Honeywell 2108N4000H Detektor für brennbare Gase

Honeywell Searchpoint Optima Plus (2108N4000H) Fehler & Warning Troubleshooting Table Reading methods: HIRSCH 475/375 Communicator, SHC1 Handheld Interrogator, EDD Device Description File; W=Warning, F=Fault. Under fault condition, output defaults to 0mA (this HART version can be set to 1mA). Some faults are latched and require manual clearing or power cycle reset. Error Code Status English ...

  • Produktdetails

Honeywell Searchpoint Optima Plus (2108N4000H) Fehler & Warning Troubleshooting Table

Reading methods: HIRSCH 475/375 Communicator, SHC1 Handheld Interrogator, EDD Device Description File; W=Warning, F=Fault. Under fault condition, output defaults to 0mA (this HART version can be set to 1mA). Some faults are latched and require manual clearing or power cycle reset.

Error CodeStatusEnglischer NameFehlerbeschreibungOn-site Troubleshooting StepsLatched
0W / FTemperature Limit ExceededOperating temperature near or out of -40~+65℃ range1. Measure ambient temperature of the detectorNEIN
2. Check direct sunlight or overheating from heat tracing
3. Belüftung verbessern & shading; relocate if over-temperature
4W / FBad 24V SupplySupply voltage outside 18~32VDC operating range1. Klemmenspannung unter Last messen (not no-load power supply)NEIN
2. Check cable voltage drop, Kurzschluss und Drahtstärke
3. Überprüfen Sie die Stromkapazität und starten Sie die Schleife neu
5W / FFehlerhafte 4-20-mA-SchleifeAbweichung des Analogausgangs >0.5mA, kann kein korrektes Signal ausgeben1. Polarität prüfen, Abschirmung, Erdung und Schleifenwiderstand✅ Verriegelt
2. Vermeiden Sie das Hot-Plugging von Multimetersonden
3. Aus- und wieder einschalten; wenn der Fehler bestehen bleibt, Der Ausgangskreis ist beschädigt
6W / FNegativer GaswertNegative Nulldrift des Gasmesswerts1. Bestätigen Sie eine saubere Atmosphäre ohne KohlenwasserstoffgasNEIN
2. Staubfilter entfernen und optisches Fenster reinigen
3. Führen Sie eine Nullkalibrierung durch; Beseitigen Sie Kondensation und Lösungsmittelstörungen
8W / FVerdeckte Optik (Optische Verschmutzung)Linse & Gaskammer durch Öl verstopft, Staub oder Wasserdampf, optische Wegdämpfung1. Wetterschutz und Staubschutz entfernenNEIN (häufige Warnung)
2. Wischen Sie das optische Fenster mit Linsenpapier und wasserfreiem Ethanol ab
3. Trocknen und zurücksetzen; Bei starker Kondensation die Heizfunktion prüfen
11W / FGeringe LampenleistungDie Leistung der Infrarotlampe ist beeinträchtigt, Altern am Lebensende1. Reinigen Sie zunächst die Optik, um Verunreinigungen auszuschließenNEIN
2. Wenn der Alarm nach dem Zurücksetzen weiterhin besteht: Ersetzen Sie das optische Modul aufgrund eines Lampenfehlers
13FHardwarefehlerSelbsttestfehler der Hauptplatine und des Antriebsschaltkreises1. Ausschalten für 5 Minuten, dann erneut einschalten✅ Verriegelt
2. Stromversorgung stabilisieren
3. Wiederkehrender Fehler: Senden Sie den Sender zur Reparatur ein oder ersetzen Sie ihn
16FSchlechte SignalqualitätLaut, Instabiles Infrarotsignal mit niedrigem SNR1. Reinigen Sie zuerst das optische Fenster und den Filter✅ Verriegelt
2. Überprüfen Sie, ob in der Gaskammer Wasser oder Frost eindringt
3. Ersetzen Sie die optische Baugruppe, wenn eine Alterung der Lampe oder ein optischer Versatz auftritt
22W / FInterner Firmware-FehlerFirmware-Prüfsummenfehler, Speicherausnahme1. Neustart mit vollständigem Ein- und Ausschalten✅ Verriegelt
2. Fehlerprotokoll über HART-Tool löschen
3. Anhaltender Fehler: Firmware neu flashen oder Hauptplatine austauschen

