Siemens 3RB2056-1FC2 Electronic Overload Relay

Status: Discontinued by original manufacturer, Class 10E, S6-Rahmen, electronic motor protection relay Basic Specifications Order No.: 3RB2056-1FC2 Current setting range: 50 … 200 A Frame size: S6 (compatible with S6 contactors such as 3RT1056) Reiseklasse: Class 10E (behoben, nicht verstellbar) Matched motor power at 400V 50Hz: 30~90 kW Main circuit connection: Busbar connection Auxiliary ...

  • Produktdetails

Status: Discontinued by original manufacturer, Class 10E, S6-Rahmen, electronic motor protection relay

Grundlegende Spezifikationen

Bestell-Nr.: 3RB2056-1FC2

Aktueller Einstellbereich: 50 … 200 A

Rahmengröße: S6 (compatible with S6 contactors such as 3RT1056)

Reiseklasse: Class 10E (behoben, nicht verstellbar)

Matched motor power at 400V 50Hz: 30~90 kW

Hauptstromkreisanschluss: Sammelschienenanschluss

Hilfsstromkreis: Schraubklemmen, auxiliary contacts 1NO + 1NC

Reset-Modus: Handbuch / automatic reset selectable

Montage: Direct snap-on to S6 contactor or standalone mounting

Schutzklasse: IP20

Bemessungsisolationsspannung: 1000V und, Stoßspannungsfestigkeit 8 kV

Frequency range: 50/60Hz

Betriebstemperatur: -25℃ ~ +60℃

Schutzfunktionen

Elektronischer Typ, different from bimetallic thermal relays:

Inverse-time overload protection

Phasenverlust / phase unbalance protection

Motor stall protection

Built-in test button for loop testing

Modellunterscheidung (Easily Confused Models in the Same Series)

3RB2056-1FC2: Class10E, eingestellt

3RB2056-2FC2 / 2FX2: Class20E, heavy-duty start version, häufigster Ersatz

Replacement Selection Suggestions

  1. Direct replacement with same specification: 3RB2056-2FC2 (Class20E); if Class10 is strictly required, prioritize the new generation 3RB3056 series electronic Überlastrelais
  2. Matching contactor: Siemens 3RT1056 (S6)
  3. Inländische Alternative: Domestic electronic thermal relay with 50-200A, S6 footprint, 1NO+1NC, Klasse 10

Wichtige Anmerkungen

3RB2056-1FC2 is an older imported 3RB2 model, discontinued by Siemens. Stock units are only available from inventory. New projects are generally recommended to adopt the new 3RB30 series.

3RB2056-1FC2 (S6 / 50-200A / Class10E) Verdrahtung & Inbetriebnahmehandbuch

Bemerkungen: Electronic type requiring auxiliary power supply A1/A2; main circuit adopts busbar connection (S6, matched with 3RT1056 contactor), not through-core type; Kontakte: 95-96 (NC normally closed), 97-98 (NEIN normalerweise geöffnet), 1NO+1NC

  1. Terminaldefinition

A1, A2: Auxiliary power supply terminals (AC/DC 24V or 110~240V, depending on sub-version). The 3RB20 draws power here. The electronic relay must be powered up for phase loss/unbalance protection to work.

95, 96: Öffnerkontakt (NC) → Standard usage: wired in series into the contactor coil control circuit to cut off and stop the motor on overload trip

97, 98: Normalerweise offener Kontakt (NEIN) → For fault alarm, PLC fault input or fault indicator light

Hauptstromkreis: Upper busbar connects to contactor output, lower busbar connects to motor (L1/L2/L3 straight through. The thermal relay does not break the main circuit, only the control circuit)

Frontplatte: Current adjustment knob (50-200A), M/A DIP switch (Handbuch / auto reset), TEST test button, RESET reset button

  1. Standardschaltplan (Direct-On-Line Start Circuit)

1) Hauptstromkreis

3-phase power supply → Circuit breaker → 3RT1056 (S6 contactor) → 3RB2056-1FC2 busbar input → 3RB busbar output → Motor

2) Hilfsstromkreis

  1. A1/A2: Connected to control power supply (to power the electronic board of thermal relay)
  2. Schaltkreis der Schützspule: Power supply → Stop button → Start button (selbsthemmend) → 95-96 (NC) → Contactor coil → Power supply neutral
  3. Fault signal: 97-98 parallel to fault indicator or PLC DI point

Wichtig: 95-96 is the protection series contact, opens on trip; 97-98 closes synchronously to output fault signal

3) Eigenständige Montage (Not clipped onto contactor)

Main circuit remains busbar connection, auxiliary terminals unchanged, fixed separately on backplate. A1/A2 must be powered.

