Имеет компактную структуру, high-efficiency control and reliable performance, Danfoss FC-051P18KT4E20H3BXCXXXSXXX инвертор delivers outstanding performance in fields including fans & водяные насосы, обработка материалов, еда & textile industry, water treatment, achieving an average energy-saving rate of 30-50%. It also extends service life of equipment, improves product quality and cuts maintenance costs. Reasonable configuration shall be conducted according to load characteristics, ambient conditions and control requirements during model selection to maximize its technical advantages.
- Model Code Definition
| Код | Значение | Подробное описание |
| FC-051 | Код серии | VLT® Micro Drive FC-51 Compact General-purpose Inverter Series |
| P18K | Мощность | Matched motor power: 18.5кВт / 25HP |
| T4 | Power Supply Spec. | T=Three-phase input; 4=380-480VAC voltage class |
| E20 | Класс защиты | защита IP20, chassis mounting type |
| H3 | RFI Filter | Equipped with RFI Class A1/B (С1) filter |
| Б | Brake Unit | Built-in brake chopper |
| Х | Local Control Panel | Without local control panel (LCP to be ordered separately) |
| С | PCB Coating | Coated printed circuit board for higher reliability in harsh environments |
| Х | Power Option | Standard power configuration without special options |
| Х | Adapter A | Standard cable entry |
| Х | Adapter B | No extra adapters |
| SXXX | Версия программного обеспечения | Latest standard software version |
| М5 | Размер кадра | M5 frame (corresponding to 18.5kW power grade) |
| Номер заказа. | 132F0060 | Official unique identification code |
- Основные технические характеристики
| Категория | Спецификация | Примечания |
| Основные параметры | ||
| Номинальная мощность | 18.5кВт / 25HP | Matched motor power |
| Номинальный выходной ток | 37А (Heavy-duty) / 34А (Light-duty) | Current values for different load types |
| Входное напряжение | 3-phase 380-480VAC | Допустимое колебание: ±10% |
| Input Frequency | 50/60Гц | Auto-adaptive |
| Выходное напряжение | 0~100% of input voltage | Varies with frequency |
| Output Frequency | 0-200Гц (VVC+ Mode) / 0-400Гц (U/f Mode) | Vector control / V/f ratio control |
| Control Features | ||
| Режим управления | VVC+ (Voltage Vector Control), U/f Control | Closed-loop vector control available (encoder optional) |
| Перегрузочная способность | 150% rated current for 60 секунды | Standard overload protection |
| Acc/Dec Time | 0.1~3600s | Acceleration and deceleration time set independently |
| Цифровой вход | 5 programmable inputs | Support PNP/NPN logic, 0-24В постоянного тока |
| Аналоговый вход | 1 channel 0-10V/4-20mA | Programmable functions |
| Релейный выход | 2 каналы (1 НЕТ + 1 Северная Каролина) | Max switching capacity: 250VAC/2A |
| Physical Properties | ||
| Степень защиты | IP20 | Chassis mounting |
| Метод охлаждения | Natural cooling + принудительное воздушное охлаждение | M5 frame with built-in fan |
| Температура окружающей среды | -20°С ~ +50°С | Derating operation required above 40°C |
| Относительная влажность | 5%~95%, неконденсирующийся | Standard industrial environment requirement |
| Масса | Приблизительно. 9.98кг (net weight) | Приблизительно. 10.27kg with package |
| Сертификация & Согласие | ||
| Сертификаты безопасности | CE, UL, кУЛ, РоХС | Compliant with EU Low Voltage Directive 2014/35/EU |
| EMC Standard | В 55011 Класс А | EMC requirement for industrial environment |
| ECCN Code | Евросоюз: Y901, US: 3A999.a | Export control classification code |
- Full Series Model List (380-480V Three-phase)
| Власть | Модель | Номер заказа | Номинальный ток | Размер кадра |
| 0.37кВт | FC-051PK37T4E20H3BXCXXXSXXX | 132F0001 | 1.1А | M1 |
