Пепперл+Фукс WE77/Ex-2 Installation & Руководство по проводке
WE77/Ex-2: Dual-channel NAMUR isolated switch amplifier (intrinsically safe barrier). Must be installed in safe-area control cabinet only. Blue terminals = intrinsically safe side (connect to field explosion-proof sensors). White/red terminals = non-intrinsically safe side (connect to ПЛК and power supply).
Название продукта: Isolated Intrinsically Safe Switch Amplifier
Примечание: WE77/Ex-2 is an obsolete legacy model. Recommended replacement for new projects: KFA6-SR2-Ex2
- Определение кода модели
WE77: Семейство продуктов, NAMUR switch amplifier
Ex: Intrinsically safe explosion-proof design
2: Dual-channel version (WE77/Ex-1 = single-channel)
Two power supply variants:
- WE77/Ex-2 115V: 115Питание переменного тока, В
- WE77/Ex-2 230V: 230В (220В) AC supply, most common in China
- Основные функции
Intrinsically safe isolated barrier for NAMUR sensors and dry contact mechanical switches located in hazardous areas. It isolates and transmits binary switch signals from hazardous area to control system in safe area. Equipped with LB Lead Breakage detection, supports reverse operation mode. Each channel has independent relay change-over contact output.
Field side: Intrinsically safe circuit EEx ia IIC, suitable for Zone0/1/2 hazardous locations
Control side: Passive relay dry contact output (non-intrinsically safe)
Supported inputs: NAMUR proximity sensors (EN60947-5-6), passive mechanical contacts
- Основные электрические характеристики
Intrinsically Safe Parameters (Полевая сторона)
U₀: 13.5 В Вашингтоне
I₀: 62 мА
P₀: 125 mW
Explosion group: МИБ / ИИК
Permitted external values: МИБ: Co=0.929µF, Lo=5mH; ИИК: Co=0.23µF, Lo=3mH
NAMUR Input
Open circuit voltage ≈8V DC, short-circuit current ≈8mA
Switching threshold: 1.2~2.1mA, гистерезис прибл..0.2мА
Lead breakage detection: Fault alarm upon cable disconnection
Релейный выход (1 SPDT change-over contact per channel)
Рейтинг контактов: 250V AC /4A; 24VDC/4A
Время ответа: Pull-in ≈10ms, Drop-out ≈20ms
Макс. частота переключения: <10Hz
Механическая жизнь: 10⁷ switching cycles
Источник питания
230Версия V: 198~253V AC, 45~65Hz; Power dissipation approx.2.5W
115Версия V: 103.5~126V AC, 45~65Hz
- Механический & Экологические данные
Измерение: 40(Вт) ×104(ЧАС) ×110(Д) мм
Масса: approx.410g
Монтаж: DIN rail clip mounting
Enclosure protection: IP20 (только для установки в шкаф)
Температура окружающей среды: -25℃ ~ +60 ℃
Терминалы: Винтовые клеммы
- Информация о сертификации
ATEX Certificate: PTB 02 АТЕХ 2065 / PTB Ex-79/2043X
Explosion marking: II (1) GD [EEx ia] ИИК
- Назначение терминала (WE77/Ex-2)
Channel1 field input: Терминал 1(-), 2(+)
Channel2 field input: Терминал 8(+), 9(-)
Channel1 relay output: 10/11/12 (change-over contact)
Channel2 relay output: 13/14/15 (change-over contact)
Источник питания: 17, 18
- Приложение
Химическая, фармацевтический, масло & gas hazardous locations: Signal isolation for NAMUR proximity sensors, explosion-proof limit switches, explosion-proof level switches. Relay signals are sent to PLC/DCS DI modules.
- Запчасти & Примечания по замене
- WE77/Ex-2 no longer recommended for new projects by manufacturer. Прямая замена: KFA6-SR2-Ex2 (dual-channel NAMUR safety barrier, релейный выход, equivalent function, smaller footprint)
- For maintenance of existing systems: Only surplus / stock spare parts available. Confirm 115V or 230V variant before procurement, the two versions are not interchangeable.
