Model Code Explanation Code Segment Description FBs Prefix for standard Fatek PLC series 40 Total I/O points: 40 (24 inputs + 16 outputs) MC High-performance main unit, different from MA/MB economy type and MN high-speed NC type R Output type: Salida de relé. Large contact capacity, suitable for AC and DC loads 2 Mark for 2nd ...

  • Detalles del producto

Explicación del código del modelo

Segmento de códigoDescripción
FBsPrefix for standard Fatek PLC serie
40Total I/O points: 40 (24 inputs + 16 outputs)
MCHigh-performance main unit, different from MA/MB economy type and MN high-speed NC type
RTipo de salida: Salida de relé. Large contact capacity, suitable for AC and DC loads
2Mark for 2nd generation upgraded version
C.A.Fuente de alimentación: Wide voltage range 100~240VAC
  1. Main Specifications
CategoríaEspecificaciones detalladas
Configuración de E/S24-channel 24VDC digital inputs, 16-channel relay outputs
High-speed Inputs6 channels @ 200KHz high-speed counting + 2 channels @ 20KHz medium-speed counting + 16 general inputs
High-speed OutputsRelay outputs do not support high-speed pulse. Only transistor models (T/J) provide 6 channels @ 200KHz + 2 channels @ 20KHz
Communication PortsIncorporado 1 integrated RS232/USB port (Port0), expandable up to 5 communication ports in total
Program Memory8KB (estándar), expandable to 16KB
Data Memory4KB (estándar), expandable to 8KB
High-speed Counter4 groups of Hardware High-speed Counters (HHSC), máximo. 200KHz; 4 groups of Software High-speed Counters (SHSC), máximo. 5KHz
Temporizadores0.1ms high-precision high-speed timers, supporting multiple timing modes
Instruction SetEncima 300 instructions, supporting multi-input & multi-output structures for high programming efficiency
Fuente de alimentación100~240VAC, 50/60Hz, power consumption approx. 15W.
Entorno operativoTemperatura: -20~75°C; Humedad: 10~90%RH (sin condensación)
DimensionesMontaje en carril DIN estándar, aprox. 100×100×75mm (refer to official data for exact size)
CertificacionesCE, UL certified, Cumple con las normas de seguridad industrial.
  1. Cross-brand Equivalent Comparison
MarcaModelo equivalentePrincipales diferencias
siemensS7-200 SMART SR40FBs-40MCR2-AC features higher high-speed counting frequency (200KHz vs 100KHz) and a more streamlined instruction set
mitsubishiFX3U-40MR/ES-AFatek has built-in USB + RS232 dual ports (Mitsubishi requires extra expansion); Fatek delivers better high-speed counting performance
OmrónCP1E-N40DR-ALarger program memory (8KB vs 6KB); stronger communication expansion capability (máximo. 5 puertos)
Electricidad SchneiderM221C40RMás rentable; superior high-speed counting and pulse output performance
  1. Full Model List of FBs-MC Series
ModeloI/O PointsTipo de salidaFuente de alimentaciónCaracterísticas clave
FBs-10MCR2-AC10 (6IN/4OUT)ReléC.A.Economy compact type, non-expandable
FBs-14MCR2-AC14 (8IN/6OUT)ReléC.A.Economy compact type, non-expandable
FBs-20MCR2-AC20 (12IN/8OUT)ReléC.A.Basic functional type, ampliable
FBs-24MCR2-AC24 (14IN/10OUT)ReléC.A.Basic functional type, ampliable
FBs-32MCR2-AC32 (16IN/16OUT)ReléC.A.High-performance type with built-in high-speed counting
FBs-40MCR2-AC40 (24IN/16OUT)ReléC.A.High-performance type, 6 channels 200KHz high-speed inputs
FBs-60MCR2-AC60 (36IN/24OUT)ReléC.A.High-performance type with large I/O capacity
FBs-40MCT2-AC40 (24IN/16OUT)Transistor (PNP)C.A.High-performance type, 6 channels 200KHz high-speed outputs
FBs-40MCJ2-AC40 (24IN/16OUT)Transistor (PNP)C.A.High-performance type with PNP output
FBs-40MCR2-D2440 (24IN/16OUT)ReléCC 24 VDC powered version
  1. Fallos comunes & Solución de problemas
Fenómeno de fallaPosibles causasPasos para solucionar problemas
Indicador de encendido apagadoDamaged power cable, faulty power module, abnormal input voltage1. Check power cable and socket
2. Verify input voltage within 100~240VAC
3. Inspect bulging capacitors on power module
4. Replace power module for test
No response at input pointsCableado incorrecto, defective sensor, faulty PLC input module1. Check sensor power and wiring
2. Measure input voltage (nominal 24VDC) with multimeter
3. Replace sensor for test
4. Check PLC input indicators
No action at output pointsCableado incorrecto, faulty load, damaged relay contacts1. Check load power and wiring
2. Measure output terminal voltage
3. Replace load for test
4. Check PLC output indicators
5. Replace relay module (si corresponde)
Communication failureParámetros de comunicación no coincidentes, faulty cable, damaged port1. Check baud rate, data bits and parity bits
2. Inspect cable connection and shielding
3. Replace communication cable
4. Check communication indicators
5. Try alternative communication ports
Program lossLow battery voltage, incomplete program saving, memory failure1. Check battery voltage (≥3V required)
2. Re-download program and save to EEPROM
3. Replace battery
4. Inspect memory module
  1. Solicitud & Casos de la industria