📌 Häufige allgemeine Fehler (Keine unabhängige Fehler-ID in HART)

  1. HART-Kommunikationsfehler

Überprüfen: 250In der Schleife muss ein Ω-HART-Widerstand installiert sein; richtige Polarität; einseitige Schirmerdung; keine übermäßige Anzahl von Nicht-HART-Geräten am Bus; passende Baudrate.

  1. Langsame Lesedrift ohne Fehlercode

Überprüfen: überfällige Kalibrierung; verstopfter Staubfilter; Kontinuierliche Störungen durch Kohlenwasserstoffe in geringem Konzentrationsbereich; Schweröladsorption in der Gaszelle.

  1. Keine Stromausgabe & Keine Kommunikation nach dem Einschalten

Überprüfen: Wassereintritt & Klemmenkorrosion im M25-Anschlusskasten; Durchgebrannter Stromkreis wegen Verpolung; Interne Sicherung durchgebrannt.

🛠️ Betriebsrichtlinien (für 2108N4000H)

  1. Verriegelte Fehler löschen: HART-Menü →【Fehler/Warnung】→Löschen; oder ≥30 Sekunden ausschalten und dann neu starten. Hardwarefehler treten unmittelbar nach dem Zurücksetzen erneut auf; Maskieren Sie sie nicht dauerhaft.
  2. Kalibrierungsvoraussetzung: Machen Sie den gesamten optischen Pfad frei & Lampenwarnungen vor der Nullpunkt-/Spannungskalibrierung; Bei aktiver Optik-Kontaminationswarnung wird die Kalibrierung stark abweichen.
  3. Ersatzteilabteilung: Fehler 8,11,16 = optisches Modul (Lampe + Detektor + Linse); Fehler 5,13,22 = Hauptplatinenfehler. Eine Reparatur auf Platinenebene wird nicht empfohlen; Ersetzen Sie den gesamten Sender direkt.
  4. SIL2-Erinnerung: Fehler der F-Klasse lösen eine SIL-Sicherheitsschleifenaktion aus. Betreiben Sie den Detektor nicht über einen längeren Zeitraum mit maskiertem Fehler; zeitnah Abhilfe schaffen.

(Searchpoint Optima Plus)

Produktposition: Punktförmiger NDIR-Kohlenwasserstoffbrennstoff Gasdetektor, HART-Protokollversion

Hergestellt von Honeywell Analytics UK. NDIR-Infrarotprinzip, immun gegen katalytische Perlenvergiftung. Ideal für Offshore-Plattformen, Raffinerien, LNG und andere raue Umgebungen; Sicherheitsintegritätsstufe SIL2.

✅ Modellcodierungsdefinition

2108: Searchpoint Optima Plus-Serie

N: Kohlenwasserstoff-HC-Version (Methan, Propan, Benzin usw., Ihr Modell)

4: Standard-Diffusionstyp mit Wetterschutz

000: Ohne Ferngaszelle & Probenahmepfad

H: HIRSCH 7 Protokoll überlagert mit 4-20-mA-Signal (Suffix N = reines 4-20mA ohne HART, z.B. 2108N4100N)

Faden: M25 (unterscheidet sich von der 41xx-Serie mit 3/4″NPT-Gewinde)

Standardkonfiguration: 316L Gehäuse aus elektropoliertem Edelstahl, Staubfilter, nylon weatherproof cover, sunshade against rain splash.

