3RT1064-6AP36
- 3RT: SIRIUS Electromagnetic Contactor Serie
- 1: Classic imported SIRIUS 3RT1 Series (Echivalentul intern: 3RT5/3RT6)
- 0: 3-pole contactor for motor loads (3FĂRĂ contacte principale)
- 64: Frame Size S10, AC-3 rated current 225 O
- 6: Conventional electromagnetic operating mechanism (non-electronic coil)
- O: Coil voltage code → AC/DC 220~240 V (Bobina universală AC/DC)
- P: Main circuit busbar connection
- 36: Permanently built-in auxiliary contacts 2NO + 2NC
Full Description: 3-pole power contactor, Frame S10, busbar terminals, 220~240 V AC/DC coil, fix 2 Deschis normal + 2 Contacte auxiliare normal închise.
- Main Electrical Specifications
| Articol | Parametru |
| Configurarea contactului principal | 3P Normally Open (3NU) |
| Rated operational current AC-3 / AC-3e @400 V | 225 O |
| Rated motor power (3-fază, 400 V) | 110 kW |
| Rated operational current AC-4 @400 V | 195 O |
| Control coil voltage | UC = 220~240 V AC/DC (Universal AC & DC) |
| Coil operating range | 0.7~1.25 × rated voltage |
| Standard auxiliary contacts | 2NU + 2NC (Încorporat, nedemontabil) |
| Dimensiunea cadrului | S10 |
| Conexiunea circuitului principal | Busbar connection (fixare cu șuruburi) |
| Auxiliar & coil connection | Borne cu șuruburi |
| Tensiunea nominală de izolație | 1000 V |
| Gradul de poluare | 3 |
Cable Connection Capacity
Circuitul principal: Stranded cable 70~240 mm²
Circuit auxiliar: 0.5~4 mm²
- Outline & Installation Information
Metoda de montare: Base plate screw mounting (DIN rail mounting NOT supported; large S10 frame can only be fixed to cabinet base plate)
Front protection class: IP00
Ambient operating temperature: -25℃ ~ +60℃ (full-load operation at 60℃)
- Scenarii tipice de aplicare
Direct-on-line starting of 3-phase induction motors, main contactor for star-delta starters, Bypass VFD
Compresoare de aer, pompe de apa, fani, mașini de turnat prin injecție, high-power production line drives
HVAC, centrala electrica, metalurgie, port crane power circuits
⚠️ Not recommended for long-term inching operation under AC-4 duty; select higher frame size for frequent start-stop applications.
- Alternative Selection Reference
1) Direct OEM replacement (Siemens original)
3RT1064-6AP36 (Modelul subiectului, 220~240 V AC/DC coil)
Coil voltage variants:
3RT1064-6AP36 = 220~240 V AC/DC
3RT1064-6BP36 = 110~127 V AC/DC
2) Alternativă actualizată
3RT1065-6AP36: Frame S10, AC-3 265 O (Higher capacity, dimensiuni de montaj identice)
⚠️ Important distinction: 3RT12xx series are vacuum contactors with different construction; not directly interchangeable.
Domestic economical model: 3RT5064 (AC-only coil, different terminal structure; cannot directly replace imported busbar-type 3RT1064).
- Selection Pitfall Reminders
- Main circuit adopts busbar connection, not cable terminals; terminal adapter accessories are required if cable wiring is needed.
- S10 frame without DIN rail base, only base plate mounting available.
- Bobina universală AC/DC; compatible with both AC230 V control and DC220 V control circuits.
- Auxiliary contacts 2NO+2NC are permanently built-in, cannot be removed or reconfigured freely.
- Standard ordering designation with hyphen: 3RT1064-6AP36, do not omit the hyphen.
- Optional Compatible Accessories
3RU thermal overload relays (S10 frame rating)
Suprimatoare de supratensiune (RC network, varistor for coil protection)
Mechanical interlock kits (for forward/reversing contactor pairs)
Main circuit terminal adapters (cable-to-busbar transition)
Mounting Dimensions – Siemens 3RT1064-6AP36 (Frame S10)
Important Precondition: DIN rail mounting is not supported; only base plate bolt mounting
- Overall Outer Dimensions (L × H × D, mm)
Latime W: 145 mm
Height H: 210 mm
Depth D: 202 mm (cabinet internal depth occupation)
- Base Plate Mounting Hole Dimensions (Critical for cabinet sheet metal processing)
4 fixing through holes, bolt specification: M8
- Horizontal center distance (left-right): 124 mm
- Vertical center distance (up-down): 186 mm
- Diametrul orificiului de montare: Φ9 mm (for M8 bolts)
Bounding outline of mounting hole centers: 124 mm (W) × 186 mm (H)
- Wiring Clearance for Main Circuit Busbar
Main terminals exposed on top and bottom for busbar installation:
Phase spacing: 50 mm
Terminal bolt: M12
Recommended maximum busbar thickness ≤12 mm
- Minimum Cabinet Installation Clearance (Siemens official heat dissipation specification)
Top clearance above contactor: ≥10 mm
Bottom clearance below contactor: ≥10 mm
Left & right side clearance: ≥10 mm
Front clearance (towards arc shield): ≥20 mm
Insufficient clearance causes temperature rise and derated operation.
- Greutate
Net weight of unit: aproximativ. 7.8 kg
- Supplementary Installation Notes
- 3RT1064-6AP36 = busbar connection version. Cable-terminated models of the same frame share identical overall dimensions, only terminal structure differs.
- 3RT1065 (265 O) of the same series uses S10 frame; mounting dimensions are fully interchangeable, base plate hole layout can be reused.
- Minimum center-to-center distance between two side-by-side contactors with mechanical interlock for forward/reversing circuit: 150 mm.
- For continuous full-load operation above 40℃ ambient temperature, expand surrounding heat dissipation clearance to minimum 15 mm.
Service Life Parameters – Siemens 3RT1064-6AP36 (Frame S10)
- Durată de viață mecanică (Typical value from official datasheet)
Rezistenta mecanica: 10,000,000 cicluri de operare (10 de milioane de ori)
Definiţie: No-load open/close cycles without main circuit load. Built-in standard mechanical auxiliary contacts (2NU+2NC) do not reduce mechanical life.
⚠️ Distinction:
If electronic auxiliary modules are fitted → mechanical endurance reduced to 5,000,000 cicluri.
Standard built-in 2NO+2NC mechanical auxiliary contacts of this model are not subject to this limitation.
- Durată de viață electrică (Contacte principale, key reference for selection)
Duty condition: AC-3, 400 V, normal motor start-stop (breaking 6×Ie starting current)
Electrical endurance ≈ 200,000 cicluri (200,000 ori)
AC-4 inching duty (rotor blocat, frequent reversing): Electrical life drops significantly, typically limited to tens of thousands of cycles. Select higher-rated contactor or dedicated AC-4 contactor for frequent jogging applications.
- Key Supplementary Notes
- Mechanical life ≠ Electrical life
Mechanical endurance reflects durability of magnetic core, springs and transmission mechanism; electrical endurance is limited by contact arc erosion. In most operating conditions, electrical service life expires first.
- Environmental Influences
Temperatură ridicată, praf, umiditate, coil voltage deviation and vibration will shorten both mechanical and electrical service life.
- Maximum Permissible Operating Frequency
Standard duty: ≤1200 cycles/hour. Exceeding this frequency requires current derating, resulting in aggravated temperature rise and accelerated service life reduction.
- Interchangeability within Frame
All S10 frame contactors including 3RT1064 / 3RT1065 share uniform mechanical endurance of 10 milioane de cicluri, applicable for reference.