OMRON C500-OD213 Rack-Mount PLC

OMRON C500-OD213 (3G2A5-OD213) Replacement Model Summary Critical Premise: No drop-in replacement module fits the original C500 rack. The C500 backplane bus is obsolete. Three upgrade approaches: spare-part maintenance, full-PLC upgrade, remote I/O retrofit. Key specifications of original unit: 64-point NPN sinking transistor output, DC12-24 V, 0.1 A per point, 8 points per COM group, dual 40-pin MIL ...

  • Detalles del producto

OMRON C500-OD213 (3G2A5-OD213) Replacement Model Summary

Critical Premise: No drop-in replacement module fits the original C500 rack. The C500 backplane bus is obsolete. Three upgrade approaches: spare-part maintenance, full-PLC upgrade, remote I/O retrofit.

Key specifications of original unit: 64-point NPN sinking transistor output, DC12-24 V, 0.1 A per point, 8 points per COM group, dual 40-pin MIL connectors.

Option A: Retain original C500 system (spare-part swap only, no rack/program modification)

(Alternative part number: 3G2A5-OD213)

Serie: SYSMAC C500 rack-mount PLC, fully obsolete; manufacturer support terminated (end-of-support March 2015). Sólo usado / surplus spare parts are available on the market.

Tipo de módulo: 64-point transistor output unit (NPN sinking type), MIL-C connector interface, no screw terminal block.

Decodificación de código modelo

CampoDescripción
C500SYSMAC‑C500 rack‑mount PLC series
ODOutput‑DC Transistor
213Module version / specification code; legacy part number 3G2A5‑OD213

Especificaciones eléctricas básicas

ArtículoPresupuesto
Output Points64 agujas, 8 points per common terminal (8 COM groups total)
Tipo de salidaNPN sinking transistor output
Load VoltageDC 12‑24 V
Corriente nominal por punto0.1 A (100 mA); max. 0.8 A per COM group; total max. 6.4 A for module
Output ResponseON ≤0.2 ms; OFF ≤0.3 ms
AislamientoPhotocoupler isolation
External Power SupplyDC5‑24V, ≥170 mA (for output circuit)
Consumo de energíaPowered via backplane bus
Interfaz2 × 40‑pin MIL flat‑cable connectors (no screw terminals)
Condiciones ambientalesTemperatura de funcionamiento: 0~55℃; temperatura de almacenamiento:‑20~70℃; humidity 35‑85%RH, condensation not permitted
PesoApprox. 0.6 kg

Principio de funcionamiento & Signal Flow

  1. Logic output signals from the CPU backplane bus are fed to the module internal logic circuit.
  2. Signals drive NPN transistors through photocoupler isolation.
  3. When transistor turns ON: load negative terminal is pulled to GND; load positive terminal connects to external DC24V.
  4. Cada 8 output points share one COM pin; COM must connect to external power-supply GND.

⚠️ The module does NOT supply output-side power; all load power must be provided externally.

Instalación & Pautas de cableado

  1. Install only in I/O slots of C500 CPU rack or expansion rack; hot-plug via backplane bus.
  2. Output signals use 40-pin MIL flat cables. Direct bare-wire connection is not allowed. A matching conversion terminal board is required.
  3. The COM terminal for each 8-point group must be reliably connected to external DC24V-GND. Different COM groups can be grounded separately or share a common ground.
  4. It is recommended to fit an external fuse (≤0.125 A) for each channel. No point-level self-recovery fuses are built-in.
  5. Para cargas inductivas (relevos, válvulas solenoides), fit free-wheeling diodes with reverse voltage ≥35 V.

Hard-Restriction Rules (Forbidden Operations)

❌ Never apply AC voltage to output channels; this will burn out the module immediately.

❌ Per-channel current must never exceed 100 mA; per-COM-group current must never exceed 0.8 A.

❌ Do not sharply bend MIL flat cables; do not disconnect connectors under power.

❌ Do not operate under condensing or corrosive-gas conditions.

Solución de problemas

SíntomaCausa principalRecurso
Program shows output ON but no response at channel1. Missing load power; 2. COM terminal not connected to GND; 3. Transistor breakdown; 4. Cableado rotoMeasure COM potential; check free‑wheeling diodes; use spare channel or replace module
Entire 8‑point group has no outputOpen‑circuit / missing ground on corresponding COM circuitInspect COM pin wiring and conversion terminal board
Spurious output / false triggeringExternal interference; missing free‑wheeling diodes; excessive power‑supply rippleApply shielding; add diodes for inductive loads; filter DC24V power supply
All module indicators offPoor backplane‑bus contact; rack power‑supply failureApagar, re‑seat module; inspect rack power unit

Opciones de reemplazo

Importante: No new module can plug-and-play into the legacy C500 rack. The C500 backplane hardware is obsolete. Two upgrade strategies are available.

Option 1: Maintain existing C500 system (spare-part-only repair)

Only option: used / salvaged C500-OD213 (3G2A5-OD213). Todo 64 channels must be tested upon receipt.

