Módulo de entrada analógica OMRON CJ1W-AD04U

OMRON CJ Series 4-Channel Isolated Universal Analog Input Module (Special I/O Unit) Estado: Interrumpido. Available via spare parts and second-hand markets. Compatible with CJ1/CJ2/NJ-series PLCs. Independent signal type configuration for each of the 4 canales, inter-channel isolation. Supports mixed acquisition of temperature sensors, 4~20mA and voltage signals, widely used in industrial process measurement. ✅ Model ...

  • Detalles del producto

OMRON CJ Series 4-Channel Isolated Universal Analog Módulo de entrada (Special I/O Unit)

Estado: Interrumpido. Available via spare parts and second-hand markets. Compatible with CJ1/CJ2/NJ-series PLCs. Independent signal type configuration for each of the 4 canales, inter-channel isolation. Supports mixed acquisition of temperature sensors, 4~20mA and voltage signals, widely used in industrial process measurement.

✅ Model Explanation

CJ1W: Prefix for CJ-series Special I/O Units

ANUNCIO: Entrada analógica

04: 4 canales

Ud.: Universal multi-type input

CJ1W-AD04U: Screw terminal type; CJ1W-AD04U-SL: terminal de resorte (sin herramientas) versión

📌 Core Specifications

ArtículoParámetro
Número de canales4CH, input type configurable independently per channel
Supported InputsPlatinum RTD: Pt100, Pt1000, JPt100 (3-cable)
Par termoeléctrico: k, j, t, l, R, S, B
Actual: 4~20mA, 0~20mA
Voltaje: 1~5V, 0~5V, 0~10V
Resolución1/12000 (Voltaje/Corriente, approx.14-bit)
Conversion Cycle250ms for all 4 canales
Exactitud (25℃)Voltaje/Corriente: ±0,3% FS
Platinum RTD: The greater of ±0.3%PV or ±0.8℃
Par termoeléctrico: The greater of ±0.3%PV or ±1.5℃
AislamientoChannel-to-channel isolation; opto+transformer isolation between channels and PLC bus; Withstand voltage AC500V
Fuente de alimentaciónDC5V, Max 320mA (Powered via PLC backplane)
Dimensiones31(W.) ×90(h) ×65(D) milímetros; ≤150g
TerminalesRemovable 18-pin terminal block
Unit NumberRotary switch on front: 00~95, must not overlap with other Special I/O Units

✨ Features

  1. Universal Mixed Input: 4 channels can be set to different types, p.ej. CH1=Pt100, CH2=4~20mA, CH3=K-type thermocouple
  2. Built-in Cold Junction Compensation for direct thermocouple use; 3-wire Pt100 measurement, max single wire resistance ≤20Ω
  3. High/low limit alarm per channel, alarm delay 0~60s and hysteresis setting; open-circuit/error detection
  4. Zero/Span calibration available during operation
  5. Automatic value scaling; temperature values stored in CPU multiplied by 10 (p.ej. 256.0℃ → stored as 2560)
  6. Intercambio de datos: Allocation Relay Area (measured values + alarm flags), DM Parameter Area (rango, alarma, channel type)

🛠 Instalación & Pautas de cableado

  1. Mount on CJ CPU base or expansion base; it is a Special I/O Unit. Unit number and channel types must be configured in PLC software.
  2. 3-wire Pt100: A/B/b three wires with equal length; B and b must NOT be shorted outside the module terminals.
  3. Entrada actual: Module integrates built-in 250Ω sampling resistor, connect in series directly into the loop.
  4. Max input rating: Voltage ±15V; Current 30mA. Do NOT exceed range.
  5. Warm up for 30 mins after power on to reach rated accuracy.

