimento de câmara de teste ambiental

Aplicativo

Temperatura constante & câmara de umidade, câmara de teste de envelhecimento, circuito de aquecimento resistivo com regulação contínua de potência PID.

Configuração do sistema

Saída PID DC24V do controlador de temperatura aciona G3PA; multi-section heating zone control with multiple G3PA mounted side by side on DIN rail.

Notas principais

Derate current and reserve heat dissipation clearance for side-by-side installation; ambient temperature around SSR must not exceed 60℃.

Load Selection Summary Table

Tipo de cargaRecommended DeratingRC+MOVObservações
Resistive heating tube0.7×classificaçãoOpcional (MOV recommended)Most compatible, amplamente utilizado
Halogen / Infrared lamp0.4~0.5×ratingRecomendadoExtreme cold inrush current
Single-phase fan, small motor (indutivo)0.6×classificaçãoObrigatórioHigh risk of back EMF breakdown at turn-off
AC220V solenoid coil0.6×classificaçãoObrigatórioLeakage current may cause minor false actuation

General Usage Prohibitions for G3PA-240B-VD

  1. ❌ Not for large air compressors, high-power single-phase motors (excessive starting surge)
  2. ❌ Cannot act as safety disconnect switch, independent circuit breaker required for main circuit
  3. ❌ Not suitable for high-frequency high-voltage inductive loads; risco de falha de curto-circuito triac (SSR travado LIGADO, carga continuamente alimentada, risco de incêndio por excesso de temperatura em sistemas de controle de temperatura)
  4. ❌ É necessária uma redução adicional de corrente quando a temperatura ambiente é superior a 60 ℃

Lista de falhas do G3PA-240B-VD por cenário de aplicação

Modelo: Omron G3PA-240B-VD, 40Um SSR cruzado zero de entrada CC; principais modos de falha: curto-circuito permanente na saída (mais perigoso), falha ao ligar, falso disparo intermitente.

Precaução: Se o SSR falhar em curto, carga permanece energizada continuamente. O risco de incêndio por temperatura excessiva é alto para sistemas de aquecimento. A proteção independente contra superaquecimento deve ser instalada no circuito principal.

Caso 1: Tubo de aquecimento / Forno, Máquina de temperatura de molde (Carga resistiva, Mais Comum)

Falha1: SSR entra em curto-circuito após operar por um período, o aquecimento nunca para

Sintoma: Sinal de controle PLC removido, nenhuma entrada em A1/A2, tubo de aquecimento permanece aquecido; Habitação SSR muito quente.

Causa raiz:

1) Long-time full current operation without 0.7 desclassificação; insufficient heat dissipation with side-by-side mounting.

2) Aging heating tube with partial short circuit, surge current breaks triac.

3) Grid voltage spike without varistor protection.

Remédio: Control load current ≤28A; install 470V varistor; periodically test insulation of heating tube; add independent over-temperature thermostat for hard cut-off.

Fault2: Large temperature fluctuation under PID control, intermittent heating

Sintoma: Temperature controller output normal, heating cuts in and out randomly.

Causa raiz:

1) Insufficient output current from PLC, voltage drop on cable.

2) Loose SSR terminals, contact resistance generates heat.

3) Oxidized wiring of heating tube, mau contato.

Remédio: Aperte os terminais (torque 0.8~1.0N·m); check driving capacity of PLC transistor output; replace aged heating tube.

Falha3: SSR indicator LED on, but no heating

Causa raiz: Broken output circuit, burnt heating tube; open-circuit damage of internal triac.

Remédio: Measure resistance of heating tube after power-off; measure AC voltage across SSR output terminals.

Caso 2: Halogen / Infrared Lamp Bank

Falha1: SSR damaged immediately upon lamp switch-on

Sintoma: SSR burns out right after lamp activation even if average current is low.

Causa raiz: Extremely low cold resistance of halogen lamp, inrush current reaches 8~10 times rated; zero-cross turn-on still cannot eliminate huge surge without derating.

Remédio: Limit load current to 0.4~0.5×SSR rating; fit NTC surge suppression thermistor in lamp circuit; prefer lamp-specific SSR.

Fault2: Lamp flickering

Causa raiz: Fluctuating supply voltage; lamp aging; internal component aging of SSR.

Remédio: Replace aged lamps; verify power supply stability.

Caso 3: Single-phase Fan, Small Motor (Carga Indutiva)

Falha1: SSR breaks down every time fan stops

Sintoma: Fan runs normally, SSR fails when control signal turns off.

Causa raiz: A indutância do enrolamento do motor gera alta EMF traseira no desligamento; RC+MOV não instalado.

Remédio: Instale o amortecedor RC (100Ω/2W +0,1μF/400VAC em série) +470Varistor V, fio diretamente próximo aos terminais SSR.

