Módulo de bus de distribución de energía ETA EM12-T01-001

(Modelo completo: EM12-T01-001-DC24V-40A) Información básica Marca: E-T-A Germany Series: REX12-T Modular DC Power Distribution System Product Name: Main Feed Module / Power Bus Distribution Module Application: Main inlet unit for REX12-T electronic circuit protector system, which distributes DC24V positive bus power uniformly to a full row of multi-channel protectors Model Code Breakdown `EM12-T01-001` EM12: Feed ...

  • Detalles del producto

(Modelo completo: EM12-T01-001-DC24V-40A)

  1. Información básica

Marca: E-T-A Germany

Serie: REX12-T Modular DC Power Distribution System

Nombre del producto: Main Feed Module / Power Bus Distribution Module

Solicitud: Main inlet unit for REX12-T electronic circuit protector system, which distributes DC24V positive bus power uniformly to a full row of multi-channel protectors

  1. Desglose del código del modelo

`EM12-T01-001`

  1. EM12: Feed module series matched with REX12
  2. t: Standard analog signal type (without IO-Link communication; equipped with passive collective alarm contact Si)
  3. 01: Single positive pole feed version
  4. 001: Basic hardware version with standard DC24V, 40A specifications

Full suffix specifications:

CC 24 V: Tensión de funcionamiento nominal

40A: Maximum total inlet current of the module

  1. Parámetros eléctricos básicos
Elemento de parámetroValor de especificación
Tensión nominalCC 24 V, operating range DC18~30V
Max Total Inlet Current40A
No-Load Static Power ConsumptionTypical 10mA
Protección de polaridad inversaBuilt-in anti-reverse diode
Voltage Drop Buffer10EM (no false alarm for short-term voltage drop)
Alarm Contact SiNormally open passive contact; load DC30V/0.5A, minimum driving 10V/1mA
Método de cableadoTool-free push-in spring terminals, max 10mm² copper wire
Tensión soportada dieléctricaInput/Output AC2000V for 1 minuto
Resistencia de aislamiento≥100MΩ @500VDC
  1. Ambiental & Dimensiones mecánicas

Montaje: Carril DIN estándar de 35 mm

Dimensiones generales: W12.4mm × H98mm × D80mm

Temperatura de funcionamiento: -25℃ ~ +60℃

Storage/Transport Temperature: -40℃ ~ +85℃

| Clase de protección | IP20 (for cabinet internal use only) |

| Certificaciones | UL508A, CSA, CE, RoHS, ALCANZAR |

  1. Funciones centrales
  2. Central Bus Power Distribution

Connect external 24VDC power supply to this module. Built-in metal busbars on the side automatically supply power in parallel to all series-connected REX12-T circuit protectors on the right side of the rail without cross-module wiring.

  1. Global Collective Fault Alarm (Si Contact)

Once any REX12 protector trips due to overload or short circuit, the internal passive Si contact opens. It can be connected to PLC or indicator lights to realize unified fault signal for the entire row of circuits.

  1. Protección de polaridad inversa & Voltage Fluctuation Resistance

Reversed positive and negative power poles will not damage the module. The 10ms voltage drop buffer prevents false alarms caused by instantaneous voltage drop of switching power supplies.

  1. Expansion Compatibility

Unlimited series connection of REX12 single/dual-channel electronic circuit breakers on the right side. Multiple EM12-T01 modules can be connected in parallel to expand total current capacity.

  1. Escenarios de aplicación típicos

24VDC load distribution in industrial control cabinets: PLC outputs, servoaccionamientos, sensores, válvulas solenoides, robots, on-board DC power distribution for rail transit, electric control boxes for construction machinery.

  1. Comparison with Same Series Models
  2. EM12-T01-001: Standard analog type with only passive alarm contacts, sin función de comunicación
  3. EM12D-T: Intelligent communication version supporting IO-Link/Modbus RTU, capable of reading channel current and fault codes
  4. EM12-T00: Simplified version without alarm contacts
  5. PM12-T: Potential expansion module for multi-row busbar extension
  6. Standard Full Order Name

Modelo de pedido completo: EM12-T01-001-DC24V-40A

Reference Stock SKUs for Distributors: DigiKey 302-1471-ND, RS 175-0362

Complete Installation Specification for E-T-A EM12-T01-001-DC24V-40A

  1. Standard Mounting Form

Exclusive Standard Mounting: TH35-7.5 standard 35mm DIN rail (EN50022)

No base screw fixing or wall-mounted options; only DIN rail clip-on installation. Only horizontal side-by-side mounting is permitted; vertical, upside-down or tilted installation is prohibited.

Dimensiones generales: W12.4mm × H98mm × D80mm, single module width, seamlessly connected side by side with REX12 circuit breakers of the same series.

  1. DIN Rail Clip-In Installation Steps (Power Off Operation Required!)
  2. Rail Preprocessing

Adopt standard steel/aluminum TH35 rail and deburr after cutting. Mount the rail horizontally with fixing screw spacing ≤250mm to avoid shaking and deformation.

  1. Module Clip-In

Hook the upper slot of the module onto the top edge of the DIN rail, press down the bottom of the module gently until a “hacer clic” sound indicates full locking. Verify no vertical looseness and the module cannot be lifted upward.