⚠️ Solución de problemas (Fallos comunes)

  1. ERR Red LED: Duplicate unit number, insufficient backplane 5V supply, terminales sueltos, incorrect parameter download
  2. Fluctuating temperature reading: Cold junction interference for thermocouple, unbalanced resistance of 3 Pt100 wires, interferencia del bucle de tierra
  3. Abnormal 4~20mA reading: Incomplete closed loop, missing external transmitter power supply
  4. Open-circuit alarm: Broken sensor cable or poor contact

🔁 Referencia de selección alternativa

Same-series upgraded model: CJ1W-PH41U (Faster sampling, wider signal types; also discontinued)

New project recommendation for NX series: NX-AD4204 / NX-TC3404 (Separate or universal temperature & entrada analógica)

Simple alternative if only 4~20mA/voltage required: CJ1W-AD041 (Analog only, no thermocouple/RTD support)

📎 Supporting Document

Manual No.: W466-E1-02 (CJ1W-AD04U Operation Manual)

Compatible PLCs for CJ1W-AD04U (CJ-series Universal Analog Special I/O Unit)

This module is a CJ bus Special I/O Unit, mounted directly on CJ backplane. Restrictions apply for NJ/CP1H. Not compatible with CS series.

✅ Native Direct Compatibility (CJ1 CPUs, mount directly on CJ rack)

CJ1M: CJ1M-CPU11 / CPU12 / CPU13 (Including ETN Ethernet versions)

CJ1G: CJ1G-CPU42H / 43H /44H /45H; CJ1G-CPU42P/43P/44P/45P (Tipo de control de bucle)

CJ1H: CJ1H-CPU65H / 66H/67H

✅ Native Direct Compatibility (CPU CJ2, mount directly on CJ rack)

CJ2M: CJ2M-CPU11 /12 /13 /14 /15 /31 /32 /33 /34

CJ2H: CJ2H-CPU64 /65 /66 /67 (Incluyendo modelos -EIP Ethernet)

✅ Serie Nueva Jersey (Controlador de máquina, utilizable con advertencias)

NJ501, NJ301 y otros controladores NJ: Puede utilizar CJ1W-AD04U con bastidor CJ

Nota: Todavía se trata como unidad de E/S especial en el sistema NJ. El software de configuración es Sysmac Studio, diferente de CX-Programmer para CJ. Algunas instrucciones nativas de E/S especiales de CJ no son compatibles.

✅ CP1H (Se requiere adaptador, no se puede conectar directamente)

La CPU CP1H no tiene un backplane CJ nativo. Debe utilizar CP1W-EXT01 (Adaptador de unidad CJ). Máximo 2 Unidades de E/S especiales CJ (AD04U pertenece a esta categoría). CP1E/CP1L no compatible.

❌ Incompatible

  1. Serie CS1 (CS1G/CS1H): Bus de backplane diferente, no se puede utilizar directamente
  2. CP1E, CP1L, CPM, CQM1, C200H: No hay soporte para los módulos de E/S especiales CJ1W en absoluto
  3. PLC serie NX: NX utiliza módulos NX-AD dedicados, no se puede montar en el backplane NX

📌 Notas de uso importantes

  1. Ubicación de montaje: Bastidor de CPU o bastidor de expansión CJ. El interruptor giratorio en el frente del módulo establece el número de unidad (00~95). No hay duplicados de números de unidades de E/S especiales.
  2. Software: Programador CX para CJ1/CJ2; Sysmac Studio para Nueva Jersey
  3. Consumo de energía: DC5V, 320mamá. Calcular la capacidad de energía del backplane durante la selección.
  4. Máximo por sistema: Arriba a 40 Unidades de E/S especiales CJ (Limitado por la fuente de alimentación y la capacidad de la CPU)
  5. Pasos para configurar CJ1W-AD04U en CX-Programmer (CJ1M / CJ2M / CJ2H / CJ1G)

Requisito previo: Establecer el número de unidad giratoria de hardware (00~95). No hay duplicados entre unidades de E/S especiales. Registre este número para la configuración del software..

