Fuente de alimentación de plano posterior Allen-Bradley 1756-PA75

1756-PA75 1756: ControlLogix 5000 Chassis Series PA: AC Input Backplane Power Supply 75: Maximum backplane output power 75W Derivative Models: 1756-PA75K: PCB with conformal coating (for corrosive and humid environments) 1756-PA75R: Redundancy-specific power supply. Cannot be directly used interchangeably with PA75. Requires 1756-PSCA2 Adapter + 1756-CPR2 Cable > ⚠️ Critical Note: The standard 1756-PA75 does ...

  • Detalles del producto

1756-PA75

1756: ControlLogix 5000 Chassis Series

Pensilvania: AC Input Backplane Fuente de alimentación

75: Maximum backplane output power 75W

Modelos derivados:

1756-PA75K: PCB with conformal coating (for corrosive and humid environments)

1756-PA75R: Redundancy-specific power supply. Cannot be directly used interchangeably with PA75. Requires 1756-PSCA2 Adapter + 1756-CPR2 Cable

> ⚠️ Critical Note: The standard 1756-PA75 does not support native redundancy! PA75R kit must be selected for redundant configurations.

  1. Especificaciones eléctricas básicas

Input Ratings

Voltaje de entrada: 85~265 VAC (wide-range, compatible with 120V/240V systems)

Frecuencia: 47~63 Hz

Maximum input apparent power: 100 Virginia

Maximum inrush current: 20 A

Multi-rail DC Backplane Output (75W full load at 0~60℃)

Output RailMaximum Current
5.1 En DC13.0 A
3.3 En DC4.0 A
1.2 En DC1.5 A
24 En DC (Auxiliary Backplane)2.8 A

Mecánico & Especificaciones ambientales

Form Factor: Standard single-slot 1756 power module, installed in the leftmost slot of ControlLogix chassis

Dimensiones: 140 × 112 × 145 milímetros

Peso: Aprox.. 1.45 kilos

Temperatura de funcionamiento: 0~+60 ℃; Temperatura de almacenamiento: -40~+85 ℃

Humedad: 5%~95%, sin condensación

Aislamiento: Reinforced insulation between input and backplane, rated for continuous 250V withstand

Certificaciones: UL, CE, CCC, CSA, etc..

Funciones de protección: Sobretensión, sobrecorriente, sobre temperatura, protección contra cortocircuitos

  1. Front Panel Indicators
  2. DE ACUERDO (Verde)

Steady ON: Power supply healthy

APAGADO / Flashing: Fault detected

  1. FAULT (Rojo)

Illuminated: Sobrecarga, sobre temperatura, falla interna

  1. Alarma (Relay Dry Contact)

Passive alarm contact, can be wired to external alarm circuits.

  1. Comparison with Similar Models
ModeloTipo de entradaClasificación de potenciaRedundancy CapabilityEscenarios de aplicación típicos
1756-PA7585–265V AC75W.Standard standalone unit, not directly redundantGeneral single-chassis systems
1756-PA75K85–265V AC75W.Autónomo, conformal coated PCBHúmedo, polvoriento, corrosive enclosures
1756-PA75R85–265V AC75W.Supports dual-unit redundancy (requires PSCA2+CPR2)Critical production lines requiring zero downtime
1756-PB7518–32V DC75W.Standalone DC input power supplySites with only 24VDC available
1756-PA7285–265V AC72W.Legacy model, lower load capacityReplacement for obsolete equipment
  1. Key Selection Rules & Evitar trampas
  2. Do not judge load solely by total 75W power rating!

Calculate current consumption of all modules in the chassis for each voltage rail (5.1V/3.3V/1.2V). Exceeding the limit on any single rail will trigger FAULT shutdown.

  1. Installation position: Must be mounted in the first leftmost slot of the chassis; cannot be placed in middle or right slots.
  2. Thermal management: Avoid long-term enclosure temperature above 55℃; derate power in high-temperature environments.
  3. Hot Swapping: Hot-swap capable. It is recommended to stop controller logic before swapping to prevent transient interference to communication modules.
  4. Redundancy Misconception: Two standard PA75 units cannot be paralleled directly to achieve redundancy. PA75R redundancy kit is mandatory.
  5. Solución de problemas comunes
  6. FAULT red light ON, OK light OFF

Step1: Remove all modules from chassis, leave only power supply and power on.

If fault persists under no load → Power supply failure.