Notiz: 3RB20 has no A3/A4 remote reset terminals (remote reset is available on 3RB21 only). Only local panel reset or automatic reset is supported.

  1. M / A Reset DIP Switch

M = Manual Reset (Recommended for safety circuits) : After overload / phase loss trip, the RESET button on panel must be pressed to reset; no automatic restart

A = Auto Reset : Automatically resets after approx. 3 minutes delay after tripping, suitable for low-risk fans with unattended operation; A mode is strictly prohibited for equipment with entanglement hazard

  1. Complete Commissioning Procedure (Before Power-on → No-load → On-load)

Schritt 1: Prüfung vor dem Einschalten (Ausschalten)

  1. Check rated current on motor nameplate, set the current knob to motor rated current (Dh)

Beispiel: Motor rated 88A → Align knob at 88A; do not set directly to 200A

Range 50-200A, Class10E fixed and non-adjustable

  1. Set M/A DIP switch per process requirement (M is default)
  2. Check tightening torque of busbar bolts, no loose 3-phase busbar connections; secure auxiliary terminal screws
  3. Durchgangsprüfung mit Multimeter: 95-96 conducting normally; 97-98 open normally

Schritt 2: Power on Auxiliary Supply and Test Functions (No High Voltage on Main Circuit!)

  1. Supply power only to A1/A2, no 380V on main circuit
  2. Drücken [PRÜFEN] Taste:

95-96 öffnet sich, 97-98 closes → Contact action normal

Release TEST and press RESET to restore normal state

TEST only simulates contact action, does not simulate real overload current, it is a loop verification

  1. Reset test: For M mode, RESET button must be pressed to restore after test; for A mode wait for auto reset (M mode is used during commissioning generally)

Schritt 3: Energize Main Circuit and No-load Test Run

  1. Close main circuit, start motor for no-load operation
  2. Measure 3-phase no-load current with clamp meter and record; confirm no severe unbalance
  3. If 3-phase current deviation>20%, check motor, wiring and power supply first. The electronic relay will trip for phase loss/unbalance protection directly

Schritt 4: On-load Operation and Current Verification (Kritisch)

  1. After motor runs stably at rated load, measure 3-phase operating current with clamp meter
  2. If steady operating current is 70A, set the knob to 70A;
  3. Pay attention not to run below the lower limit of the range if starting inrush current is high and rated current is near 50A lower limit;

Definition of Class10E: Trips within 10s at 7.2 mal Nennstrom, suitable for standard motors; not suitable for heavy-duty long-start applications (use 3RB2056-2FC2 Class20E for heavy duty)

Schritt 5: Fault Simulation and Acceptance

  1. Cut off one phase (power off before operation), energize and verify: thermal relay triggers phase loss protection, 95-96 opens to stop motor
  2. Aufzeichnen: setting current, Reset-Modus, trip logs
  3. Akzeptanzkriterien: Überlast, phase loss and phase unbalance trigger reliable tripping; self-locking circuit and fault signal output normal
  4. Quick Fault Troubleshooting
  5. Keine Auslösung bei Überlast: ① A1/A2 no power supply (no supply = no protection for electronic relay); ② setting current too high; ③ TEST button failure
  6. Trip immediately upon energizing: Schwere 3-Phasen-Unsymmetrie, Kurzschluss der Motorwicklung, setting current too low
  7. Cannot auto reset after trip: DIP switch at M (Normal); if switch at A and still no auto reset, device aging
  8. Normal no-load, trips frequently under load: Motorüberlastung, bearing jam, large supply voltage drop, setting current too low
  9. Important Safety Reminders

This is an electronic thermal relay. Protection fails if A1/A2 power is lost! This differs fundamentally from traditional bimetallic 3RU thermal relays

S6 busbar requires strict tightening torque. Poor contact causes heating and false tripping

Automatic reset mode A is forbidden for safety-critical equipment (Förderer, Mischer)

  1. Matching Replacement Reference

Same frame Class10: New generation 3RB3056

Same frame Class20: 3RB2056-2FC2 (heavy-duty start)

3RB2056-1FC2 (S6 / 50-200A / Class10E) Fehler & Lösungen

Pre-reminder: Electronic relay loses all protection without A1/A2 supply, different from traditional bimetallic 3RU. No fault indicator LEDs. Troubleshooting relies on TEST button, multimeter and clamp meter.

Fehler 1: No trip when motor is overloaded (Protection failure)

Symptom: Motor overheats obviously, 95-96 contacts of thermal relay do not act and motor does not stop

Ursache 1: A1/A2 auxiliary supply lost, wrong voltage or loose terminals (Most frequent)

Abhilfe: Measure A1/A2 voltage; verify supply specification; tighten auxiliary terminals. Continuous power supply is required for current detection

Ursache 2: Current knob set far higher than motor rated current

Abhilfe: Reset to motor rated current per nameplate, verify with clamp meter under operation

Ursache 3: Loose main busbar bolts, poor contact and abnormal internal sampling

Abhilfe: Ausschalten, tighten 3-phase busbar to S6 specified torque; check busbar for oxidation and discoloration from heat

Ursache 4: Internal sampling board damaged or component aging (High risk for discontinued stock units)

Abhilfe: Run TEST test. If 95-96 does not switch when TEST pressed → relay damaged, direkt ersetzen

Fehler 2: Normal no-load, frequent tripping under load (Fehlauslösung)

Symptom: Starts fine without load, trips shortly after loading, 95-96 öffnet sich

Ursache 1: Strom zu niedrig einstellen; Class10E trips fast, not fit for heavy-duty long-start motors

Abhilfe: Überprüfen Sie den Nennstrom des Motors; use 3RB2056-2FC2 (Class20E) for heavy starting applications

Ursache 2: 3-Phasenstromunsymmetrie, Phasenverlust, burnt contactor contacts

Abhilfe: Measure 3-phase currents with clamp meter; trip triggered if deviation>20%; check upstream contactor and power supply

Ursache 3: Loose busbar generates heat and sampling drift causes false overload judgement

Abhilfe: Stop equipment, check busbar temperature and oxidation, nachziehen

Ursache 4: Umgebungstemperatur über 60℃, schlechte Schrankbelüftung

Abhilfe: Kühlung verbessern; reserve current margin for high-temperature environments

Fehler 3: Immediate trip when energizing / beginnend (Trip on switch-on)

Symptom: Thermal relay trips as soon as main circuit is energized before motor rotates

Ursache 1: Motor winding short circuit, insulation failure, mechanical seizure or stall

Abhilfe: Disconnect motor, Testen Sie die Isolierung mit einem Megger; check bearing by hand rotation

Ursache 2: Interference on A1/A2 supply, large control voltage fluctuation

Abhilfe: Add filter on control supply; separate supply from variable frequency drives and large contactors

Ursache 3: DIP switch at A auto reset, fault still present and re-trips immediately after closing

Abhilfe: Switch to M manual reset, eliminate root fault before re-energizing, avoid repeated trial switching

Fehler 4: Kann nach einer Auslösung nicht zurückgesetzt werden (RESET button ineffective)

Symptom: After protection triggers, 95-96 cannot restore conduction even after pressing RESET

Ursache 1: Root fault persists (ständige Überlastung, Phasenverlust, seizure) so protection latches

Abhilfe: Cut main circuit, eliminate load fault then reset

Ursache 2: DIP switch at M manual reset but A1/A2 supply drops

Abhilfe: Reset only with stable A1/A2 supply; reset not possible when power is lost

Ursache 3: Interner mechanischer Stau, contact welding or electronic board latch-up

Abhilfe: Ausschalten und ausruhen 5 minutes and retry; if still fails TEST test, Einheit austauschen

Ergänzen: 3RB20 has no remote reset terminals. Remote reset is available only on 3RB21. Do not add external remote reset wiring.

