Phönix 2981800 Sicherheitsrelais - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-Mail: kent@bestcontactor.com

Um Kontakt |

Phönix 2981800 Sicherheitsrelais - Schütz,Leistungsschalter,Solarwechselrichter,Stromzähler,Solarbatterien

elektrisch/

Phönix 2981800 Sicherheitsrelais

  Model Segment Full Designation Description 2981800 Bestell-Nr. Phoenix Contact global unique part number PSR PSR Phoenix Contact PSR series safety relay (Programmable Safety Relay) SCP SCP Safety function: dedicated for Emergency Stop / Safety Gate monitoring (Safety Control for E-Stop/Door) 24DC 24DC Control voltage: DC24V input ESD ESD Function feature: Emergency Stop Delay ...

  • Produktdetails

 

ModellsegmentFull DesignationBeschreibung
2981800Bestell-Nr.Phoenix Contact global unique part number
PSRPSRPhoenix Contact PSR series safety relay (Programmable Safety Relay)
SCPSCPSafety function: dedicated for Emergency Stop / Safety Gate monitoring (Safety Control for E-Stop/Door)
24Gleichstrom24GleichstromSteuerspannung: DC24V input
ESDESDFunction feature: Emergency Stop Delay
4X14X1Kontaktkonfiguration: 4 Kontakte (2 safety NO + 2 auxiliary NO), 1-channel safety input
3030Delay range: adjustable power-off delay 0.1s ~ 30s

Kernanwendung: Single-channel safety relay for Emergency Stop and Safety Gate monitoring. It complies with safety rating SIL 3 / Cat.4 PL e, with 0.1–30s adjustable power-off delay. Suitable for protection scenarios of automated equipment requiring safety stop delay.

  1. Kernspezifikationen
ParameterkategorieDetaillierte SpezifikationBemerkungen
Safety PerformanceSicherheitsniveau: SIL 3 (IEC 61508)Meets highest industrial safety requirements
Performance Level: PL e, Kategorie 4 (IN ISO 13849-1)
PFHd: 2.5×10⁻⁸/h
EingabemerkmaleSteuerspannung: DC24V (19.2~28.8V)Compatible with standard industrial 24V DC control systems
Eingangsstrom: Max 40mA
Input Channel: 1 safety input (NC/NO optional)
Reset-Modus: Automatisch / Manual selectable
AusgabeeigenschaftenSafety Contacts: 2 pcs N/O (Force-guided)Force-guided safety contacts ensure fail-safe operation
Hilfskontakte: 2 pcs N/O
Kontaktbewertung: AC-15: 230V/2.5A
DC-13: 24V/2.5A
Max Switching Voltage: 250V AC/DC
Max Switching Current: 6A
VerzögerungseigenschaftenPower-off delay: continuously adjustable 0.1s~30sAdapt to different equipment stopping time requirements
Setting Accuracy: ±10 %
Physikalische EigenschaftenAbmessungen: W22.5mm × H99mm × D121mmSingle-channel width, spart Platz im Schrank
Gewicht: Ca. 0.22kg
Montage: 35mm DIN-Schiene (IN 60715)
Verdrahtung: Plug-in screw terminals
UmwelteigenschaftenBetriebstemperatur: -20~+60℃Industrial-grade environmental adaptability for harsh working conditions
Lagertemperatur: -40~+85℃
Luftfeuchtigkeit: 5~95%RH (nicht kondensierend)
Vibrationsfestigkeit: 10~150Hz, 2G
Schockfestigkeit: 15G
Safety CertificationsCE, UL, CSA, TÜV, ATEXCompliant with international safety standards, globally applicable
  1. Zubehörliste & Installationsrichtlinien

3.1 Standardzubehör

Safety relay unit ×1

Installation manual ×1

Terminal marking label ×1

Fixing clip ×2 (for DIN rail locking)

Delay adjustment screwdriver ×1 (special tool)

3.2 Vorsichtsmaßnahmen bei der Installation

  1. Mounting Requirement: Install on standard 35mm DIN rail; maintain ≥5mm clearance from adjacent modules for heat dissipation.
  2. Verkabelungsspezifikation:

Steuerkreis: Connect DC24V to A1(+)、A2(-)

Safety Input: Connect E-stop / safety gate contact to S11S12 (NC contact preferred)

Safety Output: Connect safety circuit (z.B. Schützspule) Zu 13-14、23-24

Auxiliary Output: Connect alarm / indication circuit to 31-32、41-42

  1. Reset Setting:

Auto Reset: Automatically restore after power cycle

Manueller Reset: Requires external reset signal or manual reset button operation

  1. Delay Adjustment: Use the dedicated screwdriver to adjust the front panel potentiometer to set 0.1–30s power-off delay.
  2. Cross-model & Cross-brand Replacement

4.1 Phoenix Contact Same Series Alternative Models

Model No.KernunterschiedAnwendungsszenario
29818001 Kanal, 2 Sicherheit + 2 Hilfskontakte, 0.1–30s delayStandard E-stop / safety gate monitoring (current model)
29818011 Kanal, 2 Sicherheit + 2 Hilfskontakte, 0.1–10s delayEquipment with short stopping time
29818021 Kanal, 2 Sicherheit + 2 Hilfskontakte, 0.1–1s delayFast stop equipment
29818102 Kanäle, 4 Sicherheit + 2 Hilfskontakte, no delayDual-channel redundant safety system
29818201 Kanal, 2 Sicherheit + 2 Hilfskontakte, with alarm outputSystem requiring alarm indication

4.2 Cross-brand Equivalent Solutions

MarkeModellSchlüsselparameterKompatibilitätshinweis
SchneiderZelio SR2P121BD1 Kanal, 2 Sicherheitskontakte, 24In DC, Kat.4Similar function, different wiring layout
Siemens3SK1111-1AB301 Kanal, 2 Sicherheitskontakte, 24In DC, SIL 3Different dimensions, cabinet rearrangement required
OmronG9SA-321-T151 Kanal, 2 Sicherheitskontakte, 24In DC, Kat.4Delay range 0.05–10s, slightly narrower
ABBMSR12751 Kanal, 2 Sicherheitskontakte, 24In DC, SIL 3Higher price, fully identical function
WeidmüllerDRM570730LT1 Kanal, 2 Sicherheitskontakte, 24In DC, Kat.4Fixed 1s non-adjustable delay

 

  1. Auswahl & Replacement Guidelines

5.1 Core Selection Criteria

✅ Safety Level Matching: Ensure required safety rating (SIL/PL/Cat.) does not exceed product capability (SIL 3 / Cat.4 PL e).

✅ I/O Requirement:

Eingang: 1 channel sufficient; confirm NC or NO contact type.

Ausgabe: Verify 2 Sicherheit + 2 auxiliary contacts meet control demands.

Kontaktkapazität: Ensure load current ≤2.5A (AC-15/DC-13).

✅ Delay Requirement: Confirm 0.1–30s adjustable range covers equipment stopping time.

✅ Reset Mode: Select auto or manual reset according to operation needs.

✅ Environmental Adaptation: Operating temperature ≤60℃ and humidity within industrial standard range.

5.2 Upgrade & Ersatzoptionen

Option A: Same Series Function Upgrade

More channels: 2981800 → 2981810 (2 Kanäle, 4 Sicherheitskontakte)

Add alarm output: 2981800 → 2981820 (with alarm output)

Shorter delay: 2981800 → 2981801 (0.1–10s) oder 2981802 (0.1–1s)

Option B: Migrate from PSRclassic to PSRmini (Space Optimization)

Ersatzmodell: 2981900 (PSRmini-SCP-24DC/ESD/4X1/30)

Vorteil: Only 17.5mm width (5mm narrower), identische Funktionen, spart Platz im Schrank.

Option C: Migrate from PSRclassic to PSRmodular (System Expansion)

Lösung: PSRmodular system + safety function modules

Vorteil: Multi-channel expandable; integrates safety gate, E-stop, light curtain and other safety functions, suitable for complex safety systems.

5.3 Allgemeine Fehlerbehebung

FehlerphänomenMögliche UrsacheLösung
Module indicator offControl power disconnected or faultyCheck DC24V input, measure voltage within 19.2~28.8V
No safety output actionSafety input loop openCheck E-stop / safety gate contact wiring and loop continuity
Abnormal delay timeImproper potentiometer adjustmentReadjust with dedicated screwdriver; calibrate with timer recommended
Reset failureIncorrect reset mode settingVerify auto/manual reset configuration and check reset signal
KontakthaftungOverload current exceededMeasure load current; add intermediate relay if necessary

Phoenix Contact 2981800 (PSR-SCP-24DC/ESD/4X1/30) is a single-channel safety relay with adjustable power-off delay, specially designed for emergency stop and safety gate monitoring, reaching the highest safety level SIL 3 / Cat.4 PL e. Its 22.5mm slim design and plug-in wiring facilitate installation and maintenance, while the 0.1–30s adjustable delay adapts to various equipment shutdown requirements. Während der Auswahl, focus on safety rating, I/O configuration, delay range and reset mode. For upgrade, choose extended models in the same series or migrate to PSRmini / PSRmodular for space saving or system expansion.

Complete Model List of Phoenix Contact Safety Relays (Structured Classification)

  1. Model Naming Rule Overview
PrefixSeries CodeMiddle CodeBedeutungSuffixBedeutung
PSRBasic identifier for Phoenix safety relaySCPE-stop / Safety Gate dedicated24GleichstromControl voltage DC24V
PSRSicherheitsrelaisSPPStandard Safety ProtectionESDEmergency Stop Delay (0.1-30S)
PSRSicherheitsrelaisMCMini Compact4X1Kontakt: 4 NEIN (2 Sicherheit + 2 Hilfs-)
PSRSicherheitsrelaisMSMonitoring Safety30Delay time range (0.1-30S)
PSRSicherheitsrelaisUNIUniversal ConfigurablePIPush-in spring terminal
PSRSicherheitsrelaisMMMotion MonitoringSCSchraubklemme
  1. PSRclassic Series (Standard Safety Relays)

2.1 E-Stop / Safety Gate (SCP Series)

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-SCP-24DC/ESD/4X1/3029818001Ch, 2Safety+2Aux, 0.1-30s delaySIL 3/Cat.4 PL eStandard E-stop / Safety Gate
PSR-SCP-24DC/ESD/4X1/1029818011Ch, 2Safety+2Aux, 0.1-10s delaySIL 3/Cat.4 PL eShort stop time equipment
PSR-SCP-24DC/ESD/4X1/129818021Ch, 2Safety+2Aux, 0.1-1s delaySIL 3/Cat.4 PL eFast stop equipment
PSR-SCP-24DC/ESD/5X1/1X2/30029814281/2Ch, 3Safety+1NC+2Aux, 0.1-300s delaySIL 3/Cat.4 PL eLong delay shutdown system
PSR-SCP-24UC/ESA4/3X1/1X2/B29637632Ch, 3Safety+1Aux, no delaySIL 3/Cat.4 PL eDual-channel redundant safety system
PSR-SCP-24DC/MXF3/4X1/2X2/B2903257Multi-Ch, 4Safety+2Aux, 3 SicherheitsfunktionenSIL 3/Cat.4 PL eMulti-function safety monitoring

2.2 Standard Safety Function (SPP Series)

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-SPP-24DC/SDC4/2X1/B29014261Ch, 2Safety contacts, no delaySIL 3/Cat.4 PL eBasic safety loop
PSR-SPP-230AC/ESAM2/3X1/1X2/B29014311Ch, 3Safety+1Aux, AC230VSIL 3/Cat.4 PL eAC power supply system
PSR-SPP-24UC/URM/3X1/3X229014271Ch, 3Safety+3Aux, universal voltageSIL 3/Cat.4 PL eMulti-voltage compatible system
PSR-SPP-24DC/ESD/3X1/1X2/3029814271Ch, 3Safety+1Aux, 0.1-30s delaySIL 3/Cat.4 PL eDelay-type safety system

2.3 Light Curtain Monitoring (SCR Series)

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-SCR-24DC/3X1/1X229815002Ch, 3Safety+1Aux, dedicated for light curtainSIL 3/Cat.4 PL eStandard light curtain monitoring
PSR-SCR-24DC/4X1/2X229815012Ch, 4Safety+2Aux, dedicated for light curtainSIL 3/Cat.4 PL eComplex light curtain safety system
PSR-SCR-24DC/5X1/1X229815022Ch, 5Safety+1Aux, dedicated for light curtainSIL 3/Cat.4 PL eHigh-density safety output

2.4 Two-Hand Control (SCT Series)

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-SCT-24DC/2X1/1X229816002Ch, 2Safety+1Aux, two-hand controlSIL 3/Cat.4 PL eStandard two-hand operation
PSR-SCT-24DC/3X1/2X229816012Ch, 3Safety+2Aux, two-hand controlSIL 3/Cat.4 PL eComplex two-hand operation
  1. PSRmini Series (Micro Compact, 17.5mm Width)

3.1 Basic Safety Function (MC-Serie)

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-MC32-3NO-1NC-24-230UC-SP27005251/2Ch, 3Safety+1NC, universal voltageSIL 3/Cat.4 PL eGeneral safety monitoring
PSR-MC34-3NO-1DO-24DC-SP27005481/2Ch, 3Safety+1diagnostic output, DC24VSIL 3/Cat.4 PL eSystem with diagnostic output
PSR-MC45-3NO-1DO-24DC-SC10820241Ch, 3Safety+1diagnostic output, DC24VSIL 3/Cat.4 PL eCompact E-stop system
PSR-MC22-2NO-1NC-24DC-SP27005001Ch, 2Safety+1NC, DC24VSIL 3/Cat.4 PL eSmall safety loop

3.2 Safety Monitoring Module (MS Series)

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-MS21-1NO-1DO-24DC-SC27021921Ch, 1Safety+1digital output, DC24VSIL 3/Cat.4 PL eSafety controller expansion
PSR-MS31-2NO-1DO-24DC-SP27022001Ch, 2Safety+1digital output, DC24VSIL 3/Cat.4 PL eSafety status monitoring
  1. PSRmodular Series (Modular Safety System)

4.1 Main Control Module

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-UNI-L-1X4NO-1DO-24DC-PI14876481/2Ch, 4Safety+1DO, konfigurierbarSIL 3/Cat.4 PL eUniversal configurable safety system
PSR-UNI-L-2X4NO-2DO-24DC-PI14876492Ch, 8Safety+2DO, konfigurierbarSIL 3/Cat.4 PL eComplex safety system
PSR-UNI-L-1X2NO-1NC-1DO-24DC-PI14876501/2Ch, 2Safety+1NC+1DOSIL 3/Cat.4 PL eSystem with NC output

4.2 Expansion Module

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-EXT-L-1X4NO-24DC-PI14876514-safety output expansionSIL 3/Cat.4 PL eOutput expansion
PSR-EXT-L-1X2NO-1NC-24DC-PI14876522Safety+1NC output expansionSIL 3/Cat.4 PL eMixed output expansion
  1. PSRmotion Series (Motion Monitoring Safety Relay)

5.1 Zero Speed / OverSpeed Monitoring

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-MM25-1NO-2DO-24DC-SC2702355Sensorless zero-speed monitoring, 3-PhasenmotorSIL 3/Cat.3 PL eMotor zero-speed safety protection
PSR-MM35-1NO-2DO-24DC-SC2702356Overspeed monitoring, 3-PhasenmotorSIL 3/Cat.3 PL eMotor overspeed safety protection
PSR-MM45-1NO-2DO-24DC-SC2702357Zero-speed + overspeed dual monitoring, 3-PhasenmotorSIL 3/Cat.3 PL eFull motor speed monitoring

5.2 Rotation Direction Monitoring

ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-MD25-1NO-2DO-24DC-SC2702360Rotation direction monitoring, 3-PhasenmotorSIL 3/Cat.3 PL eMotor rotation direction safety control
  1. Safety Coupling Relays (PSR-SCP/SPP Series)
ModellBestell-Nr.Core ParameterSicherheitsniveauAnwendung
PSR-SCP-24DC/FSP/1X1/1X229817001Safety+1Aux contact, coupling functionSIL 3Safety signal isolation
PSR-SCP-24DC/FSP2/2X1/1X229817012Safety+1Aux contact, coupling functionSIL 3Dual-channel safety isolation
PSR-PS21-1NO-1NC-24DC-SC29817021Safety+1NC contact, coupling functionSIL 3Safety signal switching
  1. Key Selection Parameter Comparison
ParameterkategorieKey IndexAuswahltipps
SicherheitsniveauSIL 1-3, Cat.1-4, PL a-eDetermined by equipment risk assessment; max support SIL 3/Cat.4 PL e
Input Channel1 Channel / 2 ChannelSingle channel for basic safety; dual channel for redundant safety
KontaktkonfigurationQuantity of safety / Hilfskontakte≥2 safety contacts recommended; auxiliary contacts for alarm & indication
SteuerspannungDC24V / AC230V / UniversalMatch on-site control system power supply
Function FeatureDelay / Diagnostic / Cross-circuit detectionE-stop requires delay; complex system needs diagnostic function
Mounting Width17.5mm / 22.5mm / 27.5mmChoose PSRmini (17.5mm) for limited cabinet space
Wiring TypeScrew / Push-in springPush-in for frequent wiring; screw type for vibration environment
  1. Ergänzende Hinweise

8.1 Series Positioning

PSRclassic: Standard type with complete functions, width starting from 22.5mm, suitable for conventional safety applications.

PSRmini: Micro compact type, only 17.5mm width, spart Platz im Schrank.

PSRmodular: Configurable modular system, suitable for complex safety systems with expandable functions.

PSRmotion: Dedicated for motion monitoring, applicable to motor zero-speed / overspeed / rotation direction safety control.

8.2 Ersatzinformationen

Old models are gradually phased out; priority recommended to select models manufactured after 2020.

Some models are discontinued; refer to Phoenix Contact official website or technical support for replacement.

8.3 Sicherheitszertifizierung

Full series certified by CE, UL, CSA, TÜV, konform mit IEC 61508 and EN ISO 13849-1.

Partial models with ATEX certification for explosive atmosphere applications.