  1. Nuevo proyecto & Seleccionar modelo de CPU
  2. Abra CX-Programmer → Nuevo proyecto
  3. Tipo de dispositivo: CJ1M / CJ2M / CJ2H / CJ1G, seleccione la CPU correspondiente
  4. Aceptar para ingresar al espacio de trabajo del proyecto
  5. Configuración de la unidad y la tabla de E/S (Paso central)
  6. Haga doble clic [Tabla de E/S y configuración de la unidad] en el árbol del proyecto para abrir la vista del rack
  7. Haga clic con el botón derecho en la ranura del rack vacía → [Agregar unidad]
  8. Categoría: E/S analógicas generales → CJ1W-AD04U, DE ACUERDO
  9. Seleccione la unidad AD04U, haga clic derecho [Unit Settings] to open module parameter window

⚠️ Unit number must match hardware rotary switch! Ejemplo: hardware set to 0, software unit number =0

  1. Channel Parameter Configuration (Entrada universal, independent per channel)

Each channel can independently select sensor type: Pt100/Pt1000/JPt100 / K/J/T/L/R/S/B thermocouple /4~~20mA /0~~10V etc.

Channel Enable: Check to activate unused channels; disable unused channels otherwise alarms easily triggered

Tipo de entrada: Dropdown to select sensor/range

Temperature Unit: ℃ / ℉ (for temperature inputs)

Alarm Settings: Límite superior/inferior, alarm delay 0~60s, histéresis; enable open-wire detection

Zero/Span Calibration: Optional online calibration

Averaging Processing: Reduce signal fluctuation (opcional)

Register Allocation Rule:

Unit No. norte:

CIO: Starts at `CIO 2000 + 100×N`

CH1 Measured Value: `2000+100N`

CH2 Measured Value: `2001`

CH3 Measured Value: `2002`

CH4 Measured Value: `2003`

Alarm flags and status bits in subsequent bits

DM Parameter Area: `D20000 + 100×N` stores channel type, range parameters

Ejemplo: Unit No.=0

CH1 Value → CIO2000; CH2→CIO2001; CH3→CIO2002; CH4→CIO2003

  1. Download and Online Verification
  2. After parameter setup, [Transfer to PLC] (Download I/O table + special unit parameters together)
  3. Switch PLC to Monitor mode and watch CIO channel readings
  4. No ERR red light = basic configuration OK. ERR red light causes: mismatched unit number, insufficient backplane 5V, incorrect parameters

Nota importante: AD04U is a Special I/O Unit. Parameters download into PLC memory and auto-load to module on power-up. No initialization instructions required in user program.

  1. Restrictions for CP1H + CP1W-EXT01 + CJ1W-AD04U

Hardware architecture: CP1H CPU + CP1W-EXT01 Adapter + CJ Backplane + CJ1W-AD04U

✅ Permitido

  1. Máximo 2 Unidades de E/S especiales CJ (AD04U counts as Special I/O; combination: 1×AD04U + otra E/S especial de CJ)
  2. Solo admite unidades de E/S especiales CJ / Unidades de bus de CPU; E/S básicas de CJ (CJ1W-ID/OD) no se puede montar
  3. La configuración de CX-Programmer es casi idéntica a la configuración de CJ: Agregue AD04U en la tabla de E/S y establezca el número de unidad

❌ Limitaciones estrictas

  1. Cantidad máxima: 2 unidades, no se puede sumar el 3er. Se permiten dos AD04U, pero se debe validar el presupuesto actual del backplane de 5 V (320mA para AD04U)
  2. Longitud de extensión: Sólo un segmento de la base CJ después de EXT01; No hay más bases de expansión CJ ni conexiones en cascada de cables de expansión
  3. Las instrucciones de E/S especiales de CJ avanzadas parciales no están disponibles; Las funciones básicas de adquisición y alarma del AD04U funcionan normalmente.
  4. Capacidad del programa CP1H y espacio de direcciones del CIO limitado; evitar grandes números de unidades, recomendado 0, 1
  5. Fuente de alimentación: 5La alimentación V para el bastidor CJ después de EXT01 debe tener capacidad suficiente. Dos AD04U consumen un total de 640 mA, reserva ≥30% de margen que representa el consumo base
  6. CP1E / CP1L no puede utilizar EXT01, sólo CP1H (Modelos XA/X)
  7. DIRECCIÓN: CIO y DM compensan las mismas reglas que CJ, pero el área del CIO de CP1H es limitada, número de unidad ≤15 recomendado

⚠️ Errores comunes

  1. Falta el terminador CJ1W-TER01 al final del bastidor EXT01 (suministrado con adaptador, Error de E/S si falta)
  2. Número de unidad duplicado en dos módulos → LED rojo ERR
  3. Selección incorrecta: Intento de montar la unidad básica DI/DO CJ1W-ID211 después de EXT01 → No reconocido
  4. Corriente insuficiente de 5 V en la placa posterior: ERR parpadea después del encendido, sin datos de medición

Procedimiento de depuración simplificado para CP1H + AD04U

  1. Cableado de hardware: Monte CP1W-EXT01 en el puerto lateral CP1H → base CJ → AD04U, Instale el terminador CJ1W-TER01 en el extremo del bastidor.
  2. Establezca el número de unidad giratoria AD04U en 0 (o 1)
  3. Nuevo proyecto CP1H en CX-Programmer, abrir tabla de E/S, agregue CJ1W-AD04U debajo del bastidor de expansión EXT01, hacer coincidir el número de unidad con el hardware
  4. Set 4-channel input types and download I/O table + parámetros
  5. Online monitor CIO area to read temperature/analog signals

Engineering Application Cases of OMRON CJ1W-AD04U (Universal Analog Input Module)

Ventajas principales: Independent 4-channel setup, inter-channel isolation, mixed acquisition of Pt100/thermocouple/4~~20mA/0~~10V. Ideal for small reactors, esterilizadores, heat exchange stations, tratamiento de agua, ovens and other mixed-sensor process applications.

PLC Host: CJ2M / CJ1M / CJ1G; HMI options: NB/NS Touchscreen, CX-Supervisor SCADA

Caso1: Temperatura & Pressure Monitoring for Small Reactor (Typical AD04U Application in Chemical/Pharmaceutical)

Project Requirements

Reactor multi-signal acquisition:

CH1: Pt100 (Vessel temperature 0~~200℃, 3-wire RTD)

CH2: Termopar tipo K (Jacket temperature 0~~400℃)

CH3: Pressure transmitter 4~~20mA (0~~1.0MPa)

CH4: Level transmitter 4~~20mA (0~~2m liquid level)

Funciones: Limit alarm, open-wire detection, real-time HMI display, over-temperature interlock output via DO module.

Arquitectura de hardware

CJ2M-CPU13 + CJ1W-AD04U (Unidad 0) + CJ1W-OD211 Digital Output + NB Touchscreen

AD04U handles mixed signals across four channels, eliminating separate temperature module and regular AI module to save rack slots.

Puntos clave de configuración

  1. Add CJ1W-AD04U in CX-Programmer I/O Table; hardware rotary switch 00
  2. Channel setup

CH1: Pt100, open-wire detection enabled; linearization onboard, stored value ×10 (256.0℃→2560)

CH2: K thermocouple, built-in cold junction compensation

CH3: 4~~20mA, range 0~~1MPa

CH4: 4~~20mA, range 0~~2m

  1. DIRECCIÓN (Unidad 0)

CH1 Temperature: CIO2000; CH2: CIO2001; CH3 Pressure: CIO2002; CH4 Level: CIO2003

  1. Programa: SCL scaling, high/low limit comparison; channel open-wire bit triggers alarm, over-temperature triggers DO to cut heating.

Field Debugging Issues

Thermocouple shield cable single-end grounding. Ground loop and temperature fluctuation occur with both ends grounded;

Unequal resistance of three Pt100 wires leads to reading drift, keep three wires same length;

30-minute module warm-up before reaching rated accuracy.

