Contactor AC ABB AX50-30-00-80

Model Code Breakdown AX50-30-00-80 AX50: AX series general-purpose AC contactor, Dimensiunea cadrului 50 30: 3-pol, 3 main Normally Open contacts (3NU), no main Normally Closed contacts 00: Fără contacte auxiliare încorporate (0NO+0NC). Auxiliary contacts must be fitted externally with CAL5X auxiliary contact blocks. 80: Coil Code ✅ Coil Voltage: AC 220~230V 50Hz / 230~240V 60Hz ...

  • Detalii despre produs

Defalcarea codului de model

AX50-30-00-80

  1. AX50: AX series general-purpose contactor AC, Dimensiunea cadrului 50
  2. 30: 3-pol, 3 main Normally Open contacts (3NU), no main Normally Closed contacts
  3. 00: Fără contacte auxiliare încorporate (0NO+0NC). Auxiliary contacts must be fitted externally with CAL5X auxiliary contact blocks.
  4. 80: Coil Code

✅ Coil Voltage: AC 220~230V 50Hz / 230~240V 60Hz (Bobina AC)

Model de comandă completă: AX50-30-00-80220-230V50Hz/230-240V60Hz

ABB Cod de comandă: 10139897

  1. Parametrii electrici de bază
ArticolCaietul de sarcini
Polii principali3P (3 Normally Open Main Contacts)
Rated Operational Current AC-3 (400V, Sarcina motorului)50 O
Matched 3-phase Motor Power @400V (AC-3)22 kW
AC-1 Resistive Load (40℃)100 O
Tensiune nominală de izolație Ui690 V
Conventional Thermal Current Ith100 O
Control CoilAC220~230V 50Hz / 230~240V 60Hz
Rezistenta mecanica≥10,000,000 operations
Rezistenta electrica (AC-3)≥1.000.000 de operații
Max Operating Frequency600 operațiuni/oră (Sarcina AC-3)
Clasa de protectieIP20 (Terminale)
Temperatura ambiantă-40℃ ~ +70℃
Metoda de montareDIN35 Rail Mount / Screw Panel Mount
  1. Outline & Dimensiuni

Width × Depth × Height: 82 mm × 110 mm × 108 mm

Greutate netă: Aproximativ. 1.05 kg

Terminal Markings:

Circuitul principal: 1L1, 3L2, 5L3 (Line Side); 2T1, 4T2, 6T3 (Load Side)

Terminale bobine: A1, A2 (bobina AC, non-polarized)

  1. Caracteristici cheie
  2. Fără contacte auxiliare încorporate. External auxiliary contact modules CAL5X-11 (1NU+1NC), CAL5X-20, CAL5X-02 must be installed separately.
  3. Direct pluggable with ABB TA series thermal overload relays to form a complete motor starter.
  4. Compatible accessories: Suprimatoare de supratensiune (RC networks, varistoare), interblocări mecanice, side-mounted auxiliary contacts.
  5. Drop-in replacement for legacy A50-30-00; AX series accessories are NOT interchangeable with older A series.
  6. Same Series Selection Reference

AX50-30-00-80: Fără contacte auxiliare încorporate (Subject Model)

AX50-30-11-80: Built-in 1NO+1NC auxiliary contacts (Cod de comandă:10139700)

  1. Compatible Replacement Options

Direct OEM Replacement

No newer superseding model; AX50 remains in mass production.

Cross-brand Equivalent Alternatives

Schneider LC1D50M7C (50O, AC220V coil)

Siemens 3RT2036-1AK60

⚠️ Replacement Checkpoints: Dimensiuni de montaj, tensiunea bobinei, auxiliary contact configuration, plug compatibility with thermal relays.

  1. Aplicații tipice

Start/stop control of 3-phase motors for air compressors, pompe de apa, fani, transportoare, mașini de turnat prin injecție, HVAC equipment; switching of resistive loads such as heaters and lighting circuits.

Complete Technical Document for ABB AX50-30-00-80 AC Contactor

Informații de bază despre produs

Model complet: AX50-30-00-80

Full Description: AX50-30-00-80 220–230V 50Hz / 230–240V 60Hz

Cod de comandă ABB: 10139897

ABB Product Code: 1SBL351074R8000

Customs HS Code: 85364900

Serie: AX series 3-pole AC operated contactor (Replaces legacy A50-30-00)

Origine: Tianjin, China

Certificari: CCC, CE, RoHS, Conform IEC 60947

  1. Defalcarea codului de model
Segment de codDescriere
AX50Seria AX, Dimensiunea cadrului 50
303-pol, 3 În mod normal Deschideți contactele principale (3NU), no main NC contacts
0Fără contacte auxiliare încorporate (0NO+0NC). Auxiliary contacts require external CAL5X accessories.
80Coil Code: AC220~230V 50Hz / AC230~240V 60Hz

⚠️ Distinction: AX50-30-11-80 is equipped with integrated 1NO+1NC auxiliary contacts. AX50-30-00-80 has no on-board auxiliary contacts.

