ABB ACS355-03E-07Convertidor de frecuencia A3-4

Descripción del modelo: ACS355 machinery drive frequency converter; 03E = 3-phase input, IP20 enclosure; 07A3 = rated output 7.3 A; 4 = 380–480 V voltage class Part Number: 3AUA0000058188 ✅ Core Electrical Specifications Rated Power: 3.0 kilovatios (sobrecarga ligera / standard duty) Rated Output Current I₂ₙ: 7.3 Una entrada: 3-phase 380–480 V ±10%, 48–63 Hz Output: ...

  • Detalles del producto

Descripción del modelo: ACS355 machinery drive frequency convertidor; 03E = 3-phase input, IP20 enclosure; 07A3 = rated output 7.3 A; 4 = 380–480 V voltage class

Número de pieza: 3AUA0000058188

✅ Especificaciones eléctricas básicas

Potencia nominal: 3.0 kilovatios (sobrecarga ligera / standard duty)

Rated Output Current I₂ₙ: 7.3 A

Aporte: 3-phase 380–480 V ±10%, 48–63Hz

Producción: 0 ~ Uₙ, 0–599Hz

Enclosure Protection: IP20 (without +B063 or other options)

Tamaño del marco: R0

Enfriamiento: Refrigeración por aire

Motores compatibles: 3 kW 3-phase asynchronous motor

📦 Dimensions & Peso

Unidad: W70 mm × H239 mm × D161 mm

Peso neto: 1.8 kilos

Packaged Size: 350×220×130 mm, Peso bruto 2.3 kilos

🧩 On-board I/O (Estándar)

5 Entradas digitales (DE)

1 Salida de relé (RO)

2 Entradas analógicas (AI, 0–10 voltios / 4–20 mA)

1 Salida analógica (HACIA, 4–20 mA)

Modbus RTU incorporado (Terminal X1)

Optional plug-in communication adapters: Profibus DP, CANabierto, DispositivoNet, EtherCAT, etc..

📌 Aplicaciones típicas

Maquinaria general: transportadores, fans, zapatillas, mezcladores, small processing machines. Supports standard V/F control and vector control, velocidades preestablecidas, ramps, multi-set parameter groups.

⚠️ Selección & Notas de reemplazo

  1. For IP66 version: add suffix +B063. Dimensions and weight differ completely, part number changes.
  2. Upgrade alternative within TEJIDO portfolio: ACS380. Older ACS350 of the same power can be cross-referenced by current rating.
  3. Fusible / cortacircuitos: sized per 7.3 A converter standard circuit. Output du/dt reactor is optional.

📎 Common Spare Parts & Accesorios

Paneles de control: ACS-CP-A / ACS-CP-D

Input filter, output du/dt filter, resistencia de frenado (braking chopper built-in)

Communication adapters, Módulos de expansión de E/S

ABBACS355 (ACS355-03E-07A3-4)|Factory Default Parameters for ABB Standard Macro (9902=1)

Nota: Parameters in Group 99 (datos de la placa del motor) have no fixed default values. Enter data per 3 kW motor nameplate after power-up.

Número de parámetro.Nombre del parámetroValor predeterminadoObservaciones
9902Application Macro Selection1 ABB Standard MacroDI1 start, DI2 direction, AI1 reference; más utilizado
9904Motor Control Mode3 Scalar (V/F)Opcional: 1=Vector Speed, 2=Vector Torque
9905Motor Rated Voltage—Follow nameplate; 380 V for standard 3 kilovatios del motor
9906Corriente nominal del motor—Typical value for matched motor ≈6.2 A
9907Motor Rated Frequency—50 Hz for general asynchronous motors
9908Motor Rated Speed—1440 rpm (4-polo)
9909Motor Rated Power—3.0 kilovatios
1001Ext1 Start/Stop Command2 DI1DI1 closed = Run
1002Ext Direction Command3 DI2DI2=0 Forward, DI2=1 Reverse
1103Ext Reference 1 Selección1 AI1AI1 0–10 V / 4–20 mA
1105Ext Reference 1 Máximo50.0 HzMatches full-scale AI signal
1201Constant Speed Selection0 Not SelectedMulti-speed via DI combination
1301AI1 Minimum0.0 V0 V corresponde a 0 Hz
1302AI1 Maximum10.0 V10 V corresponde a 50 Hz
1304AI2 Minimum0.0 VAI2 disabled by default
1401Relay Output RO1 Source0 ReadyOutput when drive is ready
1501AO1 Signal Source102 Frecuencia de salidaHACIA: 4–20 mA mapped to 0–50 Hz
1504AO1 Minimum Output4 mamá
1505AO1 Maximum Output20 mamá
2007Minimum Frequency0.0 Hz
2008Maximum Frequency50.0 Hz
2202Tiempo de aceleración 15.0 s
2203Tiempo de desaceleración 15.0 s
2102Stop Mode1 Coast Stop2=Ramp Stop
2601U/F Ratio1 LinealSquared for fan/pump duty
3017Overcurrent Trip Limit4×I₂n
3025STO Function0 Alarm OnlyEmpezar a 1 triggers fault 0044
5302EFB Station Address1Modbus RTU Slave Address
5303Velocidad de baudios9600
5304Paridad0 No Parity, 1 Stop Bit

ACS355 Fault Code List (English with Troubleshooting Guidance)

Código de fallaNombre de fallaDescripciónSolución de problemas comunes
1OVERCURRENTOutput current exceeds trip thresholdCortocircuito del motor, daño del cable, locked load, tiempo de rampa demasiado corto, incorrect motor data
2DC OVERVOLTDC bus voltage too highdesaceleración rápida, regenerative load, high supply voltage, falta resistencia de frenado
3DEV OVERTEMPIGBT module overtemperatureBlocked airflow, ventilador fallido, temperatura ambiente alta, sobrecarga, mala ventilación del gabinete
4SHORT CIRCMotor-side short circuitMotor winding short, phase-to-phase short on power cable, shorted output terminals
6DC UNDERVOLTDC bus voltage insufficientFalta fase de entrada, open fuse/contact, voltage dip, undersized supply
9MOT OVERTEMPEstimated motor temperature exceededSobrecarga del motor, mal enfriamiento, incorrect motor thermal protection settings
16EARTH FAULTEarth leakage on motor/power cableDamaged cable insulation, motor insulation failure, entrada de humedad
22SUPPLY PHASEPérdida de fase de entrada / 3-desequilibrio de faseFusible de entrada quemado, poor contactor contacts, unbalanced 3-phase supply
44SAFE TORQUE OFF (STO)STO safety circuit activatedSTO terminals not jumpered, safety loop open, parameter 3025=1 triggers fault
28COMM ERRORBuilt-in EFB bus communication breakModbus wiring, resistencia de terminación, abordar el conflicto, master offline
35AI1 LOSSAI1 signal below fault thresholdTransmitter wire break, faulty sensor, threshold setting in 3021
36AI2 LOSSAI2 signal lossBroken AI2 wiring, transmisor defectuoso
41ID RUN FAILMotor identification run failedWrong motor wiring, clasificación de potencia no coincidente, rotor bloqueado
51USER PARAM FAULTParameter set corruptedRestore factory defaults and re-enter motor parameters
71FAN FAULTCooling fan failureFan jammed, fan supply fault

✅ Reset Methods: Panel RESET, DI reset, communication reset, ciclo de energía. Fault history stored in Group 04 parámetros.

Quick Operation

Restablecimiento de fábrica: Parámetro 9606, enter RESET. The drive restarts and loads ABB Standard Macro defaults.

Installation Notes for ABB ACS355-03E-07A3-4 (Frame R0, IP20)

This unit is for cabinet installation only. Clasificación IP20, not suitable for direct outdoor exposure.