Riesgos: component aging, no OEM warranty.

Option 2: Actualización del sistema (Recomendado)

  1. CS1-series upgrade: CS1G-CPU + CS1W-OD261 (64-point transistor, MIL connector). C500 rack cannot be reused; new backplane rack required.
  2. CJ1/CJ2 compact-rack: CJ1W-OD261 (64-point output). Smaller footprint. Requires full replacement of CPU, power supply and rack; program porting is mandatory.

Nota: CJ1W-OD213 is an 8-point output module. It is NOT a replacement for C500-OD213. The two are completely incompatible. Do not confuse part numbers.

Escenarios de aplicación típicos

Legacy equipment: imported production lines from the 1990s, maquinaria de embalaje, maquinaria textil, older assembly lines. C500 racks plus OD213 modules are widely deployed to drive 64-channel solenoid valves and miniature relays.

Selection Pitfall Avoidance

  1. Distinguish part numbers: C500-ID213 is input module; OD213 is output module. They cannot be interchanged.
  2. This unit uses MIL-style connectors instead of screw terminals. When ordering spares, confirm availability of matching conversion terminal boards and flat cables.
  3. Per-channel maximum current is only 100 mA. Not for direct drive of high-current loads; use intermediate relays.

Sole solution: used / salvaged C500-OD213 (3G2A5-OD213)

Riesgos: envejecimiento de los componentes, no OEM warranty. Test all 64 output channels on arrival.

❗ Warning: CJ1W-OD213 cannot be used as replacement. It is only 8-point. Similar-sounding model number, incompatible backplane and rack; frequent procurement mistake.

Option B: Full upgrade to modern OMRON PLC (new genuine components, recomendado)

Full replacement of CPU, power supply and rack; PLC program porting required. I/O electrical characteristics match: 64-point NPN sinking, MIL-40 connectors.

Modelo de reemplazoSerieAgujasTipo de salidaObservaciones
CS1W‑OD261CS164Transistor hundimiento NPNClosest electrical match for legacy‑machine retrofits. Requires CS1 CPU + CS1 rack. C500 rack cannot be reused
CJ1W‑OD262CJ164Transistor hundimiento NPNTamaño compacto, rentable. Requires CJ1 CPU + CJ‑series rack
CJ2W‑OD262CJ264Transistor hundimiento NPNLatest‑generation CJ2 platform, enhanced performance

Parameter difference: original C500-OD213 uses 8 points per COM. CS1W-OD261 / CJ1W-OD262 adopt 16 points per COM. Field-wiring grouping for DC24V-GND must be redesigned. Per-point drive capability remains unchanged despite higher group current rating.

Option C: Remote I/O retrofit (keep original C500-CPU; remove local OD213)

Retain C500-CPU; replace local 64-point output with communication-based remote I/O. CPU and most user program can be preserved, but field wiring must be modified:

  1. Fit C500-RM201 remote master module plus remote slave unit:

SRT2-OD261: 64-point NPN transistor remote output unit with MIL connector.

Pros: CPU unchanged, minimal program adjustment. Cons: additional master hardware and remote cabling; introduces communication-link failure risk.

Option D: Domestic third-party solution (cost-oriented full-system retrofit)

No third-party module can plug into C500 rack. Complete PLC replacement is mandatory:

Domestic PLC (Inovance H3U/H5U, Xinje XD/XG etc.) + 64-point NPN sinking output module, plus MIL-40 conversion terminal board.

Entire PLC program must be rewritten. Suitable for overhaul projects with tight budget constraints.

Obtención & Retrofit Pitfall Checklist

  1. Strictly distinguish C500-OD213 (64-punto) vs CJ1W-OD213 (8-punto): similar nomenclature yet fully incompatible, a common purchasing error.
  2. CS1W-OD261 / CJ1W-OD262 use 16-point COM groups versus the original 8-point groups. Re-plan external DC24V-GND wiring during retrofit.
  3. Connectors: legacy MIL-C flat cables can be reused, but terminal-board pin-out must be cross-checked against manuals. Never power-up directly without verification.
  4. Fit free-wheeling diodes for inductive loads; keep per-point current below 100 mA.

Upgrade-path Recommendation

  1. Short-downtime urgent production recovery: install used original C500-OD213 for immediate restoration; schedule full system upgrade during future planned shutdowns.
  2. Acceptable downtime for program modification: prefer CS1W-OD261 (CS1-system), best electrical compatibility with legacy equipment.
  3. Target service-life extension of 3-5+ años: select CJ2-series CJ2W-OD262.

OMRON C500-OD213 (3G2A5-OD213) Ámbito de aplicación

Module profile: 64-point NPN sinking transistor output unit, part of the 1990s-era SYSMAC-C500 large-scale PLC platform. Designed for high-density low-current drive of solenoid valves, miniature relays and indicator lamps. Only found on ageing installed-base machinery; not for new projects.

Compatible Load Profile

Rated max. 100 mA per point for DC12-24 V loads: solenoid coils, miniature DC relays, signal lamps.

Not for direct drive of high-power contactors or heaters; intermediate relays are required for heavy-duty loads.

Dual 40-pin MIL connectors deployed with flat cables and conversion terminal boards for high-density signal wiring.

Industrias principales & Equipment Use-Cases

1️⃣ Packaging Machinery

Vertical / maquinas envasadoras horizontales, bag-making machines, filling and carton-sealing equipment

Función: bulk control of pneumatic solenoid-valve banks for cylinder actuation, alimentación, corte, pressing and material baffles. High-channel-count cylinder systems use this 64-point module to reduce rack-slot consumption.

2️⃣ Textile Machinery (mostly legacy imported units)

Air-jet looms, water-jet looms, carding machines, legacy dyeing & finishing production lines

Función: drive large numbers of pneumatic directional valves, weft-selection solenoids, indicator lamps and logic relays. Multi-piece OD213 configurations deliver massive I/O capacity for textile plants.

3️⃣ Early-generation Automotive-Component Assembly Lines

Legacy assembly lines, tooling fixtures, test stations, sistemas transportadores

Función: control pneumatic clamping fixtures, stop cylinders, status lamps and sorting actuators. Centralised solenoid-valve drive for multi-station production cells.

4️⃣ Legacy Material-Handling & Sorting Equipment

Older roller conveyors, sorters, transfer and lifting mechanisms

Función: actuate diverting baffles, sorting cylinders, change-over mechanisms and position-indicator lamps. Suited for high-density discrete-output conveyor applications.

5️⃣ Plastics & Maquinaria de caucho (imported legacy equipment)

Large injection-moulding auxiliary equipment, robotic part-removal units, rubber-vulcanisation lines

Función: drive mould core-pull solenoids, ejector actuators, material-path switch valves and alarm lamps.

6️⃣ Light-Industry Metallurgy & Building-Material Lines

Building-material production lines, auxiliary metallurgy equipment, ceramic-processing lines

Función: control pneumatic actuators, material baffles, sorting mechanisms and status indication. Frequently fitted on imported complete-plant systems of that era.

7️⃣ General-purpose imported turn-key production lines (1990-early-2000s)

Many European and Japanese turn-key plants adopted the C500 platform with C500-OD213 for high-density output. This explains strong aftermarket spare-part demand today.

Non-applicable Scenarios (hard-selection limits for this module)

  1. ❌ AC loads: DC-transistor output hardware; direct connection to AC solenoid valves will destroy the unit.
  2. ❌ Loads exceeding 100  mA per channel or high-power contactors: intermediate relays mandatory.
  3. ❌ High-vibration, condensing or corrosive-gas environments.
  4. ❌ New-build projects: full C500 platform is obsolete and must not be specified.

Operational-Maintenance Profile

Today C500-OD213 units are almost exclusively encountered in spare-part-repair scenarios: the host machine remains in service while the module has failed. Users must source used spares or execute system-modernisation projects.

AK1782HB 17689/AC220V/240V0.23A 175×175х90
PFB1224UHEC8 120х120х30
FFR0624SHE 24 В 0,40 А 80X80X30
condensador” CBB65 35 мкф на 450в”,
condensador”CBB65 450В 50 мкф”,10
condensador”CBB65 45 мкф на 450в”,
condensador”CBB61, 4мкф, 450В, 5%”
condensador”CBB61, 3мкф, 450В, 5%”
condensador”CBB61, 2,5мкф, 450В, 5%”
VNY 4 NS/NT art 481046
Temperature/indicator blockGEFRAN 40T-48-4-00-RR-0-0-0-0″
X20DI9371 Rev.GO
X20 BM11
Omron DRT1-AD04 24 VCC”
DRT2-OD16ML Разъем DRT 2NPN 24 B”
C200HW-PA204 100-240 В
C200HG-CPU43-E
CJ1W-DRM21 Omron
Omron C200HW-CLK21
C200H-OD219 OMRON
C200H DA004
C500-OD218 3G2A5-OD218
C200H-ID217SYSMAC C200H
DCN1 3
CVM1-PA208″,
CVM1-CLK21″,1
CV500-ETN01
CVM1-CPU11-V2
C500-OD213 3G2A5-OD213
C500-AD501
BH24047 315 В 230 В
BH16097/230V 300W
3IF060.6 REV D0
SLC 500 1747-BA Ser-A”,
S15-PA-5-C11-PK”
BHT 16.24A 1000/403622
BHT 16.21A 1500/403622
BHT 16.24A 5000/403622
BTK-2-111-DIN
603C01″
Sensor KEYENCE LR-TB5000
IFM/IFM IE5099 IEC3002-BPOG
IF5330 IFA3004-BPKG
IF5333 IFA3004-APKG
UNDK 20P11/099186 PNP
IFM 203 10-36V
sbfx1 12-24vac

Anterior:

Próximo:

Deja una respuesta

Dejar un mensaje