Fault2: O ventilador gira lentamente após o SSR ser desligado

Sintoma: O ventilador não para completamente após a remoção do sinal PLC, rotação em baixa velocidade.

Causa raiz: Corrente de fuga introduzida pelo amortecedor RC, tensão fraca induzida no enrolamento do motor.

Remédio: Instale um resistor de sangria de 10kΩ/5W nos terminais do motor; ou use contator mecânico para corte completo.

Caso 4: Banco de bobina solenóide AC220V (Carga Indutiva)

Falha1: Solenóide puxa aleatoriamente (falso acionamento)

Sintoma: O solenóide ocasionalmente vibra ou atua sem sinal de saída do PLC.

Causa raiz: Corrente de fuga RC; interferência eletromagnética quando o cabo de controle passa paralelo ao cabo de alimentação; fio de controle excessivamente longo.

Remédio: Instale um resistor de sangria de 10kΩ/5W nos terminais de carga; roteamento separado para cabos de controle e alimentação; ajuste o capacitor anti-interferência de 1000pF no lado de entrada.

Fault2: SSR danificado após vários ciclos de comutação

Causa raiz: Pico de alta tensão devido ao desligamento da bobina sem proteção RC+MOV.

Remédio: Instale RC+MOV; não conecte solenóides excessivos em paralelo, reduzir a corrente total para 0,6×classificação.

Caso 5: Rolo Motorizado Transportador

Falha1: Partida/parada instável do rolo, falha ocasional na inicialização

Sintoma: Às vezes, o rolo não inicia mesmo quando o sinal de controle é enviado ao SSR.

Causa raiz: Grande surto de partida do motor; margem SSR insuficiente; voltage drop on cable.

Remédio: Reduza a capacidade de carga; verifique a bitola do cabo de alimentação; RC+MOV obrigatório para carga indutiva.

Fault2: Superaquecimento severo do SSR

Causa raiz: Operação de corrente pesada de longa data; fraca dissipação de calor para múltiplos SSR montados lado a lado em trilho DIN.

Remédio: Aumente a folga de montagem entre as unidades SSR; reduzir a corrente de carga; adicione ventilador de resfriamento auxiliar, se necessário.

Falhas comuns gerais (Aplicável a todos os cenários)

  1. O LED indicador de entrada em A1/A2 não acende

Sequência de solução de problemas:

1) Verifique a saída do PLC, confirme a presença de DC24V.

2) Fio de controle quebrado, polaridade invertida (tolerado até certo ponto, polaridade reversa de longo prazo danifica o LED de entrada).

3) Circuito de entrada queimado do SSR.

  1. LED de entrada normal, nenhuma ação de saída

Solução de problemas: Fonte de alimentação principal disponível; terminais de saída soltos; open-circuit damage of internal triac.

  1. Falha aleatória de SSR sob alta temperatura ambiente

Causa raiz: Temperatura ambiente> 60 ℃, a dissipação de calor se deteriora, desvio característico do dispositivo.

Remédio: Melhorar a ventilação do gabinete; desclassificar ainda mais a corrente; monte o SSR longe de componentes geradores de calor.

  1. Atuação falsa aleatória do SSR causada por interferência

Sintoma: SSR liga/desliga irregularmente durante a operação do equipamento.

Contramedidas:

1) Calhas de cabos separadas para sinal de controle e cabo de alimentação, evite roteamento paralelo longo.

2) Instale o relé de isolamento no lado da saída do PLC.

3) Conecte o capacitor cerâmico de alta tensão 1000pF no lado da entrada.

Procedimento de diagnóstico rápido de falhas (Para comissionamento no local)

  1. Desconecte a alimentação principal CA, mantenha a alimentação de controle DC24V ligada, verifique se o LED de entrada SSR segue o sinal do PLC.
  2. Desligar, medir a resistência nos terminais de saída SSR:

Estado normal (sem sinal de entrada): Alta resistência, Nível megaohm.

Resistência próxima ao estado condutor sem entrada: SSR em curto-circuito, NÃO energize!

  1. Ligar com carga, measure AC voltage across SSR output terminals:

Com sinal LIGADO: Queda de tensão no SSR ≤1,6V.

Com sinal desligado: Tensão através do SSR perto de AC220V.

  1. Verifique a temperatura do invólucro SSR; melhorar a redução ou dissipação de calor se a temperatura exceder 70 ℃.

Regras de segurança

  1. A falha de curto-circuito é o modo de falha típico deste SSR. A proteção mecânica independente contra superaquecimento deve ser instalada para aplicações de aquecimento; não confie apenas em PLC e SSR.
  2. Não execute testes de longo prazo sem RC+MOV para qualquer carga indutiva.
  3. SSR não deve ser usado como chave de isolamento de segurança; o disjuntor principal deve ser aberto para manutenção do equipamento.