Caso2: Food Sterilizer (Steam Sterilization Equipment)

Requisitos

Multi-point temperature measurement inside chamber, monitor cavity temperature and steam pressure for pasteurization / high-temperature sterilization process logging.

CH1: Pt100 Chamber Temperature 0~~135℃

CH2: Pt100 Product Core Temperature

CH3: 4~~20mA Steam Pressure 0~0.4MPa

CH4: Reserved for cooling water K thermocouple

System Features

Sterilization site has heavy electrical interference, inter-channel isolation of AD04U delivers better noise immunity than non-isolated regular AI. Data uploaded to touchscreen to save process curves for food batch traceability.

Expansión: Add CJ1W-DA021 analog output module for PID temperature control to modulate steam regulating valve.

Caso3: Estación de intercambio de calor (climatización / District Heating Substation)

Requisitos

Primary supply temp, primary return temp, supply pressure, return pressure

CH1: Pt100 Primary Supply

CH2: Pt100 Primary Return

CH3: 4~~20mA Supply Pressure 0~~1.6MPa

CH4: 4~~20mA Return Pressure 0~~1.6MPa

SOCIEDAD ANÓNIMA: CJ1M-CPU12; Remote SCADA, heat calculation, high/low pressure and overtemperature alarm.

Puntos clave

Sensors distributed over long wiring distances in heating stations. Built-in open-circuit detection alerts maintenance staff immediately on probe failure.

Caso4: CP1H+CP1W-EXT01+CJ1W-AD04U Low-cost Water Tank Temperature & Monitoreo de nivel

Hardware

CP1H-X40DT-D + CP1W-EXT01 Adapter + CJ Base + CJ1W-AD04U + CJ1W-TER01 Terminator

Limitación: máx. 2 Unidades de E/S especiales CJ; solo 1 AD04U used here

Canales:

CH1: 4~~20mA Liquid Level 0~~5m

CH2: Pt100 Water Temperature

CH3, CH4 Reserved

Solicitud: Water purification / sewage tank, pump start-stop interlock by liquid level, alarma de sobretemperatura.

Nota: No CJ basic DI/DO allowed after EXT01, only Special I/O; calculate 5V backplane consumption (320mA for AD04U).

Caso5: Oven / Heat Treatment Furnace Monitoring (K Thermocouple Dominant)

CH1/CH2 K thermocouple for multi-point furnace temperature; CH3 4~~20mA fan wind pressure; CH4 0~~10V speed potentiometer.

Suitable for small heat treatment and drying ovens. Supports thermocouple + Voltaje + current within single module, which is the biggest advantage of AD04U. Regular CJ1W-AD041 only handles 4~20mA/voltage and does not support RTD/thermocouple.

General Programming Guidelines for CJ1W-AD04U

  1. Temperatura (Pt100/Thermocouple): Onboard linearization, raw value = actual temperature ×10;

Ejemplo: CIO2000=1250 → 125.0℃

  1. 4~20mA Raw Range: 4mA corresponds to 1/12000, 20mA corresponds to full scale; SCL instruction scales engineering value in PLC program
  2. Alarmas: Module hardware provides per-channel high/low limit and open-wire bits in subsequent CIO bits, no need to write comparison logic for open-circuit detection.

Guía de selección (When to choose AD04U)

✅ Adecuado: Mixed sensor types (Pt100, thermocouple plus 4~~20mA transmitters), inter-channel isolation required, ≤4 points

❌ No apto: Pure 4~~20mA acquisition with many points (CJ1W-AD081 recommended); muestreo de alta velocidad (CJ1W-PH41U recommended)

Summary of Common Faults in Field Commissioning

  1. ERR Red LED: Duplicate unit number, insufficient backplane 5V power, I/O table parameter not downloaded
  2. Jumpy temperature reading: Shield cable grounded at both ends, sensor cables routed together with power cables
  3. 4~20mA locked at 4mA: Transmitter loop open, 2-wire transmitter wiring error
  4. Pt100 reading drift: Unequal resistance among three wires

Anterior:

Próximo: