Siemens 6EP1437-2BA10 SITOP POWER 40 Trifazat Industrial Power Supply
- Defalcarea codului de model
6EP1437-2BA10
6EP: Standard industrial power supply series of SITOP
1437: High-power three-phase AC model, 40A output platform
2: Basic standard version (without redundant diagnostic interface)
BA: Montare pe șină DIN, 24Ieșire VDC
10: 3-phase 400–500V input, 40O / 960W output specification
- Parametrii electrici de bază
Partea de intrare (3-Phase Industrial Grid)
Input format: 3×400~500V AC, 3-phase 5-wire L1/L2/L3/PE
Frecvenţă: 50/60Hz
Voltage dip tolerance: Minimum 340V for 2 seconds without output collapse
Wire gauge for input terminals: 0.5~4mm² solid/stranded copper wire
Partea de ieșire (Standard Industrial 24VDC)
Ieșire nominală: 24VDC / 40O, total power 960W
Adjustable output voltage range: 22.8~26.4V (tweaked via potentiometer at bottom)
Clipoci & zgomot: Ripple <150mVpp, peak noise <240mVpp
Output terminals: Dual groups of +/terminals for parallel connection; wire gauge 0.5~10mm²
Parallel expansion: Two identical units can be directly paralleled for max. 80A output
Funcții de protecție (Full-condition Protection)
- Protecție la scurtcircuit: Automatic hiccup current limiting, auto-recovery after fault clearance
- Protecție la supratensiune (OVP): Output cut-off when voltage >27V
- Protecție la suprasarcină (OLP): Current limiting at 120% curent nominal
- Protecție la supra-temperatură (OTP): Shutdown on overheat, auto-restart after cooling down
- Protection against input phase loss, surge and industrial EMC interference
III. Mecanic & Specificații de mediu
Montare: Vertical installation on standard 35mm DIN rail
Dimensiuni de gabarit (L × H × D): 160 × 125 × 121 mm
Greutate netă: Aproximativ. 2.0 kg
Clasa de protectie: IP20 (for cabinet installation only)
Temperatura de functionare: 0~+55°C (full power derating required above 55°C)
Depozitare / temperatura de transport: -25℃~+85℃
Umiditate: 5%~95%RH, fara condens
Certificari: CE, UL, GL marine certification; compliant with EN61010, EN61000 industrial EMC standards
- Comparison Table of Same-Series 3-Phase Power Supplies
| Comanda nr. | Intrare | 24V Output | Putere | Poziționare |
| 6EP1436-2BA10 | 3AC 400–500V | 20O | 480W | Medium-capacity 3-phase power supply |
| 6EP1437-2BA10 | 3AC 400–500V | 40O | 960W | High-power standard 3-phase power supply |
| 6EP1437-3BA00 | 3AC 400–500V | 40O | 960W | Equipped with relay signal output (fault contacts 13/14) |
- Definiția terminalului
- Input terminals: L1, L2, L3, PE (3 faze + protective earth)
- Output terminals: Dual sets of +24V, 0V (parallel for current sharing)
- Voltage trimming potentiometer: Located at bottom; adjust with flat screwdriver
- Indicator light: Solid green = normal output; oprit / flashing = fault (pierdere de fază, scurt-circuit, supraîncălzire)
- Scenarii tipice de aplicare
- Large PLC control cabinets (S7-1500/400, full-station power supply for ET200SP distributed I/O)
- Multi-axis servo systems, inverter control stations, posturi de lucru robot
- Ambalare, sortarea logistica, automotive welding & assembly production lines
- Tratarea apei, wind power, metalurgie, cement and other high-power industrial control equipment
- Centralized 24V power supply scenarios requiring 3-phase industrial incoming power and high current loads
VII. Înlocuire & Capacity Expansion Solutions
- Upgraded same-spec model: 6EP1437-3BA00 (with fault relay contacts for PLC diagnostic connection)
- Capacity expansion: Parallel two 6EP1437-2BA10 units for max. 80O / 1920W output
- Downsized alternative: 6EP1436-2BA10 (20O / 480W) for half-load applications
VIII. Installation Prohibitions & Ghid de depanare
Operațiuni interzise (Critical Restrictions)
- Horizontal or upside-down mounting is strictly prohibited; blocked cooling air duct triggers rapid over-temperature protection
- Long-term power-on with direct output short circuit will cause continuous hiccup power derating
- Long-term operation with missing input phase accelerates aging of internal power components
- Do not install alongside high-power inverters without partition plates to avoid EMC interference
Common Fault Matrix
| Fenomen | Cauza de bază | Countermeasures |
| Green light off, no 24V output | 3-phase power loss, întrerupătorul de circuit s-a declanșat, internal overheating | Check 3-phase incoming voltage; power off and cool down then restart; clean dust in air duct |
| Green light flashing, output voltage drop | Output overload / scurt-circuit | Disconnect loads and locate short circuit by segmentation; limit total load within 40A |
| Output voltage below 23V under load | Undersized cables causing excessive voltage drop | Thicken 24V main cables; add auxiliary power supplies nearby |
| Frequent over-temperature shutdown | Ambient temp >55℃, clogged air duct, fully enclosed cabinet | Install cabinet cooling fan, lower ambient temperature, reserve ≥50mm top & bottom ventilation clearance |
Official Overall Dimensions of Siemens 6EP1437-2BA10 (SITOP POWER 40 3-Phase 40A Power Supply)
- Overall Unit Dimensions (L × H × D, unitate: mm)
160 × 125 × 121 mm
Lăţime (horizontal along DIN rail): 160 mm
Înălţime (vertical cooling air flow direction): 125 mm
Adâncime (cabinet depth direction): 121 mm
Greutate netă: Aproximativ. 2.0 kg
- Dimension Differentiation of Confusable Same-Series Models (Avoid Errors in Procurement & Cabinet Layout)
| Comanda nr. | Caietul de sarcini | L × H × D (mm) | Greutate |
| 6EP1436-2BA10 | 3-phase 20A | 90 × 125 × 120 | 1.6 kg |
| 6EP1437-2BA10 | 3-phase 40A (without fault contacts) | 160 × 125 × 121 | 2.0 kg |
| 6EP1437-3BA00 | 3-phase 40A (with fault relay) | 160 × 125 × 121 | 2.0 kg |
| 6EP1437-2BA20 (New PSU300S Series) | New generation 40A | 145 × 145 × 150 | 3.1 kg |
- Cabinet Installation Clearance Requirements
- Sina de montare: Standard 35mm TH35 DIN rail, instalare verticală (terminals downward)
- Top & bottom ventilation clearance: Reserve at least 40mm for heat dissipation; derating mandatory if ambient temp exceeds 55℃
- Side-by-side mounting: Units of same model can be tightly arranged without extra spacing
Notă suplimentară
Dimensions such as 250×180×92 and 145×145×150 shown on some foreign websites belong to the new PSU300S model 6EP1437-2BA20, which is incompatible with the legacy 6EP1437-2BA10. Cabinet cutout and DIN rail layout cannot be shared between them.
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare