Modell:AU3048B
Official Classification:Display Operation Panel (Ersatzteil)
Compatible Device:ABB TTF300 Series Field-Mount Temperature Transmitter, Built-in Circular Display Module
⚠️ Important Note: Misleading information online. AU3048B is NOT a MOSFET, it is an LCD display unit dedicated for temperature transmitters.
Funktionen
- Circular embedded structure, installed directly inside the housing of TTF300 transmitter
- Equipped with LCD screen + 4 push-buttons
- Funktionen: On-site reading of temperature measurement values, Parameterkonfiguration, zero calibration, fault code retrieval
- Kommunikation: Connected to transmitter mainboard via internal bus; no external terminals
Key Information
Standard Order Description: AU3048B, Display for TTF300
Anwendung: Field replacement spare part; used when original panel blackouts or buttons fail
Kompatibilität: Only fits ABB TTF300. Not interchangeable with FEP, FXE, Deltapilot and other instrument series
Supply Note: Original OEM spare part; no domestic compatible alternatives available
Typical Fault Symptoms (Display Unit Failure)
LCD no backlight / black screen, while transmitter 4–20mA output remains normal
Buttons unresponsive; unable to access parameter menu
Screen distortion, incomplete character display
Procurement Verification Suggestion
Confirm transmitter model marked on nameplate is TTF300 before ordering.
Do not place orders if the model does not match; interface and communication protocol are incompatible.
Complete Technical Specification Document for ABB AU3048B
⚠️ Important Clarification: Multiple online sources mistakenly label AU3048B as power MOSFET.
AU3048B is original ABB spare part, vollständiger Name: Display Unit AU3048B, Type B LCD Operation Display for TTF300 Temperature Transmitter
- Basic Part Information
- Modell: AU3048B
- Official Description: Display for TTF300 (LCD Operation Display Unit Type B for TTF300 Transmitter)
- Produktkategorie: ABB Measurement Instrument Spare Parts
- Compatible Host: Only compatible with ABB TTF300 / TTF300-N Field-Mount Temperature Transmitter
❌ Incompatible with TTF200, FEP, FXE, Deltapilot and other instrument series
- Standard English Order Description (can be sent directly to suppliers)
`AU3048B, LCD Display Module Type B for TTF300 Transmitter`
- Country of Origin: China / Italien (depends on production batch)
- Mindestbestellmenge: 1 Stück
- Elektrisch & Interface Specifications
- Stromversorgung: No independent external power supply; powered via internal backplane bus from TTF300 transmitter
- Schnittstelle: Dedicated board-to-board straight connector; no external wiring terminals
- Kommunikationsprotokoll: Proprietary internal serial bus; NOT HART / RS485. Cannot operate standalone
- Stromverbrauch: Powered by host transmitter; typical additional power consumption <3mW
- Anzeige & Keypad Specifications
- Anzeigetyp: Segment LCD with backlight
- Display Capability
Numeric: 4 digits plus sign symbol, bis zu 2 decimal places
Extra elements: Bar graph, alarm status indicators, sensor diagnostic codes
Viewable data: Sensor 1 / Sensor 2 readings, electronics housing temperature, 4–20mA output percentage, fault diagnostic messages
- Keypad Layout: 4 membrane keys (UP, DOWN, EINGEBEN, ESC)
- Operation Rights: Local parameter configuration, zero trimming, fault code reading, display page switching
- Umweltspezifikationen (compliant with TTF300 transmitter specifications)
| Parameter | Bewertung |
| Betriebstemperatur (panel in service) | -40 ℃ … +70 ℃ |
| Lagerung / Transporttemperatur | -50 ℃ … +85 ℃ |
| Relative Luftfeuchtigkeit | 5%~95% RH, nicht kondensierend |
| Vibrationsfestigkeit | IEC60068-2-6; 10–60 Hz 0.21 mm; 60–2000 Hz 3g |
| EMV-Konformität | IEC/EN 61326-1 Industrial Environment |
Explosion Protection Remark: The display module itself carries no Ex certification. Overall explosion protection rating depends on the complete TTF300 transmitter certificate (ATEX / IECEx).
- Mechanische Abmessungen & Konstruktion
- Gliederung: Circular embedded module, matching circular installation cavity of TTF300 transmitter housing
- Gehäusematerial: Flame-retardant ABS plastic
- Montagemethode: Snap-fit installation by pushing into transmitter housing; Keine Schrauben erforderlich
- Schutz vor Eindringen: Front face achieves IP66/IP67 together with transmitter enclosure; bare PCB module rated IP20
- Nettogewicht: Ca. 45 G
- Supported Functions List
- Cyclic display of dual temperature sensor values (dual Pt100 transmitter models)
- Sensor drift monitoring and sensor redundancy status indication
- NE107 standard diagnostic information; sensor open-circuit / short-circuit alarm codes
- Display of transmitter 4–20mA output value and output percentage
- Local basic configuration: engineering unit setup, damping, high/low alarm limits
- On-site fault code reading without configuration software
- Fault Identification Criteria (AU3048B hardware failure)
- LCD blackout, no backlight; transmitter 4–20mA analog output works normally
- Screen distortion, missing characters
- All buttons non-functional, cannot enter configuration menu
✅ Differentiation Tip: Transmitter mainboard failure may also cause black screen. Check transmitter power supply and internal connector tightness before replacing display unit.
- Critical Compatibility Restrictions
- AU3048B ≠ AU3048A: Type A and Type B differ in firmware and pin assignment; not interchangeable
- Only supports TTF300 hardware version ≥ HW 02.00.02; older hardware versions cannot recognize new display modules
- Cannot be powered on and tested separately. Must be installed inside TTF300 transmitter for activation.
- Ersatzinformationen
No third-party domestic compatible substitutes; only original AU3048B spare part available
If local operation is unnecessary for TTF300 transmitter, the display can be removed and replaced with blank cover spare part
Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien