OMRON S8VK-T12024 DIN Rail Power Supply - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

 OMRON S8VK-T12024 DIN Rail Power Supply - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

SOCIEDAD ANÓNIMA/

OMRON S8VK-T12024 DIN Rail Power Supply

S8VK: OMRON S8VK series switching power supply T: Model for three-phase AC400V input 120: Rated power 120W 24: DC24V output Core Specifications Item Parameter Rated Input Three-phase AC380~480V; Operating range AC320~576V (works with three-phase or two-phase input), DC 450~810V Rated Output DC24V, 5A, 120W Peak Output 120% sobrecarga (6A) auto-recovery protection Efficiency Typical 89% Mounting DIN35 ...

  • Detalles del producto

S8VK: OMRON S8VK series switching fuente de alimentación

t: Model for three-phase AC400V input

120: Rated power 120W

24: DC24V output

Especificaciones principales

ArtículoParámetro
Entrada nominalThree-phase AC380~480V; Operating range AC320~576V (works with three-phase or two-phase input), DC 450~810V
Salida nominalCC 24 V, 5A, 120W.
Salida máxima120% sobrecarga (6A) auto-recovery protection
EficienciaTípico 89%
MontajeMontaje en carril DIN35, terminales de tornillo
Dimensiones generalesH125 × W40 × D113 mm
EnfriamientoRefrigeración por convección natural, sin ventilador
Protección de ingresoIP20
Temperatura ambiente de funcionamiento-40~+70℃ (derating required at high temperature, no condensation or icing)
Funciones de protecciónsobrecorriente (sobrecarga, auto-recovery), sobretensión (latch-off, reset by power cycle), undervoltage alarm
Funciones adicionalesmáx.. 2 units in series (external diode required); Conformal coated PCB optional; MTBF≥135,000 hours

Definición de terminal

  1. L1, L2, L3: Three-phase AC input
  2. educación física: Tierra protectora
  3. +V, -V: DC24V output
  4. V.ADJ: Output voltage trim potentiometer
  5. DC ON: Green indicator for normal output

Escenarios de aplicación típicos

Three-phase industrial control cabinets, maquinas herramientas, equipo de embalaje, HVAC automatic control, 380V powered automated production lines, supplying DC24V for PLCs, sensores, relays and valve islands.

In-series Comparison

S8VK-T12024: 120W. / 5A / Width 40mm

S8VK-T24024: 240W /10A / Width 60mm

S8VK-T48024: 480W /20A / Width 95mm

S8VK-T96024: 960W /40A

Referencia de selección alternativa

  1. OMRON single-phase version: S8VK-C12024 (also 120W/24V, single-phase 220V input, no confundas)
  2. Alternativas domésticas: Meanwell DRT-120-24, Delta DRP0120, Phoenix Contact three-phase 24V/5A rail power supply

Pautas para la solución de problemas

  1. DC indicator off: Check three-phase input voltage, PE earthing, input circuit breaker; failure to start if two phases are missing
  2. Voltage drop under load: Load exceeds rated 5A; high-temperature derating; low input voltage
  3. Intermittent undervoltage alarm: Main circuit voltage fluctuation, loose terminal wiring
  4. Overvoltage latch-off: Triggered by output overvoltage, restore by power cycling; check for load short circuit / reverse voltage

OMRON S8VK-T12024 Detailed Technical Specifications

Three-phase 380V input DIN rail switching power supply, rated 120W DC24V/5A

  1. Input Specifications
ArtículoParámetro
Rated Three-phase InputAC380~480V, 50/60Hz
Three-phase Operating Voltage RangeAC320~576V
Two-phase Input RangeAC340~576V (two-phase operation supported)
Entrada CCDC450~810V
Corriente de entradaAprox.. 0.45A @ AC400V full load
Corriente de irrupciónInternally limited
Recommended Circuit BreakerB/C/D type, 5~20A (trifásico); 2~20A (bifásico)
Recommended Fuse600Vcc, 5A fast blow
  1. Output Specifications
ArtículoParámetro
Tensión de salida nominalCC 24 V
Corriente de salida nominal5A
Potencia nominal120W.
Output Adjustment Range24V±10% (V.ADJ potentiometer)
Ripple & Ruido120mVp-p (típico)
Capacidad de sobrecargaOverload protection activates at 121% corriente nominal, auto-recovery
Protección contra sobretensiónTriggered at approx.130% rated voltage, latches off output, reset by power cycle
Undervoltage AlarmBuilt-in undervoltage detection signal
Operación paralelaMultiple units parallelable (follow current-sharing requirements)
Series Operationmáx.. 2 units in series, external isolation diode required
  1. Aislamiento & Tensión soportada
  2. Input ↔ Output: AC3000V, 1mín., cut-off current 20mA
  3. Input ↔ PE: AC2500V, 1mín., cut-off current 20mA
  4. Output ↔ PE: AC1000V, 1mín., cut-off current 30mA
  5. Resistencia de aislamiento: ≥100MΩ (DC500V, between input/output/PE)
  6. Condiciones ambientales
ArtículoParámetro
Temperatura de funcionamiento-40℃~+70℃ (derating required above 50℃, no condensation or icing)
Temperatura de almacenamiento-40℃~+85℃
Humedad relativa0~95% HR (operación & almacenamiento, sin condensación)
Resistencia a las vibraciones10~55Hz, amplitude 0.375mm, 2 hours per axis for 3 ejes
Resistencia a los golpes150m/s², 3 shocks per direction for 6 directions
Método de enfriamientoRefrigeración por convección natural, sin ventilador
Protección de ingresoIP20 (para uso interno del gabinete)
  1. Especificaciones mecánicas

Montaje: DIN35mm rail mounting

Dimensiones: H125 × W40 × D112.2 mm

Terminales: Screw-type terminals

Peso: Aprox.. 600gramo

Opcional: Conformal coated PCB version (anticorrosión & a prueba de polvo)

  1. Fiabilidad & Certificaciones

MTBF: ≥135,000 hours

Indicador: Green DC ON lamp, illuminates when output ≥80~90% rated voltage

Certificaciones de seguridad: UL, CSA, CE and other global industrial standards

  1. Definición de terminal
  2. L1, L2, L3: Three-phase AC input
  3. educación física: Tierra protectora (must be earthed reliably)
  4. +V, -V: DC24V output
  5. V.ADJ: Output voltage trim potentiometer
  6. Summary of Protection Functions

✅ Overload protection (auto-recovery)

✅ Short-circuit protection (auto-recovery)

✅ Output overvoltage protection (latch-off, reset by power cycle)

✅ Built-in undervoltage monitoring

✅ Input surge suppression

  1. Notas críticas
  2. Derating is mandatory when ambient temperature>50℃
  3. Load capacity will be limited under two-phase input
  4. External diodes are mandatory for series connection; direct series connection is prohibited
  5. PE terminal must be reliably earthed to comply with safety standards

OMRON S8VK-T Three-phase DIN Rail Power Supply Full Series List

S8VK-T: Three-phase AC380~480V input, DC24V output, Montaje en carril DIN35, fanless natural cooling; sufijo -400 = conformal coated PCB (for dust, moisture and corrosive environments)

Standard Models

ModeloPotencia nominalProducciónCorriente nominalPeak Boost CurrentDimension W×H×D(milímetros)
S8VK-T12024120W.CC 24 V5A6A40 × 125 × 112.2
S8VK-T24024240W.CC 24 V10A12A60 × 125 × 140
S8VK-T48024480W.CC 24 V20A24A95 × 125 × 140
S8VK-T96024960W.CC 24 V40A48A135 × 125 × 170

Conformal Coated (Anti-corrosion) Modelos

Coated ModelCorresponding Standard ModelFuerzaObservaciones
S8VK-T12024-400S8VK-T12024120W.PCB with coating, for dusty and humid environments
S8VK-T24024-400S8VK-T24024240W.PCB with coating
S8VK-T48024-400S8VK-T48024480W.PCB with coating
S8VK-T96024-400S8VK-T96024960W.PCB with coating

Lista de accesorios

Modelo de accesorioDescripciónApplicable Units
S82Y-VK10FFront mounting bracketT12024 (120W.)
S82Y-VK20FFront mounting bracketT24024 / T48024 (240W., 480W.)
S8VK-R10Redundancy module 10AFor power redundancy with S8VK-T
S8VK-R20Redundancy module 20AFor power redundancy with S8VK-T

Common Specifications for Entire S8VK-T Series

  1. Aporte: Three-phase AC380~480V; operating range AC320~576V; two-phase input supported; DC450~810V DC input
  2. Producción: CC 24 V, adjustable range 24V±10% (V.ADJ potentiometer)
  3. Protección: Sobrecarga / cortocircuito (auto-recovery), output overvoltage latch-off (reset by power cycle), built-in undervoltage monitoring
  4. Ambiente: Operating temperature -40℃ ~ +70℃, derating required above 50℃; fanless natural cooling; IP20 cabinet use
  5. Tensión soportada: Input↔Output AC3000V 1min; Input↔PE AC2500V 1min; Output↔PE AC1000V 1min
  6. Montaje: DIN35 rail, terminales de tornillo; multiple units parallelable for capacity expansion; máximo. 2 units in series (external diode required)

Consejos de selección rápida

All models are single DC24V output. S8VK-T series has no other voltage options (12V/48V not available in T series)

Model without -400: Standard PCB for normal control cabinets; with `-400`: Coated board for dusty, humid and corrosive gas environments

S8VK-T is three-phase power supply, do not confuse with single-phase S8VK-C / S8VK-G

Redundant power supply requires separate S8VK-R redundancy module

OMRON S8VK-T Three-phase DIN Rail Power Supply Cross-Brand Model Comparison Table

Matching prerequisites: Three-phase AC380~480V input, DC24V output, DIN35 rail mount, fanless natural cooling. Grouped into【Premium International Brands】【Taiwan Brands】【Domestic Industrial Brands】; replacement rating marked. ⚠️Differences exist in dimension, disposición de terminales, BOOST capability and PCB coating. Drawings must be verified for direct replacement.

OMRON Original ModelSpec.Contacto FénixMeanwellMeanwell RemarkssiemensDelta
S8VK-T12024 (120W/5A)3-phase 380V input 24V 5AQUINT4-PS/3AC/24DC/5 PN:2904620TDR-120-24DRT-120 obsolete; TDR is replacement; three-phase input, sin ventilador6EP3436-8SB00-0AY0DRL-24V120W3ENA
S8VK-T24024 (240W/10A)3-phase 380V input 24V 10ATRIO-PS/3AC/24DC/10 2866459TDR-240-24DRT-240 obsolete; new TDR, paralelo6EP3437-8SB00-0AY0DRL-24V240W3ENA
S8VK-T48024 (480W/20A)3-phase 380V input 24V 20ATRIO-PS/3AC/24DC/20 2866462TDR-480-24DRT-480 obsolete; new TDR, parallel expansion supported6EP3438-8SB00-0AY0DRL-24V480W3ENA
S8VK-T96024 (960W/40A)3-phase 380V input 24V 40ATRIO-PS/3AC/24DC/40 2866404TDR-960-24DRT-960 obsolete; new TDR, max 40A output6EP3440-8SB00-0AY0DRL-24V960W3ENA

Versión con revestimiento conformado (-400 Anti-corrosion) Referencia cruzada

S8VK-Txxx24-400 (PCB conformal coating for dusty/humid/corrosive environments)

  1. Contacto Fénix: QUINT4 series Coated version (coating option via suffix)
  2. Meanwell TDR: Custom conformal coating available (standard TDR uncoated, custom order required)
  3. siemens: SITOP PSU coated version
  4. Doméstico: RDW series with three-proof coating

Redundancy Module Cross Reference (S8VK-R10 / S8VK-R20)

OMRON Redundancy ModulePhoenix RedundancyMeanwell RedundancySiemens Redundancy
S8VK-R10 (10A)QUINT-DIODE/12-24DC/10DR-RDN206EP1961-3BA01
S8VK-R20 (20A)QUINT-DIODE/12-24DC/20DR-RDN206EP1961-3BA21

Key Difference Notes (Enfoque de selección)

  1. BOOST Peak Capacity

S8VK-T fixed 120% Power Boost for all models; Phoenix QUINT4 has stronger dynamic BOOST for short-time peak loads; Meanwell TDR uses conventional constant current limiting.

  1. Características de entrada

OMRON S8VK-T supports two-phase input. Some competitors’ three-phase power supplies do not support two-phase single-side power supply, verify carefully for retrofit projects.

  1. Dimensión & Instalación

OMRON S8VK-T is compact narrow-width design; Phoenix TRIO and Siemens SITOP models of same power are generally wider. DIN rail mounting space is the most common bottleneck for direct replacement.

  1. Protection Logic Difference

S8VK-T overvoltage protection is output latch-off, reset by power cycle. Some competitors adopt hiccup auto-recovery, which may affect control system logic.

  1. Rango de temperatura

OMRON S8VK-T features -40℃ cold start advantage; some Taiwan and domestic brands have lower limit of -30℃, use caution for cold-region equipment.

Selection Recommendation Strategy

Equipos de exportación, alta confiabilidad, cold environment: Prefer Phoenix QUINT4 / Siemens SITOP

Prioridad de costos, ordinary domestic automation equipment: Meanwell TDR series

Budget control for domestic projects: Domestic RDW three-phase DIN rail power supply

Anterior:

Deja una respuesta

Dejar un mensaje