PHOENIX CONTACT PLC-BSC-24DC/21

Model Definition Complete Model: PLC-BSC-24DC/21 Order Number: 2966016 Brand Series: Phoenix Contact PLC-INTERFACE ultra-slim relay base Model Breakdown PLC: Base for PLC interface relay module BSC: Basic economical base with screw connection 24DC: Rated control coil voltage DC24V 21: 1 contact de schimbare (1NU + 1NC, 1PDT single-pole double-throw) Descriere produs: Base only, relay insert not ...

  • Detalii despre produs

Definiția modelului

  1. Model complet: PLC-BSC-24DC/21
  2. Număr de ordine: 2966016
  3. Brand Series: Phoenix Contact PLC-INTERFACE ultra-slim relay base
  4. Defalcarea modelului

PLC: Base for PLC interface relay module

BSC: Basic economical base with screw connection

24DC: Rated control coil voltage DC24V

21: 1 contact de schimbare (1NU + 1NC, 1PDT single-pole double-throw)

  1. Descriere produs: Base only, relay insert not included. Must be used with matching pluggable relays (2961105 / 2961118).
  2. Electrical Specifications of Control Side Input (A1+/A2-)
  3. Tensiune nominală de control: 24 În DC
  4. Gama de tensiune de operare: 19.2 V DC ~ 30 În DC
  5. Built-in Protection Circuit: Freewheeling damping diode + reverse polarity protection diode to prevent PLC output burnout from reverse connection
  6. Indicator de stare: Integrated yellow LED on base, lights steadily when coil is energized
  7. Input Power Consumption: Aproximativ. 1.1 W
  8. Minimum Driving Current: 5 mA, directly compatible with PLC NPN/PNP transistor outputs (S7-1200/1500, Mitsubishi, Inovaţie, etc.)
  9. Rated Parameters of Load-side Contacts (12/11 Comun, 14 Deschis normal, 12 În mod normal închis)

3.1 General Load Ratings

Maximum Switching Voltage: 250 V și / 30 În DC

Rated Continuous Thermal Current Ith: 6 O

AC-15 Inductive Load (Contactor Coils): 6 O / 250 V și

DC-13 Inductive Load (Solenoid Valves): 3 O / 24 În DC

3.2 Izolare & Rezistenta la Tensiune

Isolation Withstand Voltage (Coil to Contacts): 4 kV AC for 1 minut

Withstand Voltage across Open Contacts: 2 kV AC

Rezistenta de izolare (DC 500 V Test): ≥10⁹ Ω

3.3 Rezistenta electrica (with Original Phoenix Relay Insert)

6 O / 250 V și: 100,000 operațiuni

3 O / 24 În DC: 200,000 operațiuni

3.4 Formular de contact: 1PDT Single-Pole Double-Throw (11 Comun, 14 NU, 12 NC)

  1. Dimensiuni mecanice & Montare
  2. Lăţime: 6.2 mm (ultra-slim design saves DIN rail space, zero-gap side-by-side mounting supported)
  3. Dimensiuni generale: W6.2 mm × H94 mm × D80 mm
  4. Sina de montare: Standard DIN NS35/7.5 rail
  5. Housing Flame Retardancy: UL94 V0
  6. Culoare: Base body grey-green, relay latch orange
  7. Greutate: Aproximativ. 45 g
  8. Terminal Specifications (All M3 Screw Terminals)
  9. Fire aplicabile:

Solid single-core wire: 0.14~2,5 mm²

Stranded multi-core wire: 0.14~2,5 mm²; max. 2.5 mm² with ferrule terminals

AWG Range: 26 AWG ~ 14 AWG

  1. Cuplul șurubului: 0.6~0.8 N·m
  2. Wire Stripping Length: 8 mm
  3. Terminal Partition

Partea stângă: Control circuit A1+, A2(connect to PLC outputs)

Right Side: Load circuit 12(NC), 11(COM), 14(NU)