Fehler 5: Auto reset mode A fails to reset automatically

Symptom: Set to auto reset, no recovery after long waiting post trip

Ursache 1: A1/A2 auxiliary supply interrupted, auto-reset timer stops when power is lost

Abhilfe: Keep A1/A2 continuously powered

Ursache 2: Fault remains active (persistent overload, Phasenverlust), protection stays latched and will not reset

Abhilfe: Root fault must be cleared first

Ursache 3: Unit aging, auto-reset timing circuit failure

Abhilfe: Change to M manual reset; replace if auto reset is mandatory

Fehler 6: TEST button no response (Contacts do not switch on TEST press)

Symptom: Only A1/A2 powered, 95-96 remains closed and 97-98 stays open when TEST pressed

Ursache 1: A1/A2 no power supply or mismatched voltage

Abhilfe: Measure auxiliary supply voltage

Ursache 2: TEST button mechanically jammed or internal electronic board damaged

Abhilfe: Power off and clean; replace relay if still invalid

TEST only verifies auxiliary contact loop, does not simulate real overload current. Passing TEST only confirms contact loop works, not current sampling.

Fehler 7: No fault signal output from 97-98 after trip (PLC no fault feedback)

Symptom: Motor stops after trip but NO fault signal output

Ursache 1: Loose wiring or broken wire on 97-98 Terminals

Abhilfe: Measure continuity of 97-98 under tripped state

Ursache 2: Insufficient contact rating, voltage drop when driving low-power PLC DI

Abhilfe: Confirm contact load rating; add intermediate relay if required

Ursache 3: Internal auxiliary contact burnt and damaged

Abhilfe: Run TEST test; replace relay if 97-98 does not close

Fehler 8: Random intermittent tripping during operation

Symptom: Current reading normal, trips irregularly

Ursache 1: Intermittent loose connection on busbar or auxiliary terminals (Vibration, thermal expansion)

Abhilfe: Retighten all terminals and check cabinet vibration

Ursache 2: Control supply fluctuation and harmonic interference (common with VFD circuits)

Abhilfe: Add isolation on control loop; this model is not recommended directly on VFD output, dedicated motor protection relay preferred

Ursache 3: Unit aging, sampling circuit drift (Common for old discontinued stock)

Abhilfe: Relais austauschen, prefer 3RB30 new generation

Fehler 9: Relay latches to trip immediately after auxiliary power on, motor not energized

Symptom: 380V main circuit not powered, 95-96 opens right after A1/A2 supply is switched on

Ursache: Internal electronic board failure, damaged sampling circuit

Abhilfe: Replace overload relay

Standard Field Troubleshooting Flow

  1. Confirm A1/A2 auxiliary power supply normal (First check for electronic relay)
  2. Trigger TEST button to verify contact operation
  3. Measure 3-phase operating current with clamp meter and cross-check setting value
  4. Inspect 3-phase voltage, contactor contacts, motor insulation and busbar tightness
  5. Confirm M/A reset mode matches process requirements
  6. If all above checks pass and fault persists → Relay internal damage

Critical Pitfall Notes

  1. Not recommended for direct use on VFD output side; harmonics cause false detection
  2. Auto reset mode A must not be used long-term on safety equipment (Förderer, Mischer)
  3. Dieses Modell wird nicht mehr hergestellt; inventory spares suffer higher electronic board aging risk than newer 3RB30 series
  4. S6 busbar loose torque causes continuous heating and sampling drift false tripping

SIRIUS 3RB2 Electronic Overload Relay Series Overview

Series includes: 3RB20 (Standardversion, no remote reset), 3RB21 (Enhanced version with remote reset terminals); All discontinued by OEM, only spare stock available. Electronic type requiring A1/A2 auxiliary supply; Schutz: Überlast, Phasenverlust, Phasenunsymmetrie, Stall; Standard contacts 1NO+1NC; Hauptstromschienenanschluss; Frame sizes S6 / S10 / S12; Current range 50~820A

Modellcode-Definition (3RB2 □ □□ □□□)

3RB20: Basisversion, no remote reset (3RB2056-1FC2 belongs here)

3RB21: Erweiterte Version, with remote reset terminals A3/A4

5th-6th digits: 56=S6 (50-200A); 66=S10/S12 (55-630A)

Präfix 1 = Class10E; Präfix 2 = Class20E (heavy-duty start)

Suffix:

FC2: Schraubklemmen, direct snap-on to contactor

FF2: Eigenständige Montage, Schraubklemmen

FW2: Federklemmen, snap-on

FX2: Federklemmen + standalone mounting

GC2 / GF2 / MC2 / MF2: S10/S12 specifications

  1. 3RB20 Series List (No Remote Reset)
Bestell-Nr.Aktueller BereichRahmenReiseklasseMatching ContactorBemerkungen
3RB2056-1FC250–200AS6Class10E3RT1056Snap-on, Schraubklemmen, main subject, eingestellt
3RB2056-1FF250–200AS6Class10E3RT1056Standalone, Schraubklemmen
3RB2056-1FW250–200AS6Class10E3RT1056Snap-on, Federklemmen
3RB2056-1FX250–200AS6Class10E3RT1056Standalone, Federklemmen
3RB2056-2FC250–200AS6Class20E3RT1056Heavy-duty snap-on, Schraubklemmen, popular replacement
3RB2056-2FF250–200AS6Class20E3RT1056Heavy-duty standalone, Schraubklemmen
3RB2056-2FW250–200AS6Class20E3RT1056Heavy-duty snap-on, Federklemmen
3RB2056-2FX250–200AS6Class20E3RT1056Heavy-duty standalone, Federklemmen
3RB2066-1GC255–250AS10Class10E3RT1065Snap-on, Schraubklemmen
3RB2066-1GF255–250AS10Class10E3RT1065Standalone, Schraubklemmen
3RB2066-1MC2160–630AS12Class10E3RT1066Snap-on, Schraubklemmen
3RB2066-1MF2160–630AS12Class10E3RT1066Standalone, Schraubklemmen
3RB2066-2GC255–250AS10Class20E3RT1065Heavy-duty snap-on, Schraubklemmen
3RB2066-2GF255–250AS10Class20E3RT1065Heavy-duty standalone, Schraubklemmen
3RB2066-2MC2160–630AS12Class20E3RT1066Heavy-duty snap-on, Schraubklemmen
3RB2066-2MF2160–630AS12Class20E3RT1066Heavy-duty standalone, Schraubklemmen
3RB2011 + 3UF18630–820AS14Class10E3TF68/3TF69CT combination solution
  1. 3RB21 Series List (With Remote Reset A3/A4)

Suitable for PLC remote reset; protection functions and current ranges same as 3RB20

| 3RB2156-1FC2 | 50-200A | S6 | Class10E | Remote reset, snap-on, Schraubklemmen |

| 3RB2156-1FF2 | 50-200A | S6 | Class10E | Remote reset, eigenständig, Schraubklemmen |

| 3RB2156-2FC2 | 50-200A | S6 | Class20E | Schwere Beanspruchung + remote reset |

| 3RB2166-1GC2 | 55-250A | S10 | Class10E | S10 remote reset |

| 3RB2166-1MC2 | 160-630A | S12 | Class10E | S12 remote reset |

| 3RB2166-2GC2 | 55-250A | S10 | Class20E | S10 heavy duty + remote reset |

| 3RB2166-2MC2 | 160-630A | S12 | Class20E | S12 heavy duty + remote reset |

| 3RB2111 + 3UF18 | 630-820A | S14 | Class10E | CT combination, remote reset |

 

  1. Common Series Parameters
  2. Auxiliary supply: A1/A2, AC/DC 24V or AC110~240V (depends on sub-version). Protection fails when supply is lost
  3. Hilfskontakte: 95-96 (NC), 97-98 (NEIN), 1NO+1NC, 5Eine Bewertung
  4. Zurücksetzen: M/A DIP switch (Handbuch / auto reset); 3RB21 adds A3/A4 remote reset
  5. Schutzklasse: IP20; Insulation voltage 1000V AC, Stoßspannungsfestigkeit 8 kV; Operating temperature -25~+60℃
  6. Hauptstromkreis: Sammelschienenanschluss, not through-core CT type
  7. Anwendung: Standard 3-phase asynchronous motors; Not recommended directly on VFD output; harmonics cause false tripping
  8. New Generation Replacement Series (Empfohlen für neue Projekte)

S6 50-200A replacement: 3RB3056 (neue Generation, better stability, active supply)

S10/S12 high-current: 3RB3066 for equivalent replacement

  1. Kurzanleitung zur Auswahl

No remote reset required → 3RB20

PLC remote reset required → 3RB21

Standardventilatoren, Pumps, smooth start → Class10E (Präfix 1)

Bandförderer, Brecher, heavy-duty long start → Class20E (Präfix 2)

Snap-on mounting with contactor → FC2 / GC2 / MC2

Separate backplate mounting → FF2 / GF2 / MF2