Mini-MW W2YV Compact Dual-Output Isolator
M-SYSTEM (Japan), DIN-Schienenmontage, 4-way galvanic isolation (Eingang / Output1 / Output2 / Stromversorgung). Designed for 4~20mA industrial signal isolation, ground loop interference suppression and 1-input 2-output signal distribution.
✅ Model Decoding W2YV-AAA-M
W2YV ①②③ ④
- ① A: Input signal = DC 4~20mA (Input resistance: 250Oh)
- ② A: Ausgabe 1 = DC 4~20mA (Max load ≤750Ω)
- ③ A: Ausgabe 2 = DC 4~20mA (Max load ≤350Ω)
- ④ M: Power supply = AC 85~264V wide-range AC (47~66Hz)
Full definition: 4~20mA input, two independent isolated 4~20mA outputs, AC85-264V powered signal distribution isolator
📋 Grundlegende technische Spezifikationen
| Artikel | Spezifikationen |
| Isolation Structure | Galvanic isolation between Input / OUT1 / OUT2 / Stromversorgung |
| Genauigkeit | ±0.1% FS |
| Temperaturdrift | ±0.015% /℃ |
| Ansprechzeit | ≤0.5s (0~90 %) |
| Spannungsbeständig | 2000V und, 1 Minute (between each isolation barrier) |
| Isolationswiderstand | ≥100MΩ @500VDC |
| Null / Span Adjustment | Front panel independent trimming; separate ZERO/SPAN adjustment for two outputs |
| Montage | DIN-Schiene, dense side-by-side installation for high-density cabinet layout |
| Gesamtabmessungen | W29.5 × H88.5 × D124 mm |
| Terminals | M3-Schraube, Anzugsdrehmoment 0.8 N·m |
| Betriebsumgebung | -5 ~ +55℃, 30~90 % relative Luftfeuchtigkeit (nicht kondensierend) |
| Stromverbrauch | Ca. 4VA @AC100V; Ca. 6VA @AC240V |
| Gewicht | Ca. 200G |
🎯 Typical Applications
- Eliminate ground loop interference between SPS Und Sender
- Distribute one 4~20mA measurement signal to PLC + recorder / indicator (1-input 2-output signal splitting)
- Provide galvanic isolation between field transmitters and control room systems to protect AI modules
- Impedance conversion for parallel acquisition by multiple receiving instruments
⚙️ Selection & Ersatzinformationen
Same series DC powered variant: W2YV-AAA-R2 (DC11~27V supply)
Inländische Alternativen: Yutong, Chenzhu, Wanxun and other 1-in-2-out 4-20mA isolators (compare isolation rating, accuracy and temperature drift)
Notiz: The two current outputs have different maximum load limits. OUT2 max load is only 350Ω. Use OUT1 for high-load applications.
📌 Troubleshooting Guide
- Ungenaue Ausgabe: Recalibrate ZERO/SPAN on front panel; check 250Ω matching resistor on input loop
- Kein Ausgangssignal: Verify AC supply 85~264V; check tightness of M3 terminal screws
- Signaldrift: Check earthing; ensure input side ground is separated from PLC ground. The isolator is used to break common ground.
