Honeywell Searchpoint Optima Plus (2108N4000H) Fehler & Warning Troubleshooting Table
Reading methods: HIRSCH 475/375 Communicator, SHC1 Handheld Interrogator, EDD Device Description File; W=Warning, F=Fault. Under fault condition, output defaults to 0mA (this HART version can be set to 1mA). Some faults are latched and require manual clearing or power cycle reset.
| Error Code | Status | Englischer Name | Fehlerbeschreibung | On-site Troubleshooting Steps | Latched |
| 0 | W / F | Temperature Limit Exceeded | Operating temperature near or out of -40~+65℃ range | 1. Measure ambient temperature of the detector | NEIN |
| 2. Check direct sunlight or overheating from heat tracing | |||||
| 3. Belüftung verbessern & shading; relocate if over-temperature | |||||
| 4 | W / F | Bad 24V Supply | Supply voltage outside 18~32VDC operating range | 1. Klemmenspannung unter Last messen (not no-load power supply) | NEIN |
| 2. Check cable voltage drop, Kurzschluss und Drahtstärke | |||||
| 3. Überprüfen Sie die Stromkapazität und starten Sie die Schleife neu | |||||
| 5 | W / F | Fehlerhafte 4-20-mA-Schleife | Abweichung des Analogausgangs >0.5mA, kann kein korrektes Signal ausgeben | 1. Polarität prüfen, Abschirmung, Erdung und Schleifenwiderstand | ✅ Verriegelt |
| 2. Vermeiden Sie das Hot-Plugging von Multimetersonden | |||||
| 3. Aus- und wieder einschalten; wenn der Fehler bestehen bleibt, Der Ausgangskreis ist beschädigt | |||||
| 6 | W / F | Negativer Gaswert | Negative Nulldrift des Gasmesswerts | 1. Bestätigen Sie eine saubere Atmosphäre ohne Kohlenwasserstoffgas | NEIN |
| 2. Staubfilter entfernen und optisches Fenster reinigen | |||||
| 3. Führen Sie eine Nullkalibrierung durch; Beseitigen Sie Kondensation und Lösungsmittelstörungen | |||||
| 8 | W / F | Verdeckte Optik (Optische Verschmutzung) | Linse & Gaskammer durch Öl verstopft, Staub oder Wasserdampf, optische Wegdämpfung | 1. Wetterschutz und Staubschutz entfernen | NEIN (häufige Warnung) |
| 2. Wischen Sie das optische Fenster mit Linsenpapier und wasserfreiem Ethanol ab | |||||
| 3. Trocknen und zurücksetzen; Bei starker Kondensation die Heizfunktion prüfen | |||||
| 11 | W / F | Geringe Lampenleistung | Die Leistung der Infrarotlampe ist beeinträchtigt, Altern am Lebensende | 1. Reinigen Sie zunächst die Optik, um Verunreinigungen auszuschließen | NEIN |
| 2. Wenn der Alarm nach dem Zurücksetzen weiterhin besteht: Ersetzen Sie das optische Modul aufgrund eines Lampenfehlers | |||||
| 13 | F | Hardwarefehler | Selbsttestfehler der Hauptplatine und des Antriebsschaltkreises | 1. Ausschalten für 5 Minuten, dann erneut einschalten | ✅ Verriegelt |
| 2. Stromversorgung stabilisieren | |||||
| 3. Wiederkehrender Fehler: Senden Sie den Sender zur Reparatur ein oder ersetzen Sie ihn | |||||
| 16 | F | Schlechte Signalqualität | Laut, Instabiles Infrarotsignal mit niedrigem SNR | 1. Reinigen Sie zuerst das optische Fenster und den Filter | ✅ Verriegelt |
| 2. Überprüfen Sie, ob in der Gaskammer Wasser oder Frost eindringt | |||||
| 3. Ersetzen Sie die optische Baugruppe, wenn eine Alterung der Lampe oder ein optischer Versatz auftritt | |||||
| 22 | W / F | Interner Firmware-Fehler | Firmware-Prüfsummenfehler, Speicherausnahme | 1. Neustart mit vollständigem Ein- und Ausschalten | ✅ Verriegelt |
| 2. Fehlerprotokoll über HART-Tool löschen | |||||
| 3. Anhaltender Fehler: Firmware neu flashen oder Hauptplatine austauschen |
📌 Häufige allgemeine Fehler (Keine unabhängige Fehler-ID in HART)
- HART-Kommunikationsfehler
Überprüfen: 250In der Schleife muss ein Ω-HART-Widerstand installiert sein; richtige Polarität; einseitige Schirmerdung; keine übermäßige Anzahl von Nicht-HART-Geräten am Bus; passende Baudrate.
- Langsame Lesedrift ohne Fehlercode
Überprüfen: überfällige Kalibrierung; verstopfter Staubfilter; Kontinuierliche Störungen durch Kohlenwasserstoffe in geringem Konzentrationsbereich; Schweröladsorption in der Gaszelle.
- Keine Stromausgabe & Keine Kommunikation nach dem Einschalten
Überprüfen: Wassereintritt & Klemmenkorrosion im M25-Anschlusskasten; Durchgebrannter Stromkreis wegen Verpolung; Interne Sicherung durchgebrannt.
🛠️ Betriebsrichtlinien (für 2108N4000H)
- Verriegelte Fehler löschen: HART-Menü →【Fehler/Warnung】→Löschen; oder ≥30 Sekunden ausschalten und dann neu starten. Hardwarefehler treten unmittelbar nach dem Zurücksetzen erneut auf; Maskieren Sie sie nicht dauerhaft.
- Kalibrierungsvoraussetzung: Machen Sie den gesamten optischen Pfad frei & Lampenwarnungen vor der Nullpunkt-/Spannungskalibrierung; Bei aktiver Optik-Kontaminationswarnung wird die Kalibrierung stark abweichen.
- Ersatzteilabteilung: Fehler 8,11,16 = optisches Modul (Lampe + Detektor + Linse); Fehler 5,13,22 = Hauptplatinenfehler. Eine Reparatur auf Platinenebene wird nicht empfohlen; Ersetzen Sie den gesamten Sender direkt.
- SIL2-Erinnerung: Fehler der F-Klasse lösen eine SIL-Sicherheitsschleifenaktion aus. Betreiben Sie den Detektor nicht über einen längeren Zeitraum mit maskiertem Fehler; zeitnah Abhilfe schaffen.
(Searchpoint Optima Plus)
Produktposition: Punktförmiger NDIR-Kohlenwasserstoffbrennstoff Gasdetektor, HART-Protokollversion
Hergestellt von Honeywell Analytics UK. NDIR-Infrarotprinzip, immun gegen katalytische Perlenvergiftung. Ideal für Offshore-Plattformen, Raffinerien, LNG und andere raue Umgebungen; Sicherheitsintegritätsstufe SIL2.
✅ Modellcodierungsdefinition
2108: Searchpoint Optima Plus-Serie
N: Kohlenwasserstoff-HC-Version (Methan, Propan, Benzin usw., Ihr Modell)
4: Standard-Diffusionstyp mit Wetterschutz
000: Ohne Ferngaszelle & Probenahmepfad
H: HIRSCH 7 Protokoll überlagert mit 4-20-mA-Signal (Suffix N = reines 4-20mA ohne HART, z.B. 2108N4100N)
Faden: M25 (unterscheidet sich von der 41xx-Serie mit 3/4″NPT-Gewinde)
Standardkonfiguration: 316L Gehäuse aus elektropoliertem Edelstahl, Staubfilter, nylon weatherproof cover, sunshade against rain splash.
📌 Wichtige technische Spezifikationen
| Artikel | Parameter |
| Erkennungsprinzip | Non-Dispersive Infrared (NDIR) |
| Messbereich | 0~100%LEL; configurable for hundreds of hydrocarbons & solvents (Methan, Propan, ethylene, Benzin, aromatics) |
| Stromversorgung | DC18~32V, nominal 24 VDC; max power consumption <4.5W |
| Signalausgang | 4-20mA + HART7; Modbus RS485 multi-drop bus available with optional DX100(M) Modul |
| Current Levels (Fault/Inhibit/Alarm) | Fehler: 0mA (HART version configurable to 1mA); Inhibit: default 2mA; Warnung: default 3mA; Over-range: 20~21.5mA (default 21mA) |
| Ansprechzeit (Methane) | T50<3s, T90<4s |
| Betriebstemperatur | -40℃ ~ +65℃ |
| Schutz vor Eindringen | IP66 / IP67 |
| Gehäusematerial | 316 Edelstahl (CF8M); total weight approx. 1.6kg |
| Sicherheitszertifizierungen | ATEX, IECEx, FM, CSA; SIL2 (IEC61508) |
| Genauigkeit | Baseline drift <±1%FSD (HC); <±2%FSD (ethylene) |
| Pressure Effect | 0.1% reading per mbar |
✨ Infrared vs Catalytic Bead Advantages
- Resistant to catalytic poisons (Silikon, lead, H₂S), longer service life and extended maintenance interval
- Fail-safe optical self-test; no silent failure risk
- Works normally in inert atmosphere (catalytic sensors require oxygen)
- Built-in temperature control heating; anti-condensation optical window; Vorwarnung vor Linsenverschmutzung
- Integriertes Ereignisprotokoll; Unterstützung des HART-Kommunikators für die Inbetriebnahme, Kalibrierung und Diagnose
🧾 Typische Anwendungsszenarien
Offshore-Öl & Gasplattformen, FPSO, Öltanker, Raffinerien, LNG/LPG-Tankstellen, Gasreglerstationen, Gasturbinenkraftwerke, Lösungsmittelbeschichtung & Druckwerkstätten, Tanklager.
📎 Modellübergreifende Referenz (zum Ersatz & Auswahl)
2108N4000H: M25-Gewinde, HIRSCH, Diffusionstyp mit Wetterschutz (Ihre Einheit)
2108N4100N: 3/4″NVV, reine 4-20mA, kein HART
2108N4100H: 3/4″NVV, HART-Version
2108N5100H: Durchfluss-Probenahmetyp mit HART, für Pipeline-Probenahmesysteme
⚠️ Wichtige Hinweise
- Der Infrarotdetektor reagiert nur auf Kohlenwasserstoffe; kann keine brennbaren Gase, die keine Kohlenwasserstoffe sind, wie z. B. H₂, erkennen, CO, NH₃.
- Das Kalibriergas muss mit dem Zielgas übereinstimmen; Der Reaktionsfaktor variiert für verschiedene Kohlenwasserstoffe.
- Katalytische Perlensensoren können nicht direkt ausgetauscht werden, ohne die Host-Logik und die Alarmschwellen erneut zu überprüfen.
- Verbrauchsmaterialien: optisches Modul, dust filter and weather shield are regular wear items.
Honeywell Searchpoint Optima Plus (2108 Serie) Vollständige Modellliste
- Modellcodierungsregeln
2108N: Standard Hydrocarbon (HC) Version (Methan, Propan, Benzin usw.)