| 0.75кВт | FC-051PK75T4E20H3BXCXXXSXXX | 132F0002 | 2.1А | M1 |
| 1.5кВт | FC-051P1K5T4E20H3BXCXXXSXXX | 132F0003 | 3.7А | M1 |
| 2.2кВт | FC-051P2K2T4E20H3BXCXXXSXXX | 132F0004 | 5.2А | M1 |
| 3.0кВт | FC-051P3K0T4E20H3BXCXXXSXXX | 132F0024 | 7.0А | M2 |
| 4.0кВт | FC-051P4K0T4E20H3BXCXXXSXXX | 132F0025 | 9.3А | M2 |
| 5.5кВт | FC-051P5K5T4E20H3BXCXXXSXXX | 132F0026 | 12.5А | М3 |
| 7.5кВт | FC-051P7K5T4E20H3BXCXXXSXXX | 132F0027 | 17.0А | М3 |
| 11кВт | FC-051P11KT4E20H3BXCXXXSXXX | 132F0059 | 25.0А | М4 |
| 15кВт | FC-051P15KT4E20H3BXCXXXSXXX | 132F0060 | 32.0А | М5 |
| 18.5кВт | FC-051P18KT4E20H3BXCXXXSXXX | 132F0060 | 37.0А | М5 |
| 22кВт | FC-051P22KT4E20H3BXCXXXSXXX | 132F0061 | 45.0А | М5 |
- Cross-brand Equivalent Model Comparison
| Danfoss FC-051P18KT4E20H3BXCXXXSXXX | Сименс | Шнайдер | АББ | Replacement Suggestion |
| 18.5kW/37A/380-480V | SINAMICS G120C 6SL3210-1KE22-6UF1 | Altivar 320 ATV320U40N4 | АКС150-03Е-04A1-4 | Similar functions, communication protocols need matching |
| Режим управления: VVC+/U/f | Векторное управление | Векторное управление | DTC Direct Torque Control | ABB features fastest dynamic response; Schneider offers higher cost performance |
| Built-in brake chopper | External accessory required | Встроенный | External accessory required | Danfoss features more flexible configuration |
| RFI Class A1/B | Optional Class A/B | Built-in Class A | Optional Class A/B | Meet industrial EMC standards |
| Without LCP (purchased separately) | Standard BOP-2 | Standard keypad | Standard assistant control panel | Siemens owns friendliest operation interface |
Obsolete Replacement: FC-051 is still mainstream without direct discontinued substitutes. For function upgrade, choose Danfoss FC-301 series with richer functions and support for PROFINET and other advanced communication protocols.
- Application Environment & Industry Cases
Применимые сценарии
Фанаты & Water Pumps: системы отопления, вентиляции и кондиционирования, water treatment plants, cooling towers, realize 30%-50% energy saving via variable frequency speed regulation
Material Conveying: Конвейеры, hoists, упаковочное оборудование, achieve smooth start/stop and precise speed control
Еда & Beverage Industry: Filling lines, этикетировочные машины, sterilization equipment, adapt to humid environment with PCB coating protection
Textile Machinery: Spinning machines, weaving machines, satisfy low-speed high-torque demands
Small Machine Tools: Drilling machines, фрезерные станки, шлифовальные машины, realize accurate speed adjustment
Non-recommended Scenarios
Heavy-duty impact loads: Such as crushers and punch presses (FC-302 series is recommended)
Explosion-proof occasions: Special explosion-proof models required (FC-051 has no explosion-proof certification)
Altitude above 1000m: Derating operation needed (1% power reduction per 100m rise)
Ambient temperature over 50°C: Additional cooling measures or derating operation required
Типичные случаи применения
- Constant Pressure Water Supply System
Adopt FC-051P18KT4 to control 18.5kW water pump with closed-loop control via pressure sensor, realizing 40% энергосбережение, stabilizing pipeline pressure and extending equipment service life.
- Packaging Production Line
Four sets of FC-051 series inverters including 18.5kW model are applied to control conveyor speed for synchronous operation, lowering product damage rate and greatly reducing downtime frequency.
- Central Air-conditioner Fan System
Applied in shopping mall air conditioner fans to adjust rotating speed automatically by ambient temperature, saving about 28,000 RMB electricity fee annually per unit and reducing operating noise.