  1. Condiții de mediu & Aprobari
  2. Temperatura de operare: -25 ℃ ~ +60 ℃
  3. Depozitare & Transport Temperature: -40 ℃ ~ +85 ℃
  4. Gradul de poluare: 3, for indoor industrial control cabinet installation
  5. Certificari: CE, cULus, VDE, GL Marine Approval, RoHS Compliant
  6. EMC Class: Class A industrial equipment
  7. Matching Relay Inserts (Must Be Ordered Separately)
Relay Insert ModelTensiunea bobineiCapacitate de contactCompatible Base
2961105DC 24 V6 A 1PDT2966016
2961118DC 24 V with LED indicator6 A 1PDT2966016
  1. Scenarii tipice de aplicare
  2. PLC digital output isolation to drive small contactors, solenoid valves and indicator lights
  3. IO signal transfer and separation of strong/weak current on automated production lines
  4. On-off control of small loads for machine tools, packaging equipment and assembly lines
  5. Ultra-slim modular signal expansion for high-density IO cabinets
  6. Series Model Selection Comparison
ModelComanda nr.LăţimeNumber of Contact SetsTensiunea bobinei
PLC-BSC-24DC/2129660166.2 mm1 changeoverDC 24 V
PLC-BSC-24DC/21-21296701514 mm2 changeoverDC 24 V
PLC-BSC-230UC/2129660296.2 mm1 changeoverAC/DC 230 V
  1. Brief Wiring Logic
  2. Conectați-vă 24 V DC PLC output to base terminals A1(+) and A2(-); LED illuminates and relay pulls in.
  3. Pull-in State: 11(COM) 14(NU) închis; 11 disconnected from 12(NC).
  4. Stare dezactivată: 11(COM) 12(NC) închis; 11 disconnected from 14(NU).
  5. Load Circuit: Connect AC220 V / DC24 V loads to COM+NO or COM+NC for switching control.
  6. Troubleshooting Guidelines
  7. LED off: No PLC output, reversed A1/A2 wiring, loose terminals
  8. LED on but load inactive: Damaged relay insert, loose contact wiring, open-circuit load
  9. Frequent contact ablation: Curentul de sarcină depășește 6 O; external auxiliary contactor required for capacity expansion
  10. Unintended operation: No absorption component for inductive PLC loads; freewheeling diode can be paralleled on the base side

Application Scenarios of PHOENIX CONTACT PLC-BSC-24DC/21 (2966016)

Acest 6.2 mm ultra-slim PLC interface relay base mainly realizes PLC transistor output isolation & transfer, strong/weak current separation and small load switching for compact control cabinet wiring. It fits all 24 V DC PLC digital output applications, categorized into industry segments, equipment types and cabinet internal functions as below:

  1. General Automation OEM Equipment Applications

1.1 Mașini-unelte & Metal Processing Equipment

CNC lathes, machining centers, polizoare, punch presses: PLC outputs drive cooling solenoid valves, lubrication pumps, tool magazine cylinders, indicator lights and small contactor coils

Bending machines, mașini de tăiat: Control pneumatic clamps, safety door warning lights and alarm buzzers

Avantaje: Ultra-slim to save cabinet space; pluggable relay allows fast replacement without wire disconnection during machine breakdowns

1.2 Ambalare, Umplere & Food Processing Machinery

Beverage filling machines, etichetatoare, flow wrapping machines, triere & rejection equipment

Control material distributing cylinders, photoelectric rejection valves, conveyor start/stop, fault warning lights and hot air blowers

Suitable for clean-room control cabinets; screw terminals resist vibration and maintain stable service life under frequent switching cycles

1.3 3C Electronice, Baterie cu litiu & PV Equipment

SMT placement machines, dispensers, lithium battery filling/sealing equipment, PV module production lines

Drive micro solenoid valves, vacuum generators, sensor indicator lights and small signal contactors

High-density PLC output points fit the 6.2 mm narrow design for compact arrangement to solve space shortage in IO cabinets

1.4 Transmiterea & Echipamente logistice

Transportoare cu bandă, linii de role, depozite automatizate, sorting lines, control cabinets matched with AGVs

Control track switch cylinders, stopper cylinders, position indicator lights, audio-visual fault alarms and guard lock prompts

  1. Discrete Manufacturing Production Line Applications
  2. Automotive Assembly Lines

Sudare, coating and final assembly stations: Solenoid valves for robot clamps, station indicator lights, safety bypass prompts and pneumatic clamping mechanisms. Isolates heavy interference from welding machines to protect PLC output points from breakdown induced by inductive loads.

  1. Cauciuc & Plastic Molding Equipment

Mașini de turnat prin injecție, extrudere: Barrel cooling fans, material suction solenoid valves, mold temperature controller signal switching and safety door status indicator lights

  1. Imprimare & Utilaje textile

Printing presses, warp knitting machines, imprimare & echipamente de vopsire: Tension cylinders, ink valves, shutdown alarms and fabric deviation correction actuators

  1. Municipal, Tratarea apei & HVAC Integrated Control Cabinets
  2. Stații de epurare, water supply pump station control cabinets: Bar screen alarms, electric valve signals, liquid level indicator lights and auxiliary control of submersible pumps
  3. Aer conditionat central & air purification units: Air damper actuators, humidifier solenoid valves and differential pressure alarm lights
  4. Building intelligent control: Lighting zoning control, exhaust fans, access status feedback and fire linkage signal transfer

Caracteristici: Designed for 24/7 funcţionare continuă; built-in freewheeling diode suppresses solenoid valve surge voltage to protect PLC I/O cards

  1. Energie Nouă, Stocarea Energiei & Test Equipment
  2. Control cabinets matched with PCS energy storage converters, lithium battery testing equipment and auxiliary cabinets of PV inverters
  3. High/low voltage electrical test benches and aging test equipment: Signal switching for test points, indicator lights and micro solenoid valves

Wide operating temperature range (-25 ℃ ~ +60 ℃) fits indoor machine rooms and constant-temperature outdoor control cabinets

  1. Tranzit Feroviar & Small Construction Machinery Matching

Metro platform screen door control cabinets, electrical boxes for small construction machinery (loaders, mașini de tăiat)

Drive warning lights, electromagnetic directional valves and operation panel indicator lights; vibration-resistant screw terminals prevent loose wiring

  1. Typical Internal Cabinet Functional Applications (General Retrofit & Project Matching)
  2. PLC Output Isolation Protection (Funcția de bază)

24 V transistor PLCs including Siemens S7-1200/1500, Allen-Bradley, Mitsubishi, Inovance and Xinje only supply 0.5 Un curent de ieșire, insufficient to directly drive solenoid valves or contactors. This relay expands the switching capacity to 6 A and isolates back EMF from inductive loads to avoid I/O point burnout.

  1. Physical Separation of Strong & Weak Current Signals

4 kV insulation isolation between 24 V weak-current PLC control circuits and 220 V AC load circuits prevents high voltage back-feed to controllers and improves equipment safety rating.

  1. High-Density IO Cabinet Wiring

6.2 mm ultra-slim width supports zero-gap side-by-side installation, doubling the number of relays on the same DIN rail length, ideal for centralized cabinets with massive I/O points.

  1. Signal Distribution & Contact Conversion

1 set of changeover contacts (1NU+1NC) enables one PLC signal to control two different loads simultaneously; NC contact can be used for fault alarm circuits.

  1. Equipment Retrofit & Old Cabinet Capacity Expansion

Replaces standard 14 mm wide relay bases to save rail space when existing cabinet space is limited. Pluggable relay design allows on-site maintenance without wire disconnection and reduces downtime.

  1. Not Recommended Application Scenarios (Application Limitations)
  2. Safety circuits, emergency stop and safety door interlocks (440R series safety relays are required; this product has no force-guided contacts and fails to meet PL e safety certification)
  3. High-power loads (single channel exceeding 6 A AC-15 / 3 A DC-13; external high-capacity contactors required for capacity expansion)
  4. Outdoor unenclosed enclosures (Grad de protecție IP20; must be installed inside standard sealed control cabinets)
  5. Unshielded cabinets with heavy interference from high-frequency high-voltage large inverters (surge suppressors must be added for matching use)

Complete Mounting Instructions for PHOENIX CONTACT PLC-BSC-24DC/21 (2966016)

  1. Basic Mounting Type: Standard DIN Rail Snap-in Installation (Only Official Mounting Method)
  2. Applicable Rail Specification

Only compatible with national/European standard NS 35/7.5 DIN mounting rail (35 mm latime, 7.5 mm height). Direct panel mounting via drilled holes or wall screw mounting is not supported.

  1. Arrangement Characteristics

Zero-gap dense side-by-side mounting available; cel 6.2 mm slim design requires no reserved heat dissipation gap for high-density IO cabinet layout. Install PLC-ATP insulating partitions between adjacent modules with mixed high/low voltage circuits for reinforced electrical isolation.

  1. Unrestricted Mounting Orientation

Can be mounted horizontally, laterally or vertically with no mandatory angle; only ensure adequate ventilation inside the control cabinet.

  1. Step-by-Step Rail Assembly & Disassembly

2.1 Base Installation Steps

  1. Remove oil stains and metal debris from the DIN rail surface and fix the rail firmly to the cabinet mounting plate.
  2. Hook the upper rear latch of the base onto the top edge of the DIN rail slot.
  3. Press down the lower half of the base until an audible click confirms the spring latch locks the base fully against the rail.
  4. Install multiple modules side by side seamlessly in sequence.
  5. Fit end stoppers at both rail ends if positioning is required to prevent sliding caused by vibration.

2.2 Base Removal Steps

  1. Cut off power and disconnect all wiring.
  2. Insert a flathead screwdriver into the spring latch slot at the bottom of the base.
  3. Pry downwards to release the lower locking mechanism.
  4. Tilt the bottom edge outward and lift the base up to disengage from the upper rail edge for removal.
  5. Relay Insert Plug-in Installation (Base Matching Operation)

This product is base-only and must be paired with 2961105 / 2961118 relay inserts:

  1. Align the relay with the upper slot of the base and press straight down for insertion.
  2. The orange latch automatically locks to prevent loosening under vibration.
  3. Removal: Pinch the orange latch to flip outward, then pull the relay insert upward for quick replacement without disconnecting wires.
  4. Terminal Wiring Installation (M3 Screw Connection)
  5. Standard wire stripping length: Fixed at 8 mm; excessive length risks short circuits, insufficient length causes poor contact.
  6. Applicable Cables: 0.14~2.5 mm² solid/stranded wires, AWG26~14; ferrule terminals are recommended for stranded wires.
  7. Cuplul de strângere: 0.6~0.8 N·m; excessive torque strips screws, insufficient torque leads to heat and poor contact.
  8. Terminal Partition: Left side A1/A2 (PLC control circuit); Right side 11/12/14 (load contact circuit). Clear zoning facilitates wiring.
  9. Optional Matching Mounting Accessories
  10. PLC-ATP Insulating Partition: Install between adjacent modules where one side carries 220 V high voltage and the other carries 24 V low voltage to strengthen electrical isolation.
  11. FBST Plug-in Bridge Connectors: Distribuie 24 V power supply for multiple modules to parallel A1/A2 terminals in batches and reduce redundant wiring.
  12. DIN Rail End Stoppers: Secure both ends of a full row of modules to prevent sliding and dropping during equipment transportation and vibration.
  13. Mounting Environment & Restrictions
  14. Grad de protecție IP20; only for installation inside sealed control cabinets. Outdoor and unenclosed box installation prohibited.
  15. Temperatura ambiantă de funcționare: -25 ℃ ~ +60 ℃; reserve ≥10 mm clearance above modules for heat dissipation.
  16. Keep away from heat-intensive and high-interference devices such as inverters and contactors; avoid tight fitting with high-power heat sources.
  17. Do not install in areas with direct exposure to water mist, heavy dust or corrosive gas.
  18. Mounting Prohibitions
  19. Violent knocking of base or relay insert is forbidden to avoid rear latch fracture.
  20. Do not pull the base diagonally with force to prevent rail deformation and latch damage.
  21. High/low voltage modules cannot be placed closely without insulating partitions, which carries risk of dielectric breakdown and electric leakage.
  22. Exposed loose copper strands from multi-core wires at terminals are prohibited to avoid phase-to-phase short circuits.