Defalcarea codului de model
MY2N-GS DC24V
- MELE: Miniature General-Purpose Power Relay Serie
- 2: 2 stâlpi (DPDT, 2NU + 2NC, 2 Form C contacts)
- N: Equipped with built-in LED operation indicator and mechanical status window (green LED for DC coils)
- GS: Upgraded new generation; direct drop-in replacement for discontinued MY2N-J
- DC24V: Rated coil voltage DC 24 V
Extended variants:
MY2N-D2-GS DC24V: Built-in freewheeling diode (suppresses coil back EMF, ideal for direct PLC driving)
MY2IN-GS: Equipped with locking test lever for circuit inspection; Suffix -R denotes export version with fully compatible pin layout
- Specificații electrice de bază
2.1 Parametrii bobinei (DC24V)
Tensiune nominală: DC 24 V
Consumul de energie al bobinei: 0.7 W
Coil resistance (@23℃): ≈662 Ω
Operate voltage: ≤80% of rated voltage (≤19.2 VDC)
Tensiunea de eliberare: ≥10% of rated voltage (≥2.4 VDC)
Allowable voltage fluctuation range: 21.6~26.4 VDC
2.2 Contact Ratings (Sarcină rezistivă, Nominal 5A)
Configurarea contactului: 2 sets of Form C changeover contacts (DPDT)
Contact material: Silver (Ag)
Rated switching capacity:
✅ 5A / 250V și
✅ 5A / 30În DC
Maximum continuous carry current: 10O (static steady-state conduction; frequent switching not recommended)
Minimum applicable load: 1mA / 5VDC (suitable for low-level signal circuits)
Maximum switching capacity: 1100VA (AC); 120W (DC)
2.3 Durata de viață
Durata de viata mecanica: 50 milioane de operațiuni (18,000 cicluri/oră)
Durata de viata electrica (@5A resistive load): ≥500,000 operations (2,400 cicluri/oră)
Operate time ≤15ms; Release time ≤5ms
2.4 Rezistenta dielectrica & Izolare
Coil ↔ Contacts: 2000V și / 1 min
Contacts of different poles: 2000V și /1 min
NO and NC contacts within the same pole: 1000V și /1 min
Insulation resistance ≥1000 MΩ (measured at 500VDC)
- Pin Definition (Standard 8-pin plug-in layout)
Compatible sockets: PYF08A-E / PYFZ-08-E
Pin 13, 14: Coil terminals (non-polarized for standard MY2N-GS; Polarity required for D2 version: Pin14=Positive, Pin13=Negative)
1st contact set: 9 (COM common), 1 (NC Normally Closed), 5 (NO Normally Open)
2nd contact set: 12 (COM common), 4 (NC Normally Closed), 8 (NO Normally Open)
Wiring principle: Energize coil pins 13-14 → 9-5 & 12-8 aproape; Power off → restore NC path 1-9 & 4-12
- Compatible Socket List
| Model de priză | Tip terminal | Metoda de montare | Observații |
| PYF08A-E | Borne cu șurub M3 | DIN rail / montare cu șuruburi | Most widely used standard domestic socket |
| PYFZ-08-E | Finger-safe screw terminals | DIN rail | Preferred for control cabinet safety design |
| PYF-08-PU | Spring push-in terminals (fără unelte) | DIN rail | Improves wiring efficiency |
Accesoriu optional: PYC-A1 locking clip (prevents relay loosening under vibration)
- Ambient Operating Limits
Temperatura de functionare: -40℃ ~ +70℃ (No condensation, no icing)
Temperatura de depozitare: -55℃~+70℃
Humidity range: 5%~95%RH; condensation and long-term moisture ingress prohibited
Unsuitable environments: Praf greu, gaz corosiv, sustained severe vibration
- Ghid de selecție & Critical Restrictions
- Sarcini inductive (electrovalve, bobine de contactor)
Standard MY2N-GS has no built-in surge suppression. For DC inductive loads, select MY2N-D2-GS with integrated diode. Fit external RC snubber circuits for AC inductive loads, otherwise rapid contact erosion will occur.
- Overload forbidden
5A is the rated switching current. Avoid switching loads exceeding 6A continuously. Derate for motors and lighting loads with high inrush current.
- Do not drive coil via high-frequency PWM
Continuous PWM switching causes contact chatter and burnout. Select SSR solid-state relays for high-frequency control scenarios.
- Never mix AC & DC coil models
Powering DC coil relays with AC voltage leads to overheating and permanent damage; AC coil relays fail to pull in under DC supply.
- Not applicable for safety circuits
No forced guided contacts. Use dedicated safety relays such as G9SX for emergency stop and safety interlock loops.
- Scenarii tipice de aplicare
PLC signal expansion, pneumatic solenoid valve control, small contactor driving, control cabinet logic interlock, lighting circuit switching, signal transfer on automated production lines.
- Drop-In & Alternative de upgrade
- Direct replacement for legacy model: MY2N-J DC24V (identical pin layout and compatible sockets)
- Built-in freewheeling diode upgrade: MY2N-D2-GS DC24V
- 4-contact variant within the same series: MY4N-GS DC24V (14-pin socket PYF14A-E required)
Application Industry & Scenario Overview: OMRON MY2N-GS DC24V 5A
Core positioning: DC24V controlled intermediate relay with 2 contacte de schimbare (DPDT). Mainly used for signal transfer after PLC outputs and low-power load switching; rated 5A/250VAC contacts, suitable for low-voltage control of high-voltage circuits.
Limitation reminder: Cannot be used as safety relay; not fit for high-frequency switching, high-inrush loads, explosive or heavily corrosive environments.
- Automatizare industrială (Largest Application Field)
- Custom automation equipment
Conveyor systems, module de transfer, stop cylinder control, directional switching for small pneumatic solenoids; signal interlock for photoelectric and proximity sensors, indicator light control.
- Mașini-unelte
CNC auxiliary indicator lamps, lubrication pump on/off, door limit signal transfer, cooling fan control, auxiliary loops for tool changers.
⚠ Machine tools contain many inductive loads (electrovalve). MY2N-D2-GS (diodă încorporată) is recommended to protect contacts and PLC modules.
- Ambalare & Mașini de imprimat
Case sealers, etichetatoare, film winding mechanisms, small actuator switching, alarm buzzers and signal light circuits.
- Cauciuc & Plastic Injection Auxiliary Equipment
Hopper heating fans, material level alarm, signal transfer for conveyor start/stop control.
- HVAC & Automatizarea clădirilor
Central air-conditioning control cabinets: Dispozitive de acționare a clapetelor de aer, differential pressure alarms, auxiliary fan control, anti-freeze protection signal interlock
Fresh air systems, ventilatoare de evacuare, cooling tower auxiliary circuits
Zone lighting control; fire alarm signal transfer (only signal relay, NOT main fire protection circuit)
- Logistică & Echipamente de depozitare
Automated warehouses, sorting conveyor lines, peripheral control cabinets for AGVs
Transportoare, sorting baffle cylinder control, logic expansion for photoelectric sensors
Indicator lights and alarm driver for warehouse access control
- Tratarea apei & Environmental Equipment
Dosing systems, auxiliary control of small water pumps, high/low level signal transfer, aeration fan auxiliary circuits, signal switching for online water quality monitoring cabinets.
Environmental note: Anti-condensation treatment is mandatory inside humid cabinets to prevent contact oxidation and poor connectivity.
- Energie, EV Charging & PV Auxiliary Cabinets
- Auxiliary fault alarm and cooling fan control for small PV combiner boxes
- Signal transfer inside AC charging station control boards, fault indicator lights and auxiliary contactor coil driving
Forbidden: Do NOT switch high-voltage DC main circuits; only permitted for low-voltage control loops.
- Utilaje alimentare & Central Kitchen Equipment (Key Target Segment)
Vegetable washing equipment, transportoare, small exhaust fans, warning lights
Smart Canteen & Central Kitchen Electrical Cabinets: Alarm signal for transparent kitchen monitoring, automatic door control, auxiliary ventilation control, solenoid valve drive for cleaning machines
✅ Advantage: DC24V is standard industrial voltage, unified with HMI, PLC and sensor power supply, supporting standardized cabinet wiring.
- Rail Support & Off-Highway Mobile Equipment
Onboard control cabinets for construction machinery, small tunnel ventilation control boxes, barrier and gate control cabinets; access control lock and traffic light drivers.
Vibration warning: Fit PYC-A1 locking clip to avoid relay disconnection.
- Laborator & Testing Instruments
Aging test equipment, thermostats, small test fixtures; electrovalve, low-power heating loads and alarm signal switching.
Compatible Load Classification
✅ Recommended Loads
- DC24V miniature solenoid valves, indicator lamps, sunete
- 220VAC small fans, lighting loads, AC contactor coils
- Passive dry contact signal transmission
❌ Not Recommended / Strictly Forbidden Loads
- High-power motors and heating elements (inrush current far exceeds 5A rating)
- Loads with switching frequency >10 cycles/minute (accelerates contact wear)
- Hazardous explosive zones (fără certificare împotriva exploziilor)
- Safety interlock and emergency stop circuits (use dedicated safety relays e.g. G9SX)
Selection Matching Advice
- Driven by PLC transistor outputs → Priority: MY2N-D2-GS (diodă încorporată, prevents back EMF damage to PLC)
- Driven by relay-output PLC → Standard MY2N-GS directly applicable
- If driving inductive loads such as contactors and solenoids without diode version, fit external surge absorption components.
Dimensiuni de montare: OMRON MY2N-GS DC24V (5O) Official Standard Values
- Relay Body (without socket, 8-pin plug-in)
Maximum overall dimension (L × W × H): 28.0 × 21.5 × 36.0 mm
Adâncime (front-back): ≤28 mm
Lăţime (left-right): ≤21.5 mm
Înălţime (excluding pins): ≤36 mm
Ace: 8 cylindrical plug pins, standard 8-pin layout for MY2 series.
- Dimensions of Common DIN-mount Sockets
1) PYF08A-E (Standard widely used socket)
Dimensiunea de ansamblu: 72 (D) ×22 (W) ×30 (H) mm
Montare: 35mm standard DIN rail or screw fixing
Screw mounting holes: 2 buc, Φ4.2×5 slotted hole, center distance 44 mm
Terminal screw specification: M3
2) PYFZ-08-E (Finger-safe safety socket)
Dimensiunea de ansamblu: 72 (D) ×23 (W) ×31 (H) mm
3) PYF-08-PU (Push-in spring terminal socket)
Dimensiunea de ansamblu: 72 ×23 ×31 mm
Reference total height: Relay fully inserted into socket ≈64 mm (for cabinet layout reservation)
- PCB Mount Alternative (Optional PY08-02 soldering socket)
For PCB soldering installation: PY08-02 PCB socket, fully pin-compatible with MY2N-GS.
- Practical Layout Parameters for Control Cabinet Design
- Minimum side-by-side mounting clearance: Can be installed adjacently; single unit occupied width 22 mm. Total width for N units ≈ 22 × N mm
- Vertical cooling clearance recommendation: ≥8mm top & fund; ≥10mm for densely packed arrangements
- Cabinet depth reservation: ≥75mm for socket + relay assembly (avoid interference with cabinet door)
- Vibration-prone applications: Install PYC-A1 locking clip to prevent dislodging.
- Important Remarks
- MY2N-GS shares identical outline dimensions and fully compatible sockets with legacy MY2N-J; direct field replacement supported.
- Narrow width of only 21.5mm, ideal for space-restricted control cabinets.
- Avoid mounting adjacent to contactors and high-power power supplies; elevated ambient temperature shortens contact service life.
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare





















NH42-63-318x560.png)