Escenarios aplicables

  1. Maquinaria de embalaje: Control conveyors, cutting, labeling and other actions; realize precise counting and positioning via high-speed counting function
  2. Maquinaria Textil: Control looms and knitting machines; support multi-axis synchronous operation
  3. Food Processing: Manage filling, sealing and sterilization processes; execute scheduled tasks via built-in calendar
  4. Machine Tool Control: Control spindle and feed of small machine tools for basic positioning
  5. Automatización de edificios: Regulate air conditioning, lighting and elevators; realize centralized monitoring via communication ports

Escenarios no recomendados

  1. High-precision high-speed positioning: Applications requiring pulse output over 200KHz (MN series recommended)
  2. Control de carga de alta potencia: Single output load exceeding relay rated capacity (typically 2A/250VAC)
  3. Severe electromagnetic interference: Environments without proper shielding, which may affect normal operation
  4. Extreme temperature: Operating temperature beyond -20~75°C

Casos de aplicación típicos

Caso 1: Automatic Packaging Line Control System

Equipo: Automatic packaging machine, conveyor, labeler

Funciones: Product counting, fixed-length film cutting, labeling position control, alarma de falla

Highlights: Precise counting via 6-channel 200KHz high-speed inputs; HMI interaction via RS232 communication; scheduled production with built-in calendar

Caso 2: Small Wastewater Treatment System

Equipo: bombas de agua, valvulas, level sensors, pH sensors

Funciones: Automatic pump start/stop based on liquid level; automatic chemical dosing according to pH value; automatic standby switch upon fault

Highlights: High-power pumps and valves controlled by relay outputs; data transmission to host computer via communication expansion modules; periodic backwashing via built-in timers

  1. Directrices de selección & Reglas de referencia rápida
  2. Consejos de selección: Match I/O points to demands; select output type by load (relay for AC/DC universal use, transistor for high-speed pulse); choose power supply per on-site condition; select series by functions (MC: alto rendimiento, MAMÁ: economy, Minnesota: high-speed positioning)
  3. Quick Rules:

R = Relay, T = NPN Transistor, J = PNP Transistor

AC = AC power supply, D24 = 24VDC power supply

2 = 2nd generation with enhanced functions and stability

MC series is standard equipped with 200KHz high-speed counter and real-time calendar

Relay Output Specifications for FBs-40MCR2-AC

Tipo de salida: Relé, 16 channels in total

Rated Current per Point: 2A (carga resistiva)

Rango de voltaje nominal:

C.A.: ≤ 250VAC

corriente continua: ≤ 30VDC

máx.. Carga resistiva:

C.A.: 500Virginia (250V × 2A)

corriente continua: 60W. (30V × 2A)

Recommended Inductive Load: ≤ 80VA (to prevent contact ablation)

Mechanical Lifespan: Aprox.. 100,000 cycles under full load

Anterior:

Próximo:

Deja una respuesta

Dejar un mensaje