ОМРОН CJ Series 4-Channel Isolated Universal Analog Входной модуль (Special I/O Unit)
Статус: Снято с производства. Available via spare parts and second-hand markets. Compatible with CJ1/CJ2/NJ-series PLCs. Independent signal type configuration for each of the 4 каналы, inter-channel isolation. Supports mixed acquisition of temperature sensors, 4~20mA and voltage signals, widely used in industrial process measurement.
✅ Model Explanation
CJ1W: Prefix for CJ-series Special I/O Units
ОБЪЯВЛЕНИЕ: Аналоговый вход
04: 4 каналы
ты: Universal multi-type input
CJ1W-AD04U: Screw terminal type; CJ1W-AD04U-SL: Spring terminal (tool-free) версия
📌 Core Specifications
| Элемент | Параметр |
| Number of Channels | 4СН, input type configurable independently per channel |
| Supported Inputs | Platinum RTD: Пт100, Пт1000, JPt100 (3-проволока) |
| Термопара: К, Дж, Т, л, Р, С, Б | |
| Текущий: 4~20 мА, 0~20 мА | |
| Напряжение: 1~5V, 0~5V, 0~10 В | |
| Разрешение | 1/12000 (Напряжение/Ток, approx.14-bit) |
| Conversion Cycle | 250ms for all 4 каналы |
| Точность (25℃) | Напряжение/Ток: ±0,3% полной шкалы |
| Platinum RTD: The greater of ±0.3%PV or ±0.8℃ | |
| Термопара: The greater of ±0.3%PV or ±1.5℃ | |
| Изоляция | Channel-to-channel isolation; opto+transformer isolation between channels and PLC bus; Withstand voltage AC500V |
| Источник питания | DC5V, Max 320mA (Powered via PLC backplane) |
| Размеры | 31(Вт) ×90(ЧАС) ×65(Д) мм; ≤150g |
| Терминалы | Removable 18-pin terminal block |
| Unit Number | Rotary switch on front: 00~95, must not overlap with other Special I/O Units |
✨ Features
- Universal Mixed Input: 4 channels can be set to different types, например. CH1=Pt100, CH2=4~20mA, CH3=K-type thermocouple
- Built-in Cold Junction Compensation for direct thermocouple use; 3-wire Pt100 measurement, max single wire resistance ≤20Ω
- High/low limit alarm per channel, alarm delay 0~60s and hysteresis setting; open-circuit/error detection
- Zero/Span calibration available during operation
- Automatic value scaling; temperature values stored in CPU multiplied by 10 (например. 256.0℃ → stored as 2560)
- Data exchange: Allocation Relay Area (measured values + alarm flags), DM Parameter Area (диапазон, тревога, channel type)
🛠 Installation & Рекомендации по подключению проводов
- Mount on CJ CPU base or expansion base; it is a Special I/O Unit. Unit number and channel types must be configured in PLC software.
- 3-wire Pt100: A/B/b three wires with equal length; B and b must NOT be shorted outside the module terminals.
- Токовый вход: Module integrates built-in 250Ω sampling resistor, connect in series directly into the loop.
- Max input rating: Voltage ±15V; Current 30mA. Do NOT exceed range.
- Warm up for 30 mins after power on to reach rated accuracy.
⚠️ Troubleshooting (Распространенные неисправности)
- ERR Red LED: Duplicate unit number, insufficient backplane 5V supply, незакрепленные клеммы, incorrect parameter download
- Fluctuating temperature reading: Cold junction interference for thermocouple, unbalanced resistance of 3 Pt100 wires, ground loop interference
- Abnormal 4~20mA reading: Incomplete closed loop, missing external transmitter power supply
- Open-circuit alarm: Broken sensor cable or poor contact
🔁 Alternative Selection Reference
Same-series upgraded model: CJ1W-PH41U (Faster sampling, wider signal types; also discontinued)
New project recommendation for NX series: NX-AD4204 / NX-TC3404 (Separate or universal temperature & аналоговый вход)
Simple alternative if only 4~20mA/voltage required: CJ1W-AD041 (Analog only, no thermocouple/RTD support)
📎 Supporting Document
Manual No.: W466-E1-02 (CJ1W-AD04U Operation Manual)
Compatible PLCs for CJ1W-AD04U (CJ-series Universal Analog Special I/O Unit)
This module is a CJ bus Special I/O Unit, mounted directly on CJ backplane. Restrictions apply for NJ/CP1H. Not compatible with CS series.
✅ Native Direct Compatibility (CJ1 CPUs, mount directly on CJ rack)
CJ1M: CJ1M-CPU11 / CPU12 / CPU13 (Including ETN Ethernet versions)
CJ1G: CJ1G-CPU42H / 43H /44H /45H; CJ1G-CPU42P/43P/44P/45P (Loop control type)
CJ1H: CJ1H-CPU65H / 66H /67H
✅ Native Direct Compatibility (CJ2 CPUs, mount directly on CJ rack)
CJ2M: CJ2M-CPU11 /12 /13 /14 /15 /31 /32 /33 /34
CJ2H: CJ2H-CPU64 /65 /66 /67 (Including -EIP Ethernet models)
✅ NJ Series (Контроллер машины, usable with caveats)
NJ501, NJ301 and other NJ controllers: Can use CJ1W-AD04U with CJ rack
Примечание: Still treated as Special I/O Unit under NJ system. Configuration software is Sysmac Studio, different from CX-Programmer for CJ. Some native CJ Special I/O instructions are unsupported.
✅ CP1H (Adapter required, cannot plug directly)
CP1H CPU has no native CJ backplane. Must use CP1W-EXT01 (CJ Unit Adapter). Maximum 2 CJ Special I/O Units (AD04U belongs to this category). CP1E/CP1L not supported.
❌ Incompatible
- CS1 Series (CS1G/CS1H): Different backplane bus, cannot be used directly
- CP1E, CP1L, цена за тысячу показов, CQM1, C200H: No support for CJ1W Special I/O modules at all
- NX-series PLC: NX uses dedicated NX-AD modules, cannot mount onto NX backplane
📌 Important Usage Notes
- Место установки: CPU rack or CJ expansion rack. Rotary switch on module front sets unit number (00~95). No duplicate Special I/O unit numbers.
- Программное обеспечение: CX-Programmer for CJ1/CJ2; Sysmac Studio for NJ
- Потребляемая мощность: DC5V, 320мА. Calculate backplane power capacity during selection.
- Max per system: До 40 CJ Special I/O Units (Limited by power supply and CPU capability)
- Steps to Configure CJ1W-AD04U in CX-Programmer (CJ1M / CJ2M / CJ2H / CJ1G)
Предварительное условие: Set hardware rotary unit number (00~95). No duplicates among Special I/O Units. Record this number for software setup.
- New Project & Select CPU Model
- Open CX-Programmer → New Project
- Device Type: CJ1M / CJ2M / CJ2H / CJ1G, select corresponding CPU
- OK to enter project workspace
- I/O Table and Unit Setup (Основной шаг)
- Double-click [I/O Table and Unit Settings] in project tree to open rack view
- Right-click empty rack slot → [Add Unit]
- Категория: General Analog I/O → CJ1W-AD04U, ХОРОШО
- Select AD04U unit, right-click [Unit Settings] to open module parameter window
⚠️ Unit number must match hardware rotary switch! Пример: hardware set to 0, software unit number =0
- Channel Parameter Configuration (Универсальный вход, independent per channel)
Each channel can independently select sensor type: Pt100/Pt1000/JPt100 / K/J/T/L/R/S/B thermocouple /4~~20mA /0~~10V etc.
Channel Enable: Check to activate unused channels; disable unused channels otherwise alarms easily triggered
Тип входа: Dropdown to select sensor/range
Temperature Unit: ℃ / ℉ (for temperature inputs)
Alarm Settings: Upper/lower limit, alarm delay 0~60s, гистерезис; enable open-wire detection
Zero/Span Calibration: Optional online calibration
Averaging Processing: Reduce signal fluctuation (необязательный)
Register Allocation Rule:
Unit No. Н:
ИТ-директор: Starts at `CIO 2000 + 100×N`
CH1 Measured Value: `2000+100N`
CH2 Measured Value: `2001`
CH3 Measured Value: `2002`
CH4 Measured Value: `2003`
Alarm flags and status bits in subsequent bits
DM Parameter Area: `D20000 + 100×N` stores channel type, range parameters
Пример: Unit No.=0
CH1 Value → CIO2000; CH2→CIO2001; CH3→CIO2002; CH4→CIO2003
- Download and Online Verification
- After parameter setup, [Transfer to PLC] (Download I/O table + special unit parameters together)
- Switch PLC to Monitor mode and watch CIO channel readings
- No ERR red light = basic configuration OK. ERR red light causes: mismatched unit number, insufficient backplane 5V, неверные параметры
Важное примечание: AD04U is a Special I/O Unit. Parameters download into PLC memory and auto-load to module on power-up. No initialization instructions required in user program.