- Excessive voltage drop under load: Connect the load to OUT1 channel (OUT1 has higher load capacity)
W2YV (Mini-MW Dual-Output Signal Conditioner) Complete Model Code + Gemeinsame Modellliste
W2YV = W2YV-①②③-④⑤
①: Input signal; ②: OUT1 output; ③: OUT2 output; ④: Stromversorgung; ⑤: Optionales Suffix
Code Definition
① Input Code
A: DC 4~20mA, input resistance 250Ω
6: DC 1~5V, input impedance ≥1MΩ
② OUT1 (Kanal 1, higher load capacity: Max 750Ω)
A: DC 4~20mA
6: DC 1~5V
③ OUT2 (Kanal 2; Max 350Ω for current output; ≥5kΩ for voltage output)
A: DC 4~20mA
6: DC 1~5V
Y: Keine Ausgabe (single-output mode)
④ Power Code
M: AC85~264V (Wide AC)
R2: DC11~27V (24V DC-Versorgung)
⑤ Options (Suffix /Q, multiple options can be combined)
C01: Silicone coating (Feuchtigkeit & dust protection)
C02: Polyurethane coating
C03: Rubber coating
V01: Multi-turn trim potentiometer
S01: Stainless steel terminal screws
✅ Common Available Models of W2YV Series
- W2YV-AAA-M: 4~20mA input, dual 4~20mA outputs, AC85~264V (your target model)
- W2YV-AAA-R2: 4~20mA input, dual 4~20mA outputs, DC11~27V
- W2YV-6AA-M: 1~5V input, dual 4~20mA outputs, Wechselstromversorgung
- W2YV-6AA-R2: 1~5V input, dual 4~20mA outputs, DC supply
- W2YV-A6A-M: 4~20mA input, OUT1=1~5V, OUT2=4~20mA, Wechselstromversorgung
- W2YV-AA6-M: 4~20mA input, OUT1=4~20mA, OUT2=1~5V, Wechselstromversorgung
- W2YV-6A6-M: 1~5V input, OUT1=4~20mA, OUT2=1~5V, Wechselstromversorgung
- W2YV-A66-R2: 4~20mA input, dual 1~5V voltage outputs, DC supply
- W2YV-AAY-M: 4~20mA input, OUT1=4~20mA only, OUT2 no output (Einzelausgang)
- W2YV-666-R2: 1~5V input, dual 1~5V voltage outputs, DC supply
📌 Other W2 Family Models (Same DIN rail housing as W2 series)
W2XF: Arithmetic signal conditioner (addition / subtraction calculation)
W2VABS: Absolute value signal converter
W2RS: RTD-Widerstands-Temperaturdetektor-Isolator
W2YV ist nur für die 1-in-2-out-Isolierung und -Verteilung von DC-mA/V-Signalen vorgesehen. Für Temperaturmessungen oder Rechenfunktionen, Wählen Sie oben weitere Modelle der W2-Serie aus.
⚠️ Wichtige Auswahlhinweise
- Gemischte Ausgabe (ein Strom + eine Spannung): Legen Sie das aktuelle Signal an OUT1. OUT1 has higher load capacity (750Ω vs. 350Ω von OUT2)
- Beschichtete Versionen C01 werden für Umgebungen mit hoher Luftfeuchtigkeit und Chemikalienschränken empfohlen
- Dichte DIN-Installation nebeneinander; kein Wärmeableitungsspalt erforderlich, Das ist der entscheidende Vorteil dieser Serie
W2YV-AAA-M (M-SYSTEM) Gesamtabmessungen
Breite(W) × Höhe(H) × Tiefe(D) = 29.5 mm × 88.5 mm × 124 mm
Zoll: 1.16″ × 3,48″ × 4,88″
Ergänzende Dimensionsinformationen
- DIN-Schienenmontage: 35mm Standard-DIN-Schiene. Module können dicht nebeneinander montiert werden, Es ist kein Wärmeableitungsspalt zwischen den Modulen erforderlich, Ideal für die Anordnung von Schränken mit hoher Dichte
- Gewicht: Ca. 200G
- Montagemethode: DIN-Schienen-Clip-Montage, oder Grundplattenverschraubung (2×Φ4.2 mounting holes)
- Terminals: M3 screw terminals. The terminal block protrudes forward; above dimensions refer to maximum overall outline of the unit.
W2YV‑AAA‑M Input Signal Description
For model W2YV-AAA-M specifically: Input is fixed as DC 4~20mA (1st character A), input resistance 250Ω
All Optional Input Types of W2YV Series (1st character in model code)
- A: DC 4~20mA (Aktueller Eingang)
Input resistance: 250Oh
This is the input specification of your W2YV-AAA-M
- 6: DC 1~5V (Spannungseingang)
Input impedance ≥1MΩ, high-impedance voltage acquisition
⚠️ Wichtig: W2YV series only has these two factory fixed input ranges. It is NOT programmable. It cannot be modified on-site for 0-10V, 0-20mA, thermocouple or RTD signals. If temperature measurement or multi-range programmable function is required, select other W2 series models such as W2XF.
Brief Comparison
| Code | Signaltyp | Eingangsimpedanz |
| A | DC 4~20mA | 250Oh |
| 6 | DC 1~5V | ≥1MΩ |
Ergänzen
The input range of W2YV is locked at factory by model coding. It cannot be changed by hardware jumpers on site. Only A (4~20mA) oder 6 (1~5V) can be selected during ordering.
Schütz,Leistungsschalter,Sensor,Encoder,SPS,Konverter



















NH42-63-318x560.png)