Siemens 3TL6113-0BM4

Product: 3TL61 series 7.2 kV medium-voltage vacuum contactor (legacy imported unit, discontinued)

3TL61: 7.2 kV voltage class; 3TL65: 12 kV voltage class. The 3TL platform is an older-generation vacuum contactor manufactured in Berlin. Its successor series is the 3TM.

Model Decoding: 3TL6113-0BM4

3TL61: 7.2 kV vacuum contactor base series

13: 3-pole, rated operating current 250 A

0: Standard version, no mechanical latching

B: Coil control voltage AC 24 V

M4: Auxiliary contact configuration: 4NO + 4NC positively-driven auxiliary switch

Key Electrical Specifications

ItemParameter
Rated operating voltage Ue7.2 kV
Rated operating current Ie250 A
Number of poles3‑pole
Frequency50‑60 Hz
Coil voltageAC 24 V
Closing power600 W, holding power 90 W (with economy holding resistor)
Mechanical endurance3 million operations
Vacuum interrupter electrical endurance2 million operations
Maximum operating frequency1200 operations per hour
Auxiliary contacts4NO + 4NC, positively‑driven
Power‑frequency withstand voltage (phase‑to‑ground / phase‑to‑phase)32 kV, 1 min
Lightning impulse withstand voltage60 kV

Typical Applications

Switching of high-voltage motors, capacitor banks, transformers and reactors; contactor-fuse combination (FC-circuit) inside KYN28, XGN switchgear cubicles.

Replacement Options

  1. Siemens original successor: 3TM3313-0BB40

(7.2 kV-250 A, AC 24 V coil, 4NO+4NC auxiliary contacts, functional drop-in replacement. Cabinet cut-out dimensions require verification.)

  1. Spare part order numbers:

Vacuum interrupter: 3TY5652-0AA00

Operating coil: 3TY5651-0AB00

Economy holding resistor: 3TY5664-0AA00

Maintenance Notes

When procuring spare parts for legacy units, always verify the complete type designation plus serial number from the nameplate; do not rely solely on the order number.

The 3TL61 series uses an economy holding resistor for the coil. Do not remove it during servicing.

Main-circuit resistance shall be ≤ 280 μΩ; measurement is mandatory during overhaul.

The auxiliary switch is positively-driven. Do not substitute with standard auxiliary contacts.