  1. Rated Electrical Parameters (IEC 60947-4-1)

2.1 Parametrii circuitului principal

Element de parametruValoare
Conventional Thermal Current Ith (40℃)100 O
Tensiune nominală de izolație Ui690 V și
Rated Operational Current AC-3 (Sarcina motorului, 400V)50 O
Matched 3-phase Motor Power @400V (AC-3)22 kW
Matched 3-phase Motor Power @500V (AC-3)30 kW
AC-1 Resistive Load (40℃)100 O
Max Making Current (AC-3)500 O
Max Breaking Current (AC-3)400 O

2.2 Control Coil Parameters

Tensiunea bobinei: AC 220~230V(50Hz) / 230~240V(60Hz)

Tensiune de preluare: ≤85% Ue

Tensiune de întrerupere: 10% ~ 60% Ue

Consumul de energie al bobinei: Pick-up ≈70 VA; Holding ≈8 VA

Terminale bobine: A1, A2 (Non-polarized for AC)

2.3 Durată de viaţă & Specificații de funcționare

Rezistenta mecanica: ≥10,000,000 operations

Rezistenta electrica (AC-3, 400V, 50O): ≥1.000.000 de operații

Max Operating Frequency: 600 operațiuni/oră (AC-3 load)

  1. de mediu & Specificații de montaj
ArticolSpecificatii tehnice
Temperatura ambiantă de funcționare-40 ℃ ~ +70 ℃
Temperatura de depozitare-50 ℃ ~ +80 ℃
Permissible Altitude≤3000m; Derating necesar peste 2000 m
Clasa de protectieIP20 for main circuit terminals; IP20 for coil terminals
Metoda de montareDIN35mm Rail Mount / M4 Screw Panel Mounting
Allowable Mounting Inclination±30°; Vertical installation recommended
Rezistenta la vibratii (IEC60068-2-6)5~150Hz, Amplitude 1mm
  1. Outline Dimensions & Greutate

Width × Depth × Height: 82 mm × 110 mm × 108 mm

Greutate netă: 1.05 kg

Definiția terminalului

Main Circuit Line Side: 1L1, 3L2, 5L3

Main Circuit Load Side: 2T1, 4T2, 6T3

Circuit de control: A1, A2

  1. Accesorii optionale (Separate Order Required)

No built-in auxiliary contacts on unit; external accessories required for status feedback

  1. CAL5X-11: Side-mounted auxiliary contact block, 1NU+1NC (Most commonly used)
  2. CAL5X-20: 2 Deschis normal; CAL5X-02: 2 În mod normal închis
  3. TA Series Thermal Overload Relays: TA42DU…TA75DU, direct plug-in to build motor starters
  4. RC Surge Suppressor / Varistor: Connect across A1/A2 to suppress coil overvoltage
  5. Modul de blocare mecanică: For forward/reversing contactor interlocking
  6. Capac de protecție a terminalelor

⚠️ Important Notice: AX series accessories cannot be interchanged with legacy A series (A50).

  1. Standard Wiring Description
  2. Basic Motor Start-Stop Circuit

3-phase Power → 1L1/3L2/5L3; 2T1/4T2/6T3 → 3-phase Motor

Circuit de control: Power → Start/Stop Pushbuttons → A1, A2

  1. For running status feedback: Install CAL5X-11, use 13/14 NO contact for signal feedback
  2. Surge suppression components for coil must be wired in parallel across A1 and A2, never in series.
  3. Official Document Download Sources
  4. ABB Global Product Page (Download Datasheet, 2D Drawing, 3D CAD)

https://new.abb.com/products/1SBL351074R8000/ax50-30-00-80

  1. ABB Library library.abb.com

Search Document ID: 9AKK107492A7059 (AX Series General Manual)

  1. ABB China Online Store: Search Order Code 10139897 at mall.abb.com.cn
  2. Selecţie & Ghid de înlocuire

OEM Upgrade

No superseding model; AX50 is currently in continuous production. Discontinued legacy A50-30-00 can be directly replaced by this model.

Cross-brand Equivalent Alternatives

Schneider LC1D50M7C

Siemens 3RT2036-1AK60

Replacement Verification Points: Tensiunea bobinei, dimensiuni de montaj, plug compatibility with thermal overload relays, auxiliary contact configuration.

  1. Precauții de aplicare & Evitarea capcanelor
  2. 00 designation means no built-in auxiliary contacts. Do not assume integrated 1NO+1NC contacts.
  3. Derate load current if ambient temperature >55℃ or installation altitude >2000m.
  4. Pentru sarcini inductive (motoare), coil surge suppression is recommended to avoid PLC electromagnetic interference.
  5. Not designed for direct switching of high-voltage DC; operate only within specified AC load categories.
  6. CAL5X auxiliary blocks can only be fitted on the left and right sides of contactors; top mounting is prohibited.