2108B: Ethylene & solvent dedicated version (ethylene, aromatics, esters)
4Ziffer: 4 = Diffusion type; 5 = Flow-through sampling type (with gas cell)
Thread code: 0 = M25; 1 = 3/4″NVV
Suffix: N = 4-20mA only; H = 4-20mA + HART7 protocol
Suffix 10 = with Remote Gas Cell (RGC); 00 = without remote gas cell
- 2108N Hydrocarbon Standard Models (Hauptserie, including 2108N4000H)
2.1 M25-Gewinde (0) | Diffusion (4) | No RGC (00)
- 2108N4000N: 4-20mA, M25, diffusion, weather shield
- 2108N4000H: 4-20mA+HART, M25, diffusion (Ihr Modell)
- 2108N4001N: Ethylene calibrated, M25, diffusion, 4-20mA
- 2108N4001H: Ethylene calibrated, M25, diffusion, HIRSCH
- 2108N4010N: HC + RGC remote test cell, M25, diffusion
- 2108N4010H: HC + RGC, M25, diffusion, HIRSCH
2.2 3/4″NPT-Gewinde (1) | Diffusion (4) | No RGC (00)
- 2108N4100N: 4-20mA, NVV, diffusion
- 2108N4100H: 4-20mA+HART, NVV, diffusion
- 2108N4110N: With RGC, NVV, diffusion
- 2108N4110H: With RGC, NVV, diffusion + HIRSCH
2.3 Flow-through sampling type (5) for sampling pipeline & pre-treatment systems
M25-Gewinde (0)
- 2108N5000N: Flow gas cell, M25, 4-20mA
- 2108N5000H: Flow gas cell, M25, HIRSCH
- 2108N5010N: Flow type + RGC, M25
- 2108N5010H: Flow type + RGC, M25 + HIRSCH
3/4″NPT-Gewinde (1)
- 2108N5100N: Flow gas cell, NVV, 4-20mA
- 2108N5100H: Flow gas cell, NVV, HIRSCH
- 2108N5110N: Flow type + RGC, NVV, high concentration range (0~100%vol CH₄)
- 2108N5110H: Flow type + RGC, NVV + HIRSCH
2.4 Special XTC Marine & Multi-certified Models (44/46/48 Serie)
- 2108N4400N / H: Diffusion, Marine-Zertifizierung, M25
- 2108N4600N / H: Diffusion, UL/FM certified, M25
- 2108N4601N / H: Ethylene calibrated, 46-type diffusion
- 2108N4800N / H: Optima Plus XTC version, M25 diffusion
- 2108N5400/5600/5800 N/H: Corresponding flow-through versions (44/46/48 sampling models)
- 2108B Ethylene & Lösungsmittelspezifische Modelle (für Optima X/Z Probenahmesysteme)
Diffusionstyp (4)
- 2108B4001N / H: Ethylene calibrated, M25 diffusion
- 2108B4101N / H: Ethylene calibrated, NPT-Diffusion
Flow-through sampling type (5, Nur für Probenahmesysteme)
- 2108B5001N / H: Ethylen-Durchflusszelle, M25
- 2108B5101N / H: Ethylen-Durchflusszelle, NVV
- 2108B2001N / H: Schnell reagierendes Probenahmemodell Optima X (spezielle Brennstoffzelle)
- 2108B2051N: DNV-Marine-zertifizierte Version
- Ersatzteil-Bestellcodes für die komplette Serie
- Optisches Modul: 2108D3001 (Methane), 2108D3034 (Ethylene)
- Ferngesteuerte Gaszelle (RGC): 2108B0240
- Durchfluss-Gaszellenbaugruppe: 2108B0282
- Staubfilter + Wetterschild: 2108B2337
- Terminal & Anschlussdose: 2108B2360
- Schnellauswahltabelle (zum Ersatz)
| Montageart | Faden | Ohne RGC (Standard) | With RGC (Ferntest) |
| Wandmontierte Diffusion | M25 | 2108N4000N / H | 2108N4010N / H |
| Wandmontierte Diffusion | 3/4″NVV | 2108N4100N / H | 2108N4110N / H |
| Pipeline-Probenahme | M25 | 2108N5000N / H | 2108N5010N / H |
| Pipeline-Probenahme | 3/4″NVV | 2108N5100N / H | 2108N5110N / H |
- Ergänzende Bemerkungen
- N = nur 4-20 mA analog; H = HART aktiviert. Mischen Sie keine Loop-Typen; 250Für HART-Schleifen ist ein Ω-Widerstand zwingend erforderlich.
- 2108N erkennt nur Kohlenwasserstoffe; 2108B ist für Ethylen bestimmt, Ester und Alkohole. Keiner von beiden kann H₂ erkennen, CO oder NH₃.
- Alle Modelle erfüllen SIL2, ATEX/IECEx/FM-Zertifizierung; Schutzart IP67.