- Single-channel equivalent: WE77/Ex-1, replacement KFA6-SR1-Ex
- Распространенное устранение неполадок
- No input response: Check for LB lead breakage alarm on NAMUR loop; verify external capacitance/inductance does not exceed intrinsic safety limits
- Relay fails to switch: Confirm power supply variant matches device rating; verify input current falls within NAMUR operating range
- Frequent false lead breakage alarm: Excessive cable length with high distributed capacitance/inductance, or damaged cable insulation
- Механический монтаж
- DIN-рейка: Стандартный монтаж на DIN-рейку 35 мм.. Hook top clip onto rail, press module down to lock. Чтобы удалить: Lift bottom latch and pull outward.
- Операционная среда
Температура окружающей среды: -25℃ ~ +60 ℃, cabinet ventilation required; keep away from heat sources, vibration and corrosive gas
Класс защиты IP20, использовать только в шкафу внутри помещения, not for open or humid direct exposure
Mounting clearance: Small gaps between adjacent modules recommended for heat dissipation
- Mandatory Explosion Protection Rules
✅ Unit must be mounted in safe area, NEVER install in Zone0/1/2 hazardous areas
✅ Intrinsically safe cables (синий) and non-intrinsically safe cables (власть, релейный выход) must run in separate trunking/conduits, cannot share same conduit
- Terminal Table
| Terminal Group | Терминал №. | Описание | Circuit Classification |
| Channel1 Field NAMUR Input (Blue IS Terminals) | 1(-), 2(+) | Channel1: NAMUR proximity sensor / explosion-proof dry contact | Intrinsically safe EEx ia IIC |
| Channel2 Field NAMUR Input (Blue IS Terminals) | 8(+), 9(-) | Channel2: NAMUR proximity sensor / explosion-proof dry contact | Intrinsically safe EEx ia IIC |
| Channel1 Relay Change-over Output | 10, 11, 12 | 11 Общий, 10 НЗ нормально закрытый, 12 НЕТ Нормально открытый | Non-intrinsically safe relay |
| Channel2 Relay Change-over Output | 13, 14, 15 | 14 Общий, 13 НЗ нормально закрытый, 15 НЕТ Нормально открытый | Non-intrinsically safe relay |
| Источник питания | 17, 18 | Входная мощность переменного тока: Select 115V /230V variant, non-interchangeable | Non-intrinsically safe |
Важный: NAMUR field wiring is polarity sensitive. Reversed polarity will trigger LB lead breakage fault and unit malfunction.
- Wiring Schemes
Схема 1: NAMUR Proximity Sensor (Самый распространенный)
Channel1: 2-wire NAMUR sensor → Terminals 1(-), 2(+)
Channel2: 2-wire NAMUR sensor → Terminals 8(+), 9(-)
NAMUR loop includes LB lead breakage monitoring: Cable break, short circuit or reversed polarity will trigger channel fault LED.
Схема 2: Explosion-proof Passive Dry Contact (Концевой выключатель)
Dry contact directly connected to IS terminals, lead breakage detection remains active. No external supply for contact; WE77/Ex-2 provides approx.8V/8mA IS drive internally.
Relay Output Wiring (to PLC DI)
Each channel is SPDT passive change-over contact, no external supply required
Channel1: 11 Общий, 12 НЕТ, 10 Северная Каролина
Channel2: 14 Общий, 15 НЕТ, 13 Северная Каролина
Contact maximum rating: 250В и / 4А; 24VDC /4A. Do not overload to avoid contact burnout.
Силовая проводка
Терминалы 17 & 18 for AC supply:
WE77/Ex-2 230V version: AC 198~253V (Mainland China standard)
WE77/Ex-2 115V version: AC 103.5~126V
⚠️ Hardware differs between two power versions, НЕ взаимозаменяемы.
- Выбор кабеля (Explosion Compliance Mandatory)
- Intrinsically safe side (Blue terminals to field instrument): Blue IS cable recommended, conductor cross-section ≥0.5mm², rated voltage ≥500V
- Intrinsically safe loop must be verified for maximum permitted cable capacitance Co and inductance Lo:
IIC application: Co ≤0.23µF, Lo ≤3mH
IIB application: Co ≤0.929µF, Lo ≤5mH
Excessive cable length causes distributed capacitance/inductance over-limit, invalidating intrinsic safety certification.
- Экранированный кабель: Shield single-point earthed at control room end, shield floating at hazardous area side to prevent earth loop current.
- Wiring Procedure (Safety Sequence)
- Выключить питание! Isolate all power sources and confirm zero voltage before wiring
- Connect field intrinsically safe cables first (blue terminals), verify polarity
- Connect relay output cables to PLC DI modules
- Connect module power terminals 17 &18 последний
- Tighten all screw terminals, no loose strands or exposed copper causing short circuit
- Pre-power check: IS cables separated from power cables, no mixed routing
- Power-on commissioning: Power on without field load first and check channel LEDs. Connect field sensors, test switching action and LB fault function.
- ввод в эксплуатацию & Светодиодная индикация
Independent LED per channel: Illuminated when valid input signal present; LB lead breakage fault will extinguish LED / trigger fault alarm
Режим работы: Reversible mode available (relay de-energizes when input activates), configurable per project requirement
Lead breakage test: Disconnect field sensor wire, module shall detect line fault and activate LB alarm.
- Critical Prohibitions & Распространенные ловушки
- ❌ Megger insulation test is forbidden on intrinsically safe terminals! High voltage from megger will destroy internal IS circuit and permanently damage unit. Remove all IS wiring before any cable high voltage test.
- ❌ Never route 220V power cables or non-IS signal wires into blue intrinsically safe terminals; intrinsic safety protection will be destroyed.
- ❌ IS circuits and non-IS circuits cannot share same cable or trunking.
- ❌ Do not install WE77/Ex-2 in hazardous area.
- ❌ Do not exceed Co/Lo intrinsic safety limits, explosion certification will be invalid.
- ❌ Do not overload relay contacts; damaged relay contacts cannot be repaired separately, full module replacement required.
- Earthing Instruction
WE77/Ex-2 is transformer-isolated safety barrier; galvanic isolation between IS side and control side. Module housing connected to cabinet protective earth as standard, сопротивление земли ≤4 Ом. Isolated barrier does NOT require dedicated intrinsic safety earth like zener barriers.
- Post Power-On Quick Fault Diagnosis
- No LED illumination after power-up: Check voltage at terminal 17/18, confirm 115V/230V model match, check loose power terminals.
- Persistent LB fault alarm: ①NAMUR polarity reversed; ②broken cable; ③cable distributed capacitance/inductance over-limit; ④field sensor damaged.
- Sensor switches but relay does not toggle: Verify NAMUR current within operating range; check NO/NC contact selection.
- Unintended relay chattering/false switching: Power fluctuation, электромагнитные помехи. Use shielded cable and separate strong/weak signal wiring.
WE77/Ex-2 Intrinsically Safe Blue Terminals & Non-Intrinsically Safe Relay Terminal Current Parameters
Distinguish between intrinsic safety certified maximum short-circuit current Io (explosion parameter) and NAMUR normal operating current. Non-intrinsically safe side is relay contact rated current.
🔵 Blue Terminals: Intrinsically Safe Field Input Side
WE77/Ex-2 230V version (Mainland China mainstream)
- Intrinsic safety maximum short-circuit current Io = 62mA (certified explosion parameter. In short-circuit condition, module limits output current below this value to maintain explosion safety)
- NAMUR normal operating current: Open circuit ≈8V DC, static short-circuit current ≈8mA; Switching threshold 1.2~2.1mA per NAMUR standard
Note for 115V WE77/Ex-2 variant: Io=31mA. Always confirm power supply version during selection.
⚠️ Важно: 62mA is the safety limit short-circuit current, NOT normal working current. Under normal NAMUR sensor operation, loop current is only a few milliamps.
⚪ White Terminals: Non-intrinsically Safe Relay Output (Терминалы 10/11/12,13/14/15)
SPDT change-over contact rated load current (резистивная нагрузка) per channel
250 В переменного тока: 4А (cosφ>0.7)
24 В постоянного тока: 4А
DC 60V: 0.6А
220 В постоянного тока: 0.1А
Max contact power rating: 500Вирджиния; Overload will cause contact erosion, module non-repairable.
Дополнительный: Module Power Terminals (17,18)
Total power dissipation approx.2.5W. For 230V AC supply, power loop current is low, приблизительно.0.01А.
Summary Table
| Terminal Group | Элемент | Ценить | Примечания |
| Blue IS Terminals (230V model) | Intrinsic safety limit short-circuit current Io | 62мА | Explosion protection short-circuit limit |
| Blue IS Terminals | NAMUR normal short-circuit current | ≈8mA | NAMUR sensor operating current |
| White Non-IS Relay Contacts | Rated current at AC250V / 24 В постоянного тока | 4А | резистивная нагрузка, independent per channel |