  1. Core System Layout Rules

EM12-T01 must be installed at the far left start of the entire REX12 circuit as the main power inlet point;

Fit the side metal busbar on the right of the module against the left busbar of the next REX12 breaker, close the side connecting latch to realize parallel bus power supply;

A single EM12-T01 supports maximum 40 series-connected REX12 electronic circuit breakers;

Multi-circuit expansion: Multiple EM12-T01 modules shall supply power independently; direct side-by-side interconnection of multiple EM12 modules is forbidden.

  1. Dismantling Specification

Disconnect main power first. Use a flathead screwdriver to pry down the bottom latch and lift the module upward for removal. Disassembling series-connected modules under live power is strictly forbidden, which will cut off the busbar and cause circuit power failure.

  1. Wiring Installation (Compatible with Top/Bottom Cable Entry)

Terminal Zones & Wire Gauge Specifications

  1. LINE+ (24V main positive inlet, primary power supply)

Applicable wire: 0.5~10mm² multi-strand copper wire, M4 screw terminal, recommended torque 1.2N·m

  1. 0V (Common DC negative terminal)

Applicable wire: 0.14~2.5mm²

  1. Si (Passive collective fault alarm contact)

Applicable wire: 0.14~2.5mm², max load DC30V/0.5A

Requisitos de cableado

Both top and bottom cable entry are available; select wiring direction according to cabinet layout;

Heavy main inlet wires (≥6mm²) shall be routed separately from Si signal wires in different cable ducts to reduce interference;

Close the side interconnection latches of modules only after all wiring is completed, then switch on power.

  1. Disipación de calor & Spacing Installation Requirements
  2. Reserve ≥50mm vertical ventilation gap between upper and lower components on the same DIN rail;
  3. This module is a 40A high-current feed unit; do not mount it close to heat-generating components such as high-power power supplies, inverters and contactors;
  4. No mandatory isolation gap for densely arranged multiple modules, but cabinet ambient temperature shall be controlled ≤60℃;
  5. Natural convection ventilation must be guaranteed inside the cabinet; install cooling fans for sealed cabinets without ventilation.
  6. Reinforced Installation for Vibration & Harsh Working Conditions

For high-vibration scenarios including machine tools, rail transit and construction machinery:

  1. Install DIN rail end stops at both rail ends to prevent horizontal sliding of modules;
  2. Attach 3mm rubber shock-absorbing pads to the rail back to reduce resonance;
  3. Regularly recheck terminal torque and latch locking status.
  4. Strict Installation Prohibitions
  5. Vertical, upside-down or over 45° tilted installation is forbidden, which deteriorates heat dissipation and triggers overheat protection;
  6. Live plugging, unplugging or disassembly of series-connected modules is forbidden; busbar power cut will cause equipment shutdown;
  7. Installing EM12 in the middle or right side of REX12 circuit is forbidden, leading to bus power supply failure;
  8. Inlet wires thinner than 0.5mm² or thicker than 10mm² are forbidden, resulting in loose terminal crimping and overheating;
  9. Direct installation without protection in dusty, water mist or condensation environments is forbidden (IP20 only for cabinet internal use);
  10. Long-term total load current of single EM12 shall never exceed 40A rated value.
  11. Recommended Auxiliary Installation Materials
  12. DIN rail end fixing stops (prevent module sliding);
  13. M4 torque screwdriver (unified terminal tightening torque 1.2N·m);
  14. Crimp terminals for multi-strand wires to avoid short circuit caused by scattered copper strands;
  15. Cable duct separation: Route 24V power main wires and Si alarm signal wires separately.

Temperature Parameters of E-T-A EM12-T01-001-DC24V-40A (Original Manufacturer Manual Standard)

  1. Normal Ambient Operating Temperature

Standard Operating Range: -30 ℃ ~ +60 ℃, condensation is strictly prohibited throughout operation (EN 60204-1 cabinet application standard)

23℃ ambient temperature: Continuous full-load operation at 40A is allowed

40℃: Derate rated current to 95% (38A)

50℃: Derate rated current to 90% (36A)

60℃: Derate rated current to 85% (34A)

Dense side-by-side installation of multiple modules: Further derate current to 80% of the above value

  1. Altitude Temperature Derating (High-Altitude Working Conditions)

≤2000m: Full support for -30~+60℃ operating range

3000metro: Maximum allowable ambient temperature reduced to +55℃

4000metro: Maximum allowable ambient temperature reduced to +50℃

  1. Almacenamiento & Temperatura de transporte (Power-Off Status)

Temperatura de almacenamiento: -40 ℃ ~ +70 ℃ (with original factory packaging)

Long-Term Storage Limit: -40℃ ~ +85℃ (short-term exposure only, no power-on allowed)

  1. Instalación & Wiring Ambient Temperature

Operating environment for assembly and wiring: +5 ℃ ~ +60 ℃. Terminal disassembly and assembly are not recommended below 5℃; cold wires tend to fray and lead to unstable terminal torque.

Supplementary Usage Limitations

  1. IP20 rating only applies to cabinet internal use; cannot be directly exposed to outdoor environments with extreme temperature, water mist or dust;
  2. For sealed cabinets without forced cooling fans, long-term cabinet ambient temperature is recommended to be controlled ≤50℃;
  3. No functional failure occurs when starting at -30℃ low temperature, but preheat under no-load condition for a period before full-load operation under cold state.