(MN Type 125VDC Undervoltage Release)
Schneider LV429413 is an MN series undervoltage release specially designed for molded case circuit breakers of the Compact NSX, PowerPact Multistandard, and EasyPact CVS series. It has a rated voltage of 125VDC and uses screwless spring terminals. It is used for emergency stop or remote tripping control. When the control voltage drops below 35% ของค่าพิกัด, it automatically trips the circuit breaker to ensure system safety.
- Model Code Interpretation
| ส่วนรหัส | ความหมาย |
| LV | Prefix for Schneider low-voltage power distribution products |
| 4294 | Product category identifier for undervoltage releases |
| 13 | Specific specification code corresponding to 125VDC rating, MN type, screwless terminals |
| MN | Product type code: การปล่อยแรงดันตก; MX denotes Shunt Trip |
Core Features: 125VDC operating voltage, suitable for 100-630A molded case circuit breakers, non-delay type, tripping threshold at 35% ของแรงดันไฟฟ้าที่กำหนด.
- พารามิเตอร์ทางเทคนิคหลัก
| รายการ | ข้อมูลจำเพาะ |
| ประเภทสินค้า | MN Type Undervoltage Release |
| Rated Control Voltage | 125กระแสตรง (not for AC systems) |
| Tripping Threshold | ≤ 35% ของแรงดันไฟฟ้าที่กำหนด (ประมาณ. 43.75กระแสตรง) |
| Reset Voltage | ≥ 85% ของแรงดันไฟฟ้าที่กำหนด (ประมาณ. 106.25กระแสตรง) |
| ประเภทเทอร์มินัล | Screwless Spring Terminal |
| Compatible Breaker Series | Compact NSX 100–630A, PowerPact Multistandard, EasyPact CVS |
| ตำแหน่งการติดตั้ง | Accessory slot on front of circuit breaker |
| Wire Capacity | 1.5–2.5mm² cable |
| การป้องกันทางเข้า | IP20 (when installed) |
| อุณหภูมิในการทำงาน | -25°C ~ +70°C |
| น้ำหนัก | ประมาณ. 50ก |
| การรับรอง | ไออีซี 60947-2, แอล 489, CSA C22.2 No. 5 |
- Application Environment
- System Types
Industrial automation control systems, data center UPS systems
DC power supply systems, emergency stop circuits
Remote monitoring and tripping applications
- สภาพการทำงาน
Control voltage fluctuation: 85%-110% of rated value for stable operation
EMC performance: สอดคล้องกับ IEC 61000-4
Compatible frame sizes: 100ก, 160ก, 250ก, 400ก, 630ก (NSX series)
- ข้อกำหนดในการติดตั้ง
Must be installed in dedicated front accessory slot with reliable mechanical interlock
Control circuit to be protected by 1A fuse to prevent coil damage from short circuit
Observe polarity: “+” for positive, “-” for negative
- Cross-Reference & Replacement Models
| Replacement Type | แบบอย่าง | ยี่ห้อ | คำอธิบาย |
| Direct Replacement | LV429414 | ชไนเดอร์ | 220VAC version for AC control circuits |
| Equivalent Function | S29413 | ชไนเดอร์ (Square D) | 125VDC undervoltage release for PowerPact series |
| Cross鈥態rand Alternative | ABB TA250-125DC | เอบีบี | 125VDC undervoltage release for Tmax MCCBs |
| Domestic Alternative | CHINT NXB-MN/125DC | CHINT | For NXB series MCCBs |
- ข้อมูลการสั่งซื้ออย่างเป็นทางการ
| รายการ | รายละเอียด |
| รุ่นอย่างเป็นทางการ | LV429413 (global part number) |
| Product Name | Undervoltage Release MN, Compact NSX, 125กระแสตรง, Screwless Terminal |
| Order Note | Must match corresponding breaker model, เช่น, NSX100N, NSX250F |
| Packing | Individual package including release body, manual, mounting screws |
| รหัส EAN | 3606480019029 |
| ขั้นต่ำ | 1 piece |
- Engineering Implementation
- การตรวจสอบความเข้ากันได้
Confirm breaker model: only for Compact NSX (100-630ก), PowerPact Multistandard, EasyPact CVS
Verify control voltage: strictly 125VDC, not for AC or other DC voltages
Ensure front slot available for MN/MX accessories
- ขั้นตอนการติดตั้ง
- Disconnect main and control power to the breaker
- Remove front accessory cover
- Insert undervoltage release into slot and engage mechanical interlock
- Secure with supplied screws
- Wire 125VDC with correct polarity
- Refit cover and perform functional test
- Commissioning
Trip test: reduce voltage below 43VDC; breaker must trip automatically
Reset test: restore voltage above 106VDC; breaker should close normally
Interlock check: breaker cannot be manually closed when release is activated until voltage recovers
- Complete Model List (MN Series Undervoltage Releases)
| แบบอย่าง | แรงดันไฟฟ้าที่ได้รับการจัดอันดับ | ประเภทเทอร์มินัล | Compatible Series | หมายเหตุ |
| LV429400 | 24VAC/ดีซี | Screw Terminal | NSX/CVS | มาตรฐาน |
| LV429401 | 48VAC/ดีซี | Screw Terminal | NSX/CVS | มาตรฐาน |
| LV429402 | 110VAC/ดีซี | Screw Terminal | NSX/CVS | มาตรฐาน |
| LV429403 | 220VAC/ดีซี | Screw Terminal | NSX/CVS | มาตรฐาน |
| LV429410 | 24กระแสตรง | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429411 | 48กระแสตรง | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429412 | 110กระแสตรง | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429413 | 125กระแสตรง | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429414 | 220VAC | Screwless Terminal | NSX/CVS | Spring Terminal |
| LV429415 | 230VAC | Screwless Terminal | NSX/CVS | Spring Terminal |
- Risks & Warnings
- การจับคู่แรงดันไฟฟ้า: This model is only for 125VDC control circuits. Applying AC or incorrect DC voltage will burn the coil and damage the unit.
- Polarity: DC polarity must be observed; reversed connection causes failure or circuit damage.
- การป้องกันกระแสเกิน: Install 1A fast-acting fuse in control circuit to protect coil.
- Mechanical Interlock: Ensure reliable engagement; มิฉะนั้น, false tripping or failure to trip may occur.
- Ambient Limits: Do not use above +70°C or below -25°C to avoid performance degradation.
- การซ่อมบำรุง: Regularly check control voltage stability (85%-110% of rated) to prevent excessive mechanical wear from frequent undervoltage tripping.
คอนแทคเตอร์,เบรกเกอร์,อินเวอร์เตอร์พลังงานแสงอาทิตย์,มิเตอร์ไฟฟ้า,แบตเตอรี่พลังงานแสงอาทิตย์