- Соблюдение требований в области авиаперевозок & Сертификация
Air Freight Regulations
Built-in Capacitor: Equipped with DC bus electrolytic capacitors without lithium batteries, UN38.3 test report is not required
Transport Classification: Non-dangerous goods, deliverable as common electronic products by air
Требования к упаковке
Power off completely with capacitors discharged for more than 5 минуты
Fixed in anti-static package to avoid collision damage
Mark with labels of “Fragile Electronic Equipment” и “Эта сторона вверх”
Main Certifications
| Код неисправности | Fault Description | Возможные причины | Troubleshooting Steps |
| AL16 | Output Short Circuit | 1. Motor winding short circuit | 1. Cut off power and disconnect UVW motor wiring |
| 2. Damaged motor cable | 2. Test three-phase motor winding resistance balance | ||
| 3. Power module failure | 3. Check cable insulation condition | ||
| 4. Reset and test inverter output under no-load state | |||
| AL10 | Motor Overheating | 1. Overloaded operation | 1. Confirm actual load within rated range |
| 2. Poor motor heat dissipation | 2. Clean motor heat sink | ||
| 3. Temperature sensor failure | 3. Inspect PT100 and thermistor connection | ||
| AL51 | DC Bus Undervoltage | 1. Low input voltage | 1. Measure input voltage (normal range: 342-528В) |
| 2. Phase loss of power supply | 2. Check three-phase power balance | ||
| 3. Rectifier bridge failure | 3. Detect rectifier module output | ||
| AL71 | Inverter Overheating | 1. Excessively high ambient temperature | 1. Ensure ambient temperature ≤40°C |
| 2. Cooling fan malfunction | 2. Check fan running status | ||
| 3. Radiator blockage | 3. Remove dust and sundries on radiator | ||
| AL52 | Input Phase Loss | 1. Power supply phase missing | 1. Measure three-phase input voltage |
| 2. Loose wiring terminals | 2. Fasten terminal wiring | ||
| 3. Faulty input contactor | 3. Test contactor switching performance |
- Распространенные неисправности & Руководство по устранению неполадок
| Название аксессуара | Модель | Функция | Necessity |
| Local Control Panel | LCP 12 | On-site parameter setting and monitoring | Рекомендуется (not standard equipped) |
| Brake Resistor | MCE 101-0300 | Dissipate regenerative energy and prevent overvoltage | Mandatory for models with code B |
| Модуль связи | FC CAN/Profibus | Realize industrial network connection | Optional on demand |
| Input Filter | H3 Upgrade Kit | Upgrade EMC performance to Class B | Recommended for electromagnetic sensitive occasions |
| Protective Cover | FC-051-IP40 | Upgrade protection class to IP40 | Recommended for dusty working sites |
- Правила выбора & Quick Tips
- Согласование мощности: Inverter rated current ≥ 1.1 times motor rated current to cope with starting impact
- Voltage Confirmation: Input voltage shall stay within 380-480V with fluctuation ≤±10%
- Brake Configuration: Models with code B have built-in brake choppers, external brake resistors required (power ≥ 30% of motor power)
- Heat Dissipation: Keep ventilation space over 10cm for M5 frame; derate 10% power per 5°C rise above 40°C
- Расширение связи: Additional Modbus/Profibus modules need separate purchase for network communication
- Recommended Key Accessories
| Название аксессуара | Модель | Функция | Necessity |
| Local Control Panel | LCP 12 | On-site parameter setting and monitoring | Рекомендуется (not standard equipped) |
| Brake Resistor | MCE 101-0300 | Dissipate regenerative energy and prevent overvoltage | Mandatory for models with code B |
| Модуль связи | FC CAN/Profibus | Realize industrial network connection | Optional on demand |
| Input Filter | H3 Upgrade Kit | Upgrade EMC performance to Class B | Recommended for electromagnetic sensitive occasions |
| Protective Cover | FC-051-IP40 | Upgrade protection class to IP40 | Recommended for dusty working sites |
Full Analysis on Application Cases of Danfoss FC-051P18KT4E20H3BXCXXXSXXX (18.5кВт) Инвертор
- Overview of Core Application Fields
This 18.5kW/37A/380-480V inverter with built-in brake chopper and coated PCB board is widely applied relying on VVC+ vector control, IP20 protection and high cost performance:
HVAC industry: Central air conditioner fans, cooling towers, водяные насосы
Water treatment: Constant pressure water supply, aeration tanks, sludge return pumps
Погрузочно-разгрузочные работы: Heavy-duty conveyors, лифты, logistics sorting lines
Food industry: Filling machines, sterilization equipment, упаковочные машины
Textile industry: Spinning machines, weaving machines, setting machines
Building material machinery: Миксеры, light-duty crushers
- Detailed Introduction of Five Typical Application Cases
Случай 1: Constant Pressure Water Supply for Residential Communities
Original power frequency water supply system suffered from severe pressure fluctuation, high power consumption and frequent pump startup-stop. After adopting FC-051 constant pressure frequency conversion control system with pressure sensor feedback, it realizes sleep & wake-up automatic operation, cutting daily power consumption greatly, stabilizing water supply pressure and prolonging pump service life obviously.
Случай 2: Central Air-conditioner Fan System in Shopping Malls
Replace fixed-speed fan operation with variable frequency temperature closed-loop control, set minimum frequency to avoid fan surging, realize intelligent speed regulation according to indoor temperature, save massive electricity cost annually and lower operating noise effectively.
Случай 3: Food Packaging Production Line Multi-machine Linkage
Adopt multi-speed regulation and synchronous follow-up control to match operating speed of different conveying equipment. Built-in brake chopper achieves rapid stop, reduces material stacking and product damage rate, and improves overall production efficiency. Coated PCB adapts to humid and dusty food workshop environment.
Случай 4: Spinning Machine Control System in Textile Mill
Replace traditional slip speed regulating motor with VVC+ vector control inverter, realize high torque output at low speed, broaden speed regulation range, promote motor operating efficiency, reduce yarn breakage rate and cut daily maintenance frequency.
Случай 5: Aeration System for Sewage Treatment Plant
Match dissolved oxygen sensor to build PID closed-loop control system, automatically adjust fan air volume to keep dissolved oxygen content in optimal range, stabilize sewage treatment effect, reduce invalid energy consumption and lower equipment abrasion.
- Application Scene Matching Table
| Application Scene | Соответствующий уровень | Основные преимущества | Примечания |
| Constant pressure water supply / circulating pump | ★★★★★ | PI regulation + intelligent logic, prominent energy-saving effect | Equipped with pressure sensor and brake resistor suggested |
| Central air conditioner / cooling tower fan | ★★★★★ | Регулирование температуры с обратной связью, low noise and energy saving | Surge prevention setting required, derate at high altitude |
| Heavy conveyor / hoist | ★★★★☆ | Stable start-stop, strong overload resistance | Confirm actual load type in advance |
| Еда & beverage production line | ★★★★☆ | Многоскоростное управление, high synchronization precision | Coated PCB for humid environment adaptation |
| Textile printing & dyeing machinery | ★★★★☆ | Low-speed high torque, wide speed range | Add anti-interference measures |
| Sewage treatment aeration system | ★★★★☆ | Precise PID control, energy consumption optimization | Regular radiator cleaning required |
| Heavy impact load equipment | ★☆☆☆☆ | – | Choose FC-302 series instead |
| Explosion-proof working environment | ★☆☆☆☆ | – | Special explosion-proof inverters required |
| Altitude over 2000m | ★☆☆☆☆ | – | Not recommended due to large power derating amplitude |
- Key Selection Points for Practical Application
- Match inverter current reasonably according to actual motor load
- Select models with built-in brake units for frequent start-stop and fast stop working conditions
- Choose U/f control mode for fan & pump loads, VVC+ vector control for transmission and processing equipment
- Prioritize coated PCB models for humid, dusty and corrosive sites
- Select matched external accessories and control panels according to on-site debugging and remote control demands
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи




















NH42-63-318x560.png)