📌 Wichtige technische Spezifikationen

ArtikelParameter
ErkennungsprinzipNon-Dispersive Infrared (NDIR)
Messbereich0~100%LEL; configurable for hundreds of hydrocarbons & solvents (Methan, Propan, ethylene, Benzin, aromatics)
StromversorgungDC18~32V, nominal 24 VDC; max power consumption <4.5W
Signalausgang4-20mA + HART7; Modbus RS485 multi-drop bus available with optional DX100(M) Modul
Current Levels (Fault/Inhibit/Alarm)Fehler: 0mA (HART version configurable to 1mA); Inhibit: default 2mA; Warnung: default 3mA; Over-range: 20~21.5mA (default 21mA)
Ansprechzeit (Methane)T50<3s, T90<4s
Betriebstemperatur-40℃ ~ +65℃
Schutz vor EindringenIP66 / IP67
Gehäusematerial316 Edelstahl (CF8M); total weight approx. 1.6kg
SicherheitszertifizierungenATEX, IECEx, FM, CSA; SIL2 (IEC61508)
GenauigkeitBaseline drift <±1%FSD (HC); <±2%FSD (ethylene)
Pressure Effect0.1% reading per mbar

✨ Infrared vs Catalytic Bead Advantages

  1. Resistant to catalytic poisons (Silikon, lead, H₂S), longer service life and extended maintenance interval
  2. Fail-safe optical self-test; no silent failure risk
  3. Works normally in inert atmosphere (catalytic sensors require oxygen)
  4. Built-in temperature control heating; anti-condensation optical window; Vorwarnung vor Linsenverschmutzung
  5. Integriertes Ereignisprotokoll; Unterstützung des HART-Kommunikators für die Inbetriebnahme, Kalibrierung und Diagnose

🧾 Typische Anwendungsszenarien

Offshore-Öl & Gasplattformen, FPSO, Öltanker, Raffinerien, LNG/LPG-Tankstellen, Gasreglerstationen, Gasturbinenkraftwerke, Lösungsmittelbeschichtung & Druckwerkstätten, Tanklager.

📎 Modellübergreifende Referenz (zum Ersatz & Auswahl)

2108N4000H: M25-Gewinde, HIRSCH, Diffusionstyp mit Wetterschutz (Ihre Einheit)

2108N4100N: 3/4″NVV, reine 4-20mA, kein HART

2108N4100H: 3/4″NVV, HART-Version

2108N5100H: Durchfluss-Probenahmetyp mit HART, für Pipeline-Probenahmesysteme

⚠️ Wichtige Hinweise

  1. Der Infrarotdetektor reagiert nur auf Kohlenwasserstoffe; kann keine brennbaren Gase, die keine Kohlenwasserstoffe sind, wie z. B. H₂, erkennen, CO, NH₃.
  2. Das Kalibriergas muss mit dem Zielgas übereinstimmen; Der Reaktionsfaktor variiert für verschiedene Kohlenwasserstoffe.
  3. Katalytische Perlensensoren können nicht direkt ausgetauscht werden, ohne die Host-Logik und die Alarmschwellen erneut zu überprüfen.
  4. Verbrauchsmaterialien: optisches Modul, dust filter and weather shield are regular wear items.

Honeywell Searchpoint Optima Plus (2108 Serie) Vollständige Modellliste

  1. Modellcodierungsregeln

2108N: Standard Hydrocarbon (HC) Version (Methan, Propan, Benzin usw.)

2108B: Ethylene & solvent dedicated version (ethylene, aromatics, esters)

4Ziffer: 4 = Diffusion type; 5 = Flow-through sampling type (with gas cell)

Thread code: 0 = M25; 1 = 3/4″NVV

Suffix: N = 4-20mA only; H = 4-20mA + HART7 protocol

Suffix 10 = with Remote Gas Cell (RGC); 00 = without remote gas cell

  1. 2108N Hydrocarbon Standard Models (Hauptserie, including 2108N4000H)

2.1 M25-Gewinde (0) | Diffusion (4) | No RGC (00)

  1. 2108N4000N: 4-20mA, M25, diffusion, weather shield
  2. 2108N4000H: 4-20mA+HART, M25, diffusion (Ihr Modell)
  3. 2108N4001N: Ethylene calibrated, M25, diffusion, 4-20mA
  4. 2108N4001H: Ethylene calibrated, M25, diffusion, HIRSCH
  5. 2108N4010N: HC + RGC remote test cell, M25, diffusion
  6. 2108N4010H: HC + RGC, M25, diffusion, HIRSCH

2.2 3/4″NPT-Gewinde (1) | Diffusion (4) | No RGC (00)

  1. 2108N4100N: 4-20mA, NVV, diffusion
  2. 2108N4100H: 4-20mA+HART, NVV, diffusion
  3. 2108N4110N: With RGC, NVV, diffusion
  4. 2108N4110H: With RGC, NVV, diffusion + HIRSCH

2.3 Flow-through sampling type (5) for sampling pipeline & pre-treatment systems

M25-Gewinde (0)

  1. 2108N5000N: Flow gas cell, M25, 4-20mA
  2. 2108N5000H: Flow gas cell, M25, HIRSCH
  3. 2108N5010N: Flow type + RGC, M25
  4. 2108N5010H: Flow type + RGC, M25 + HIRSCH

3/4″NPT-Gewinde (1)

  1. 2108N5100N: Flow gas cell, NVV, 4-20mA
  2. 2108N5100H: Flow gas cell, NVV, HIRSCH
  3. 2108N5110N: Flow type + RGC, NVV, high concentration range (0~100%vol CH₄)
  4. 2108N5110H: Flow type + RGC, NVV + HIRSCH

2.4 Special XTC Marine & Multi-certified Models (44/46/48 Serie)

  1. 2108N4400N / H: Diffusion, Marine-Zertifizierung, M25
  2. 2108N4600N / H: Diffusion, UL/FM certified, M25
  3. 2108N4601N / H: Ethylene calibrated, 46-type diffusion
  4. 2108N4800N / H: Optima Plus XTC version, M25 diffusion
  5. 2108N5400/5600/5800 N/H: Corresponding flow-through versions (44/46/48 sampling models)
  6. 2108B Ethylene & Lösungsmittelspezifische Modelle (für Optima X/Z Probenahmesysteme)

Diffusionstyp (4)

  1. 2108B4001N / H: Ethylene calibrated, M25 diffusion
  2. 2108B4101N / H: Ethylene calibrated, NPT-Diffusion

Flow-through sampling type (5, Nur für Probenahmesysteme)

  1. 2108B5001N / H: Ethylen-Durchflusszelle, M25
  2. 2108B5101N / H: Ethylen-Durchflusszelle, NVV
  3. 2108B2001N / H: Schnell reagierendes Probenahmemodell Optima X (spezielle Brennstoffzelle)
  4. 2108B2051N: DNV-Marine-zertifizierte Version
  5. Ersatzteil-Bestellcodes für die komplette Serie
  6. Optisches Modul: 2108D3001 (Methane), 2108D3034 (Ethylene)
  7. Ferngesteuerte Gaszelle (RGC): 2108B0240
  8. Durchfluss-Gaszellenbaugruppe: 2108B0282
  9. Staubfilter + Wetterschild: 2108B2337
  10. Terminal & Anschlussdose: 2108B2360
  11. Schnellauswahltabelle (zum Ersatz)
MontageartFadenOhne RGC (Standard)With RGC (Ferntest)
Wandmontierte DiffusionM252108N4000N / H2108N4010N / H
Wandmontierte Diffusion3/4″NVV2108N4100N / H2108N4110N / H
Pipeline-ProbenahmeM252108N5000N / H2108N5010N / H
Pipeline-Probenahme3/4″NVV2108N5100N / H2108N5110N / H
  1. Ergänzende Bemerkungen
  2. N = nur 4-20 mA analog; H = HART aktiviert. Mischen Sie keine Loop-Typen; 250Für HART-Schleifen ist ein Ω-Widerstand zwingend erforderlich.
  3. 2108N erkennt nur Kohlenwasserstoffe; 2108B ist für Ethylen bestimmt, Ester und Alkohole. Keiner von beiden kann H₂ erkennen, CO oder NH₃.
  4. Alle Modelle erfüllen SIL2, ATEX/IECEx/FM-Zertifizierung; Schutzart IP67.

 