- Restrictions for CP1H + CP1W-EXT01 + CJ1W-AD04U
Hardware architecture: CP1H CPU + CP1W-EXT01 Adapter + CJ Backplane + CJ1W-AD04U
✅ Permitted
- Maximum 2 CJ Special I/O Units (AD04U counts as Special I/O; combination: 1×AD04U + another CJ Special I/O)
- Only supports CJ Special I/O Units / CPU Bus Units; CJ basic I/O (CJ1W-ID/OD) cannot be mounted
- CX-Programmer configuration is nearly identical to CJ setup: Add AD04U in I/O table and set unit number
❌ Hard Limitations
- Max Quantity: 2 единицы, cannot add 3rd. Two AD04Us allowed but 5V backplane current budget must be validated (320mA per AD04U)
- Extension length: Only one segment of CJ base after EXT01; No further CJ expansion base or expansion cable cascading
- Partial advanced CJ Special I/O instructions unavailable; basic acquisition and alarm functions of AD04U work normally
- CP1H program capacity and CIO address space limited; avoid large unit numbers, рекомендуется 0, 1
- Источник питания: 5V power for CJ rack after EXT01 must have sufficient capacity. Two AD04Us draw total 640mA, reserve ≥30% margin accounting for base consumption
- CP1E / CP1L cannot use EXT01, only CP1H (XA/X models)
- Адрес: CIO and DM offset rules same as CJ, but CP1H CIO area limited, unit number ≤15 recommended
⚠️ Common Pitfalls
- Missing CJ1W-TER01 terminator at the end of EXT01 rack (supplied with adapter, I/O error if missing)
- Duplicate unit number on two modules → ERR red LED
- Wrong selection: Attempt to mount CJ1W-ID211 DI/DO basic unit after EXT01 → Not recognized
- Insufficient backplane 5V current: ERR flashes after power on, no measurement data
Simplified Debug Procedure for CP1H + AD04U
- Hardware wiring: Mount CP1W-EXT01 on CP1H side port → CJ base → AD04U, install CJ1W-TER01 terminator at rack end
- Set AD04U rotary unit number to 0 (или 1)
- New CP1H project in CX-Programmer, open I/O table, add CJ1W-AD04U under EXT01 expansion rack, match unit number to hardware
- Set 4-channel input types and download I/O table + параметры
- Online monitor CIO area to read temperature/analog signals
Engineering Application Cases of OMRON CJ1W-AD04U (Universal Analog Input Module)
Core advantages: Independent 4-channel setup, inter-channel isolation, mixed acquisition of Pt100/thermocouple/4~~20mA/0~~10V. Ideal for small reactors, стерилизаторы, heat exchange stations, очистка воды, ovens and other mixed-sensor process applications.
PLC Host: CJ2M / CJ1M / CJ1G; HMI options: NB/NS Touchscreen, CX-Supervisor SCADA
Случай1: Температура & Pressure Monitoring for Small Reactor (Typical AD04U Application in Chemical/Pharmaceutical)
Project Requirements
Reactor multi-signal acquisition:
CH1: Пт100 (Vessel temperature 0~~200℃, 3-wire RTD)
CH2: Термопара типа К (Jacket temperature 0~~400℃)
CH3: Pressure transmitter 4~~20mA (0~~1.0MPa)
CH4: Level transmitter 4~~20mA (0~~2m liquid level)
Функции: Limit alarm, open-wire detection, real-time HMI display, over-temperature interlock output via DO module.
Hardware Architecture
CJ2M-CPU13 + CJ1W-AD04U (Единица 0) + CJ1W-OD211 Digital Output + NB Touchscreen
AD04U handles mixed signals across four channels, eliminating separate temperature module and regular AI module to save rack slots.
Ключевые моменты настройки
- Add CJ1W-AD04U in CX-Programmer I/O Table; hardware rotary switch 00
- Channel setup
CH1: Пт100, open-wire detection enabled; linearization onboard, stored value ×10 (256.0℃→2560)
CH2: K thermocouple, built-in cold junction compensation
CH3: 4~~20mA, range 0~~1MPa
CH4: 4~~20mA, range 0~~2m
- Адрес (Единица 0)
CH1 Temperature: CIO2000; CH2: CIO2001; CH3 Pressure: CIO2002; CH4 Level: CIO2003
- Программа: SCL scaling, high/low limit comparison; channel open-wire bit triggers alarm, over-temperature triggers DO to cut heating.
Field Debugging Issues
Thermocouple shield cable single-end grounding. Ground loop and temperature fluctuation occur with both ends grounded;
Unequal resistance of three Pt100 wires leads to reading drift, keep three wires same length;
30-minute module warm-up before reaching rated accuracy.
Случай 2: Food Sterilizer (Steam Sterilization Equipment)
Требования
Multi-point temperature measurement inside chamber, monitor cavity temperature and steam pressure for pasteurization / high-temperature sterilization process logging.
CH1: Pt100 Chamber Temperature 0~~135℃
CH2: Pt100 Product Core Temperature
CH3: 4~~20mA Steam Pressure 0~0.4MPa
CH4: Reserved for cooling water K thermocouple
System Features
Sterilization site has heavy electrical interference, inter-channel isolation of AD04U delivers better noise immunity than non-isolated regular AI. Data uploaded to touchscreen to save process curves for food batch traceability.
Расширение: Add CJ1W-DA021 analog output module for PID temperature control to modulate steam regulating valve.
Случай 3: Heat Exchange Station (ОВК / District Heating Substation)
Требования
Primary supply temp, primary return temp, supply pressure, return pressure
CH1: Pt100 Primary Supply
CH2: Pt100 Primary Return
CH3: 4~~20mA Supply Pressure 0~~1.6MPa
CH4: 4~~20mA Return Pressure 0~~1.6MPa
ПЛК: CJ1M-CPU12; Remote SCADA, heat calculation, high/low pressure and overtemperature alarm.
Ключевые моменты
Sensors distributed over long wiring distances in heating stations. Built-in open-circuit detection alerts maintenance staff immediately on probe failure.
Случай 4: CP1H+CP1W-EXT01+CJ1W-AD04U Low-cost Water Tank Temperature & Level Monitoring
Аппаратное обеспечение
CP1H-X40DT-D + CP1W-EXT01 Adapter + CJ Base + CJ1W-AD04U + CJ1W-TER01 Terminator
Ограничение: Макс 2 CJ Special I/O Units; только 1 AD04U used here
Каналы:
CH1: 4~~20mA Liquid Level 0~~5m
CH2: Pt100 Water Temperature
CH3, CH4 Reserved
Приложение: Water purification / sewage tank, pump start-stop interlock by liquid level, сигнализация перегрева.
Примечание: No CJ basic DI/DO allowed after EXT01, only Special I/O; calculate 5V backplane consumption (320mA for AD04U).
Случай5: Oven / Heat Treatment Furnace Monitoring (K Thermocouple Dominant)
CH1/CH2 K thermocouple for multi-point furnace temperature; CH3 4~~20mA fan wind pressure; CH4 0~~10V speed potentiometer.
Suitable for small heat treatment and drying ovens. Supports thermocouple + Напряжение + current within single module, which is the biggest advantage of AD04U. Regular CJ1W-AD041 only handles 4~20mA/voltage and does not support RTD/thermocouple.
General Programming Guidelines for CJ1W-AD04U
- Температура (Pt100/Thermocouple): Onboard linearization, raw value = actual temperature ×10;
Пример: CIO2000=1250 → 125.0℃
- 4~20mA Raw Range: 4mA corresponds to 1/12000, 20mA corresponds to full scale; SCL instruction scales engineering value in PLC program
- Alarms: Module hardware provides per-channel high/low limit and open-wire bits in subsequent CIO bits, no need to write comparison logic for open-circuit detection.
Руководство по выбору (When to choose AD04U)
✅ Suitable: Mixed sensor types (Пт100, thermocouple plus 4~~20mA transmitters), inter-channel isolation required, ≤4 points
❌ Не подходит: Pure 4~~20mA acquisition with many points (CJ1W-AD081 recommended); high-speed sampling (CJ1W-PH41U recommended)
Summary of Common Faults in Field Commissioning
- ERR Red LED: Duplicate unit number, insufficient backplane 5V power, I/O table parameter not downloaded
- Jumpy temperature reading: Shield cable grounded at both ends, sensor cables routed together with power cables
- 4~20mA locked at 4mA: Transmitter loop open, 2-wire transmitter wiring error
- Pt100 reading drift: Unequal resistance among three wires
Контактор,автоматический выключатель,датчик,Кодер,ПЛК,Конвертер


























NH42-63-318x560.png)