If normal under no load → Short circuit or overload from chassis modules.

  1. Circuit breaker trips immediately after power-up

The unit has high inrush current on startup; select D-curve MCB for upstream protection. Check L/N/PE wiring for short circuits.

  1. Intermittent FAULT alarm after continuous operation

Insufficient cabinet ventilation, dust accumulation; overtemperature protection triggered due to long-term near-full-load operation.

  1. Aplicaciones industriales típicas

Chemical industry, tratamiento de agua, automotive production lines, metalurgia, manejo de materiales, aceite & gas, large building DCS/PLC systems (power supply for ControlLogix L7x/L8x controller chassis).

Overload Capability of 1756-PA75 (Based on Rockwell Official Document 1756-TD005)

  1. Critical Premise

75W = Continuous rated output power (0~60℃ ambient temperature), NOT peak power. Continuous overload operation is not officially permitted.

The power supply adopts independent multi-rail current limiting protection.

Protection triggers once any single rail exceeds current limit, regardless of total power consumption.

Continuous rated current hard limits for each backplane rail:

Output RailContinuous Rated Current
5.1 VCC13.0 A
3.3 VCC4.0 A
1.2 VCC1.5 A
Backplane 24 VDC Auxiliary2.8 A
  1. Overload Classification & Actual Endurance

2.1 Continuous Overload (Long-term operation above rating)

❌ Not supported or approved by Rockwell

If any rail runs continuously above rated current, or total power exceeds 75W:

  1. Internal temperature rises steadily;
  2. FAULT indicator illuminates and output shuts down for protection once threshold is reached;
  3. Long-term marginal overload accelerates aging of internal capacitors and power semiconductors, shortens service life and voids warranty.

> Field Experience: Continuous load between 70~75W is already the design ceiling. Long-term operation at this level is not recommended. Operation above 75W is strictly prohibited.

2.2 Transient Short-duration Overload (Module power-on inrush, pulse loads)

1756-PA75 can withstand limited short-term peak loads.

Rockwell does not publish precise millisecond overload curves (no specified duration for 120%/150% sobrecarga).

Summary of official design principles plus extensive field experience:

Capable of sustaining hundreds-of-millisecond transient inrush current (simultaneous power-up surge of chassis modules);

Transient peak current may briefly exceed rated value, but cannot be sustained steadily;

System load design shall never rely on transient overload capability. Load calculation must adopt continuous rated parameters.

2.3 Mecanismo de protección & Action Logic

  1. Electronic Current Limiting + Hiccup Protection Mode

Sobrecarga / Short-circuit → Output current clamped → Voltage drop → Temporary shutdown → Automatic retry (hiccup cycling).

  1. Front panel FAULT red indicator steady ON, OK indicator OFF
  2. Alarm relay contact actuates
  3. Automatic recovery is achievable in most cases after overload load is removed. Severe sustained overload may require power cycle to recover.

2.4 Temperature Degradation of Overload Tolerance

Rated 75W output condition: Ambient Temperature 0~60℃

Cabinet temperature >50℃: Recommend 5%~10% power derating

Long-term cabinet temperature >55℃: Even if total power ≤75W, thermal accumulation easily triggers overtemperature overload protection.

Temperatura ambiente >60℃: Rated output performance is no longer guaranteed; overload endurance drops significantly.

  1. Two Common Critical Misunderstandings

Malentendido 1: Parallel two standard 1756-PA75 to increase overload capacity

❌ Absolutely Not Allowed!

Standard PA75 has no current sharing circuit. Parallel connection on backplane is forbidden.

It cannot share load, expand capacity or realize redundancy. Parallel setup will create circulating current and lead to single-point burnout.

For redundancy or capacity expansion: Adopt 1756-PA75R redundancy power supply kit (with 1756-PSCA2 & 1756-CPR2).

Malentendido 2: System will not overload as long as total power <75W.

❌ Independent current limiting for each voltage rail!

Ejemplo: Total power 68W, but 5.1V rail current reaches 13.5A → Immediate overload shutdown.

✅ Standard load verification method: Calculate total power AND current consumption of every DC rail.

