Siemens SBX61 actuator de supapă electrică cu glob

The SBX61 is a standard electric modulating valve actuator from Siemens Acvatix™ series under the Smart Infrastructure Building Automation product line. It is specially designed for 20mm-stroke 2-way/3-way globe valves. Powered by safe AC 24V supply, it supports DC 0…10V analog proportional control with factory-fitted full-range valve position feedback. It automatically returns to fully closed ...

  • Detalii despre produs

The SBX61 is a standard electric modulating valve actuator from Siemens Acvatix™ series under the Smart Infrastructure Building Automation product line. It is specially designed for 20mm-stroke 2-way/3-way globe valves. Powered by safe AC 24V supply, it supports DC 0…10V analog proportional control with factory-fitted full-range valve position feedback. It automatically returns to fully closed position upon loss of control signal. Featuring a snap-on direct mounting structure, it enables rapid installation without on-site commissioning. It is widely used for flow regulation in building automation systems including HVAC, district heating, cleanroom air conditioning and water treatment.

Per Siemens Acvatix series naming convention, each segment of the model code is explained as follows:

SB: Identificator de serie de produse, representing basic Acvatix electric globe valve actuators dedicated to driving building automation valves

X: Stroke specification code, standing for 20mm rated stroke (SBV models in the same series correspond to 40mm rated stroke)

61: Power supply and control type code, indicating AC 24V operating voltage, DC 0…10V analog positioning signal, built-in 0–10V position feedback, and automatic full-close return when control signal is lost

Specificații tehnice de bază

Evaluări electrice

Element de parametruCaietul de sarciniObservații
Operating Power SupplyAC 24V ±20%Compatible with 50/60Hz mains frequency
Rated Power Consumption5VA (at 50Hz)Low power consumption in holding state
Control Signal InputDC 0…10VAnalog proportional control
Signal Input Impedance>100 kΩMatches output of standard DDC controllers
Valve Position Feedback OutputDC 0…10VLinear correspondence with valve opening
Feedback Load CapacityLoad impedance >10 kΩMax. 10 actuators can be connected in parallel
Fail-Safe ModeAuto full-close on signal lossOnly active when control signal is disconnected while power supply remains intact

Mechanical Performance Parameters

Element de parametruCaietul de sarciniObservații
Rated Stroke20mmFull-stroke linear displacement
Rated Output Thrust800NContinuous output thrust
Full-Stroke Travel Time120sConstant-speed operation across full range
Anulare manualăStandard spanner-type manual adjustmentManually open/close valve during power failure or commissioning
Valve Position IndicationMechanical stroke scaleIntuitive real-time valve position display
Tip de montareSnap-on direct mountingTool-free installation, no adjustment required for matched valves

Fizic & Parametrii de mediu

Enclosure Rating: IP40 (standard for indoor installation)

Temperatura ambiantă de funcționare: -10℃ ~ +55℃

Depozitare & Transport Temperature: -40℃ ~ +70℃

Umiditatea relativă: 5% ~ 95%, necondens

Poziția de montare: Vertical indoor installation with valve stem pointing straight down

Allowable Medium Temperature (when assembled with valve): +1℃ ~ +95℃

Cod HS: 85371090

Standard Built-in Functions & Factory Scope of Supply

Onboard Standard Functions

  1. Proportional Control: Precise positioning via 0–10V analog signal with linearity better than ±5%
  2. Valve Position Feedback: Native 0–10V position signal output for system position readback
  3. Funcție de siguranță: Automatically drives valve to fully closed position when control signal is interrupted
  4. Manual Override Mechanism: Integrated adjustment spanner for manual valve operation without power supply
  5. Mechanical Position Scale: Visible stroke markings to judge valve position without power on site
  6. Commissioning-Free Mounting Structure: Standard snap interface for direct attachment to matched valves

Standard Accessories Included in Carton

  1. Valve stem connection & fixing kit
  2. Snap mounting assembly
  3. Multilingual Quick Installation & Commissioning Guide
  4. Product Certificate of Conformity

Compatible Valve Models

This actuator is only compatible with Siemens PN16 series globe valves with 20mm stroke. Supported models are listed below:

2-way Modulating Valves: VVF47.. serie, VVI41.. serie, VVF42..C series

3-way Modulating Valves: VXF47.. serie, VXI41.. serie, VXF42..C series

Applicable Nominal Diameter Range: DN15 ~ DN50

Definiția terminalului

Marcarea terminalelorFunction DefinitionDescriere
24VPositive terminal of operating power supplyAC 24V power input
G0Common terminal for power & semnaleInternally connected to power neutral and signal ground
YControl signal input terminalPositive pole of DC 0…10V setpoint signal
MCommon terminal for control signalsSame potential as G0, connected to controller signal ground
UValve position feedback output terminalPositive pole of DC 0…10V position feedback signal

Common Optional Accessories (Ordered Separately)

  1. AZX420 Signal Conversion Module: Converts actuator control signal to 4…20mA current input
  2. Outdoor Weather Protection Cover: Upgrades enclosure rating for open-air outdoor installation
  3. Extension Connection Cables: For long-distance wiring to controllers
  4. Auxiliary Mounting Bracket: Adaptor mounting for non-standard valves

Scenarii tipice de aplicare

Sisteme HVAC: Chilled water valves for air handling units, coil valves for fresh air units, terminal temperature control valves

Heating Systems: Secondary network regulating valves for district heating, flow control valves at heat exchange stations

Cleanrooms: Regulating valves for constant temperature & humidity air conditioning water systems

Water Treatment Systems: Makeup water valves, drain valves, chemical dosing regulating valves

Common Troubleshooting Matrix

Simptom de eroareCauza de bazăStep-by-Step Remedial Actions
Actuator does not move at allMissing power supply, incorrect wiring, control signal equals 0V1. Measure voltage at terminal 24V to confirm stable power supply
2. Verify all terminal wiring to eliminate reversed polarity and loose connections
3. Measure control signal at terminal Y to confirm normal controller output
Large deviation between valve position and control signalLoose valve stem connection, zero stroke offset1. Check whether snaps between actuator and valve stem are fully tightened
2. Cut off power, manually close valve fully and recalibrate zero position
3. Confirm controller output range matches actuator specifications
Abnormal valve position feedback signalBroken wiring in feedback loop, excessively low load impedance1. Measure output voltage at terminal U to verify linear variation with valve stroke
2. Ensure total feedback loop load impedance exceeds 10 kV
3. Inspect terminals for oxidation and loose contacts
Jerky operation with abnormal noiseStuck valve plug, worn internal gears1. Cut power and operate with manual spanner to check smooth full mechanical stroke
2. Disassemble and inspect valve plug for scale or foreign jamming debris
3. Replace the entire actuator if internal gears are damaged
Fails to return to full close upon signal lossPower supply cut off simultaneously, faulty internal drive circuit1. Confirm AC 24V supply remains intact while only control signal is lost during fault
2. Inspect control signal cables for open circuits
3. If wiring issues are ruled out, hardware failure is confirmed; return to factory for repair

Mounting Methods for Siemens SBX61 Electric Globe Valve Actuator

The SBX61 adopts standard snap-on direct mounting design from Siemens Acvatix series. No mechanical stroke adjustment is required when matched with original 20mm-stroke globe valves, and installation can be completed by a single operator. The whole process covers three key phases: mechanical valve mounting, electrical wiring, and power-on calibration. Below are official standard mounting procedures and specifications.

  1. Mechanical Mounting (Direct Valve Assembly Procedure)

Pregătirea înainte de instalare

  1. Verificarea compatibilităţii: Only compatible with Siemens 20mm rated stroke globe valves including 2-way valves (VVF47, VVI41, VVF42..C series) and 3-way valves (VXF47, VXI41, VXF42..C series), nominal diameter DN15~DN50.
  2. Pre-Check Condition: Manually rotate valve to fully closed position, wipe dust and grease off valve stem and mounting bracket, confirm no deformation or jamming of the stem.
  3. Instrumente & Consumables: No special tools required; only factory-supplied locating pins and fixing nut assemblies are needed. A small open-end spanner may be used for assistance if necessary.

Step-by-Step Mounting Procedures

  1. Remove Valve Stem Locating Pin

Pull out the original locating pin on top of the valve bracket, hold the valve stem at fully closed low position for easy alignment and insertion of the actuator.

  1. Vertically Align and Fit Actuator

Hold the actuator and lower it vertically, align the bottom drive nut with the top of the valve stem, slide it smoothly onto the valve mounting bracket. Ensure the valve stem fully engages into the internal drive slot of the actuator, and align the holes on both sides of the connecting bracket with those on the valve bracket.

  1. Insert Locating Pin for Fixation

Fine-tune the actuator angle to fully align the side connection holes, insert the matching factory locating pin and press it into locked position. Make sure the pin penetrates both brackets completely without loosening.

  1. Tighten Fixing Nuts

Fasten the fixing nuts on both sides at the bottom of the actuator to firmly connect the actuator and valve bracket. Apply moderate torque only; over-tightening will deform the bracket and is prohibited.

  1. Verify Mechanical Stroke

Use the standard manual adjustment spanner on the actuator side, turn clockwise and counter-clockwise to drive the valve through full stroke manually. Confirm smooth operation without jamming and accurate correspondence between mechanical scale and actual valve opening/closing positions.

  1. Electrical Wiring Installation

Safety Rules Before Wiring

Always perform wiring with power fully disconnected; confirm zero voltage on supply cables before connection.

The actuator rated supply is AC 24V ±20%. Connection to AC 220V power supply is strictly forbidden, which will burn out the unit instantly.

Separate power cables and signal cables during routing to avoid electromagnetic interference. Ground the shielding layer of shielded cables at single end only.

Standard Terminal Wiring Definition

Open the top cover of the actuator terminal compartment and wire per the table below:

Marcarea terminalelorFunction DefinitionSpecificații de cablare
24VAC 24V Power Input TerminalConnect to live wire of controller 24V AC power supply
G0Power Common TerminalConnect to neutral wire of 24V power supply, internally linked with signal ground
YControl Signal Input TerminalConnect to positive pole of DC 0…10V analog setpoint signal
MControl Signal Common TerminalConnect to analog signal ground of controller, same potential as G0
UValve Position Feedback Output TerminalConnect to positive pole of analog acquisition channel on controller, outputs DC 0…10V

Post-Wiring Completion

  1. Tighten all terminal screws and slightly tug cables to ensure no loose connections.
  2. Organize cables, route them out of the terminal compartment via M20 cable glands, and secure cables with proper protection.
  3. Fully snap the terminal compartment cover closed to restore IP40 enclosure protection rating.
  4. Power-On Calibration & Commissioning After Installation

The SBX61 supports automatic calibration upon power-up. No manual parameter setting is required when matched with original Siemens valves. Procedures are as follows:

  1. Confirm control signal terminals (Y-M) output DC 0V (zero-opening command).
  2. Switch on AC 24V power supply. The actuator automatically enters calibration mode, drives the valve slowly to fully closed position and records zero stroke position.
  3. Full calibration takes approximately 12 secunde. After completion, the actuator enters normal standby state with mechanical scale pointing to 0% deschidere.

Function Verification

  1. Input DC 5V control signal, verify valve opening reaches 50% with mechanical scale at midpoint.
  2. Input DC 10V control signal, verify valve fully opens with mechanical scale at 100%.
  3. Measure feedback voltage at terminal U to confirm linear match with control signal and valve opening; deviation ≤±5% is deemed normal.
  4. Optional Accessory Mounting (AZX420 Signal Conversion Module)

If conversion of 0–10V voltage signal to 4–20mA current signal is required, install the AZX420 functional module with the following steps:

  1. Cut off actuator power and remove terminal compartment cover.
  2. Break off the pre-reserved blocking plate on the actuator side for module mounting to expose the 8-pin plug interface.
  3. Align the AZX420 module with pins and push it in smoothly; a snap sound indicates fully seated installation.
  4. Toggle DIP switches on the module to set types of control signal and feedback signal respectively, then refit the compartment cover.
  5. Mounting Prohibitions & Precauții
  6. Mounting Orientation: Vertical installation is mandatory with valve stem pointing straight down. The overall tilt angle shall not exceed 5°. Orizontală, inverted or side mounting is forbidden, which causes abnormal wear of internal gears and jamming operation.
  7. Environmental Limits: Standard IP40 rating is only suitable for dry indoor spaces. Installation in open-air, rainy or condensing environments is prohibited. Ambient temperature must be maintained between -10℃~+55℃; keep the unit away from high-temperature heat sources and steam pipelines.
  8. Mechanical Restrictions: Do not forcibly twist the actuator valve stem by external force; do not operate the manual spanner when power is connected. Medium temperature of matched valves shall not exceed 95℃; dedicated high-temperature valves are required for high-temperature working conditions.
  9. Electrical Restrictions: Hot plug/unplug of control cables is forbidden; connecting power supply to signal terminals is prohibited. Shielded cables shall be adopted for long-distance wiring, and avoid laying signal cables in the same conduit as high-power cables.