  1. Montaje mecánico & Disipación de calor
  2. Orientación de montaje: Vertical upright installation is mandatory. Do not invert. Side mounting is permitted for R0 frame but vertical is preferred. Cooling air flows bottom-in, top-out; inverted mounting causes overheating fault 0003.
  3. Minimum Clearances

Top ≥75 mm, Bottom ≥75 mm; no mandatory side clearance, reserve space for maintenance.

Stacked multiple drives: hot exhaust from lower unit must not blow directly onto upper unit. Use baffles, staggered layout or independent air ducts.

  1. Mounting Options: Screw fixing or 35 carril DIN estándar mm. Mounting base must be rigid and flame-retardant. Prevent conductive dust from entering the unit during drilling (risk of short circuit).
  2. Condiciones ambientales

Temperatura ambiente: -10 ~ +50 °C; reducir la potencia superior 40 °C. Sin condensación, sin glaseado.

Altitud: Full rating ≤1000 m; derate with increasing altitude above 1000 metro.

Prohibited environment: polvo conductor, gas corrosivo, strong magnetic fields (near contactors / large single-core cables), heavy vibration or shock.

  1. Seguridad & Power-off Procedures (Crítico)

After disconnection, esperar 5 minutes for DC bus capacitors to fully discharge before opening covers, wiring or measuring. Do not touch power terminals or internal PCB when powered.

For permanent magnet motors: motor may generate back EMF when rotating even with supply disconnected. Mechanically lock the shaft before working on motor cables.

Before power-up: Disconnect U2/V2/W2 at the converter, test motor insulation to earth with 1000 V megger. Do not energise if insulation is poor (≥100 MΩ @25°C for ABB motors).

Strictly forbidden: Connect mains supply to U2/V2/W2 output terminals, this will destroy the unit.

  1. Selección de cables, Routing & CEM
  2. Cable Recommendations

cable motor: Symmetric shielded VFD cable preferred, reduces bearing currents and EMI. Unshielded standard cables often interfere with sensors and instruments.

Señales analógicas (IA/Mundo): Double-shielded twisted pair. DI/DO relay signals: shielded twisted pair. Separate power cables and control cables in different trunking, minimum gap ≥20 cm. Cross only at 90° where unavoidable.

Do not mix 24 V low-voltage and 220 V high-voltage circuits inside one cable.

  1. Shield Grounding Rules

360° shield termination with earthing clamp; avoid pigtail earthing (poor high-frequency EMC performance). Shield of motor cable grounded at both converter and motor ends.

PE conductor must be short, thick and connected reliably to cabinet earth bar.

  1. ÉL / Ungrounded Delta System: Remove internal EMC filter earth screw, otherwise earth fault 0016 may occur. Keep screw fitted for standard TN-S systems.
  2. Output-side Restrictions: Do not connect capacitors or surge suppressors to U2/V2/W2. For long motor cables (>50 metro), fit output du/dt reactor to protect motor insulation.
  3. Par de terminales & STO Safety Circuit

Par de apriete del terminal de control: 0.4 Nuevo Méjico. Power terminals follow datasheet torque specification.

STO (Desconexión de par segura): Factory fitted with jumper. If STO function is unused, STO terminals must be permanently jumpered. Open STO triggers fault 0044. For safety applications, wire to safety relay contacts.

Resistencia de frenado (BRK+, BRK-): Utilice cable blindado, mount close to drive to minimise lead inductance.

  1. Input Protection, Toma de tierra & Auxiliary Devices

Fit circuit breaker or fuses on input side, sized for 7.3 una calificación. Input AC reactor is recommended to reduce harmonic distortion.

Toma de tierra: PE conductors must be home-run separately to earth bar, do not daisy-chain. Never use neutral N as protective earth PE.

Cabinet ventilation: Install cabinet fans to keep internal temperature below 40 °C. Clean filters regularly to prevent blocked cooling paths.

  1. Pre-power-up Checklist
  2. Terminales de potencia: U1/V1/W1 supply, U2/V2/W2 motor, BRK+/braking resistor – verify connections.
  3. Circuitos de control: DI/AI/AO, STO jumper, puesta a tierra del escudo.
  4. Insulation test passed, no short circuit or earth leakage.
  5. Air path unobstructed.
  6. Motor nameplate data ready; perform motor identification after first power-up.
  7. Installation-related Fault Quick Reference

0003 Overtemp: Blocked airflow, insufficient top/bottom clearance, montaje invertido, high cabinet temperature

0016 Falla a tierra: Incorrect shield grounding, EMC screw not removed for IT system, damaged/wet motor cable

0044 STO Fault: STO terminals not jumpered, safety loop open

Fluctuating AI signals: Mixed power/control wiring, poor shield grounding, non-twisted analog cable

ABB ACS355 Model & Part Number List|03E 3-phase 380–480 V, IP20, Filtro EMC incorporado, Versión estándar

Descripción del modelo:

03 = 3-phase input; E = EMC filter enabled (50 Hz); trailing 4 = 380~480 V; +B063 = IP66 high protection variant (orden separada)

Part Number format: 3AUA00000XXXXX (ABB part number, used for purchasing, quotation and customs declaration)

Frame sizes: R0/R1/R3/R4; built-in braking chopper and STO.

ModeloPotencia nominal kWOutput Current I₂N(A)MarcoABB Part Number (3AUA)
ACS355-03E-01A2-40.371.2R03AUA0000058186
ACS355-03E-01A9-40.551.9R03AUA0000058243
ACS355-03E-02A4-40.752.4R03AUA0000058187
ACS355-03E-03A3-41.13.3R13AUA0000058184
ACS355-03E-04A1-41.54.1R13AUA0000058185
ACS355-03E-05A6-42.25.6R13AUA0000058189
ACS355-03E-07A3-437.3R03AUA0000058188
ACS355-03E-08A8-448.8R13AUA0000058190
ACS355-03E-12A5-45.512.5R33AUA0000058191
ACS355-03E-15A6-47.515.6R33AUA0000058192
ACS355-03E-23A1-41123.1R33AUA0000058193
ACS355-03E-31A0-41531R43AUA0000058195
ACS355-03E-38A0-418.538R43AUA0000058194
ACS355-03E-44A0-42244R43AUA0000058196

Supplementary Range: 01E Single-phase 200–240 V, IP20, CEM incorporado

ModeloPotencia kWCurrent AMarcoNúmero de pieza
ACS355-01E-02A4-20.372.4R03AUA0000058174
ACS355-01E-04A7-20.754.7R13AUA0000058175
ACS355-01E-06A7-21.16.7R13AUA0000058176
ACS355-01E-07A5-21.57.5R23AUA0000058177
ACS355-01E-09A8-22.29.8R23AUA0000058178

Accesorios comunes & Part Numbers for ACS355

Nombre del accesorioModeloNúmero de pieza
Basic Control PanelACS-CP-A3AUA0000040901
Panel de control asistente (Chino)ACS-CP-D3AUA0000040902
Profibus DP AdapterFPBA-013AUA0000040888
CANopen AdapterFCAN-013AUA0000040889
DeviceNet AdapterFDNA-013AUA0000040890
EtherCAT AdapterFECA-013AUA0000040891

Suffix Options (added after model +xxxx)

+B063: IP66 high protection version (for humid, dusty environments)

+N830: Non-coated PCB (standard cabinet version)

+J400: Potentiometer kit

Ejemplo: ACS355-03E-07A3-4+B063 (IP66 variant, número de pieza diferente)

Model Code Guide for Export Selection

03mi: 3-fase, EMC filter enabled (mainstream for China market) ✅

03Ud.: 3-fase, EMC filter disabled (60 Hz overseas version)

03incógnita: Export special version, not common locally

01mi / 01Ud.: Monofásico 220 V models

Replacement series: ACS380 (nueva generacion, successor to ACS355)