Basic Model Definition
Număr de catalog: 440R-N23114
Internal Model Code: MSR126.1T
Marca: Allen-Bradley (Rockwell Automation), Guardmaster Minotaur Series
Ciclu de viață: Active production model, manufactured in Czech Republic, standard 1-year warranty
- Specificații electrice de bază
2.1 Alimentare electrică
Tensiune nominală: 24V AC/DC, domeniul de operare: 0.85~1.1× rated voltage (20.4~26,4V)
Consumul de energie: 4W, compatible with 50/60Hz
Terminals A1/A2: Putere de intrare
2.2 Safety Inputs (Dual-channel 4-wire with cross short-circuit detection)
2 în mod normal închis (NC) safety input paths (S11-S12 / S21-S22)
Supports dual-channel emergency stop, safety door switches and safety light curtains; built-in cross-channel short-circuit fault diagnosis
Maximum input loop resistance: ≤90Ω
2.3 Reset Circuit (S33-S34)
MSR126.1T supports automatic reset and manual reset dual modes
- Resetare automată: Short S33 and S34; outputs close automatically after faults are cleared
- Resetare manuală: Connect an external normally open reset pushbutton to S33-S34; manual push is required to restore outputs
Difference from MSR126.1R: MSR126.1R only provides monitored manual reset without automatic reset function
2.4 Safety Output Contacts (Force-guided safety contacts complying with IEC 61810-3)
2 safety normally open (NU) contacte: 13-14, 23-24
Load Ratings:
DC-13: 6A/24V DC; 3A/24V DC (for frequent switching)
AC-15: 5A/250V AC
Timp de răspuns: Aproximativ. 15Domnișoară; Recovery Time: 100Domnișoară
No auxiliary alarm contacts
- Safety Certification Ratings (Top Industry Standards)
ISO 13849-1: Categorie 4 / PL e
IEC 61508 / IEC 61511: SIL 3
ÎN 954-1: Categoria de siguranță 4, Categorie 0 Stop
Certificari: CE, cULus, CCC, BG, C-Tick
- Dimensiuni mecanice & Montare
Lăţime: 22.5mm (compact DIN rail mounting)
Dimensiunea de ansamblu: 110mm (H) × 75 mm (D) × 22.5mm (W)
Greutate: 160g
Terminale: Fixed screw terminals (non-pluggable), Grad de protecție IP20
Temperatura de operare: -25℃ ~ +70℃
- Front Panel LED Indicator Meanings
- PWR (Verde): Steady on when power supply is normal
- CH1 (Verde): Illuminated when Channel 1 input circuit is closed
- CH2 (Verde): Illuminated when Channel 2 input circuit is closed
All three LEDs on → Safety output contacts closed; Any single channel open → Outputs cut off
- Scenarii tipice de aplicare
- Dual-channel emergency stop button circuit monitoring
- 4-wire safety door switches (with short-circuit detection)
- Perdea luminoasă de siguranță / light screen safety circuits
- Safety cut-off for machine tools, automated production lines and packaging equipment
Suitable for equipment requiring high safety ratings of PL e / SIL3
- Series Model Comparison for Selection
| Catalog No. | Internal Code | Modul de resetare | Alimentare electrică | Configurare canal |
| 440R‑N23114 | MSR126.1T | Selectable Auto/Manual Reset | 24V AC/DC | Dual-channel 4-wire |
| 440R‑N23113 | MSR126.1R | Monitored Manual Reset Only | 24V AC/DC | Dual-channel 4-wire |
| 440R‑N23112 | MSR126T | Auto/Manual Reset | 230V și | Dual-channel 4-wire |
- Brief Wiring Logic
- Connect 24V AC/DC power to terminals A1/A2
- Wire two NC safety switches (oprire de urgență / întrerupătoare de uși) in series to S11-S12 and S21-S22 respectively
- Short-circuit S33-S34 for automatic reset; connect an NO pushbutton in series for manual reset
- Wire the safety coil of main contactors in series across terminals 13-14 şi 23-24
- Disconnection of any safety input or cross-channel short-circuit will simultaneously open both NO outputs to cut power supply
- Troubleshooting Guidelines
- PWR LED off: Power phase loss, insufficient voltage or loose wiring
- Single CH1/CH2 LED off: Corresponding channel switch open or circuit wire breakage
- Both CH1 and CH2 LEDs lit but outputs fail to close: Cross-channel short-circuit fault; power cycle to reset, or reset circuit not shorted / reset button not pressed
- Sudarea la contact: Excessive output load; replace contactors with higher capacity
Full Specifications of Safety Output Contacts for Allen-Bradley 440R-N23114
- Basic Contact Structure
- Cantitate & Tip: 2 independent redundant safety normally open (NU) contacts at terminals 13-14 şi 23-24; no auxiliary alarm contacts or delayed outputs
- Contact Construction: Force-guided safety contacts (IEC 61810-3), dual-channel redundant mechanical interlock. Single contact welding cannot maintain circuit conduction, fulfilling Category 4 / PL e / SIL3 safety architecture
- Material de contact: AgSnO₂ silver tin oxide, arc-resistant and anti-welding
- Minimum Conducting Current: 10mA (ensures reliable circuit detection by contacts)
- Rated Load Currents (Official Standard Load Categories)
2.1 Sarcina AC (AC-15, standard load for electromagnetic contactors)
250V și: 6O (inductive-resistive load, cosφ=0.35)
UL B300 certified rating: 5O / 250V și
2.2 DC Load (DC-13, electrovalve / DC coils)
Frequent switching at 24V DC: 3O (standard switching rating)
Low-frequency light load (0.1Hz) at 24V DC: Max. 6A for short-term use (long-term high-frequency operation not recommended)
2.3 Continuous Thermal Current Ith (static carrying current without switching)
Maximum static continuous current per single contact: 6O (only for permanent conduction with rare break operations)
- Rezistenta electrica & Operating Timing
- Rezistenta electrica (220V și / 4O / cosφ=0.35)
6A breaking capacity: 100,000 operațiuni
4A light load: 500,000 operațiuni
- Safety Operation Timing
Response time from safety input open to contact break: ≤15ms
Contact pull-in recovery time after fault clearance: Aproximativ. 100Domnișoară
- Tensiune de rezistență dielectrică
Withstand voltage across open contacts: AC750V for 1 minut
Insulation resistance (DC500V test): ≥1000MΩ
- External Protection & Wiring Limitations
- Recommended Fuse for Output Circuit
Slow-blow fuse: 6O; Fast-acting fuse: 10O. Over-rated fuses are prohibited to prevent contact ablation and welding
- Applicable Wire Gauge: 0.2~2.5mm² solid / stranded copper wires; fixed non-pluggable screw terminals
- Maximum Operating Voltage: 250V și / 30În DC; overvoltage is strictly forbidden
- Contact Performance Matching Safety Ratings
ISO 13849-1: Categorie 4, PL e (independent cut-off via dual redundant contacts)
IEC 61508: SIL3; single contact failure will not disable safety cut-off function
Stop Category: ÎN 60204-1 Categorie 0 hard cut-off stop
- Quick Load Selection Table
| Tip de încărcare | Voltaj | Curent nominal | Scenarii de aplicare |
| AC-15 | 250V și | 6O | AC contactor coils |
| DC-13 | 24În DC | 3O | DC solenoid valves, contactoare DC |
| Static Continuous | ≤250VAC / 30VDC | 6O | Circuits with permanent conduction and minimal breaking operations |
tic Continuous | ≤250VAC / 30VDC | 6O | Circuits with permanent conduction and minimal breaking operations |