  1. Load Design & Recomendaciones de selección
  2. Reserve 15%~25% design margin for steady-state operating load
  3. Sum up backplane power consumption of all modules, tabulate current demand for 5.1V/3.3V/1.2V/24V rails separately
  4. Further increase margin if chassis contains numerous high-inrush I/O modules (salidas de relé, high-speed counters)
  5. If intermittent FAULT flashes occur during operation, priority inspection items: Single rail current close to limit, inadequate cabinet heat dissipation.
  6. Brief Overload Performance Comparison between PA75 and PA75R

PA75 (Estándar): Standalone unit, overload protection logic as stated above

PA75R (Redundancy model): Single unit rated power also 75W.

In redundant configuration, one unit must temporarily bear full load after the other fails. Transient load margin is optimized in firmware, yet continuous load cannot exceed single-unit 75W specification.

Complete Model List for 1756-PA75 Family (75W Power Class)

> Model Nomenclature Guide

Pensilvania: AC Input; PB: 24V DC Input; PC/PH: Special wide-range DC Input

75: Rated backplane output power 75W

k: PCB conformal coating (resist humidity & gas corrosivo)

R: Redundancy dedicated power supply (cannot be used as standalone regular unit)

xt: Extended temperature heavy-duty industrial version

  1. AC Input 75W Series (PA75 Family)
  2. 1756-PA75

Fuente de alimentación de CA estándar, 85~265VAC, 75W., most widely used for general applications.

  1. 1756-PA75K

Variante con revestimiento conformado. Electrical performance identical to PA75. Suitable for chemical, húmedo, dusty and corrosive enclosures.

  1. 1756-PA75R

Redundancy-dedicated AC power supply, equipped with internal hardware for redundant communication. Must be matched with: 1756-PSCA2 (Redundancy Adapter) + 1756-CPR2 Cable.

⚠️ Forbidden to install directly into chassis and operate as standalone unit!

  1. 1756-PA75RK

Redundancy type + conformal coated PCB. Selected for redundant systems deployed in corrosive environments.

  1. 75W DC Input Equivalent Models (For cross-reference replacement)
  2. 1756-PB75: 18~32VDC (24Alimentación VCC) standard power supply
  3. 1756-PB75K: 24V DC input + conformal coating
  4. 1756-PB75R: 24V DC redundancy power supply
  5. 1756-PB75RK: 24V DC redundancy + conformal coating
  6. 1756-PC75: 48V DC dedicated input power supply
  7. 1756-PH75: Wide-range DC 48~125VDC (subestación, DC panel applications)
  8. 1756-PH75K: Wide-range DC input + conformal coating
  9. Other Power Rating Power Supplies for the Same Chassis (Selection Distinction)

3.1 Legacy 72W Series (Lower 5V rail current, not recommended for new projects)

1756-PA72 (C.A.), 1756-PA72K

1756-PB72 (corriente continua), 1756-PB72K

3.2 Low-power single-slot models (Same physical slot width, menor potencia)

1756-PA50 / PB50: 50W.

1756-PA30XT / PB30XT: 30W., XT extended temperature series

3.3 XT Extended Temperature Heavy-duty Series (-20℃~70℃ operating range)

1756-PAXT (AC extended temp), 1756-PBXT (DC extended temp)

1756-PAXTR / PBXTR: Redundancy power supply for XT series

  1. Critical Selection Pitfall Notes
  2. 1756-PA75 ≠ PA75R

Two standard PA75 units cannot be paralleled for redundancy. PA75R kit is required for redundant systems.

  1. K suffix only indicates conformal coating. Electrical parameters and backplane load capacity are fully identical to non-K models; direct interchange is supported.
  2. Mechanical dimension: All standard 75W power supplies (PA75/PA75K/PB75 etc.) are single-slot form factor, mounted on leftmost chassis slot.

PA75R redundancy power supply cannot directly power chassis without matching redundancy adapter.

  1. Hardware revision suffix /A /B: Iterative hardware upgrades. Units with same catalog number (A/B revisions) are electrically compatible and directly interchangeable.

Tabla de selección rápida

ModeloTipo de entradaRevestimiento conformadoSoporte de redundanciaEscenarios de aplicación típicos
1756-PA7585~265VAC❌ NoAutónomoStandard control cabinets in general workshops
1756-PA75K85~265VAC✅ YesAutónomoHigh-humidity, coastal & chemical corrosive environments
1756-PA75R85~265VAC❌ NoRedundante (requiere accesorios)High-reliability production lines intolerant to shutdown
1756-PA75RK85~265VAC✅ YesRedundante (requiere accesorios)High-reliability systems in corrosive atmosphere