The GV2P32 is a 3-pole thermal-magnetic motor circuit breaker (MPCB) from Schneider TeSys GV2 series. It features an adjustable current setting of 24-32A, compatible with 15kW @ 400V three-phase motors. Providing dual protection against overload and short circuit, with IP20 protection degree, it is widely applied in industrial motor control circuits.
- Explicación del código del modelo
| Segmento de código | Significado | Descripción |
| GV2 | Serie de productos | TeSys GV2 series motor circuit breakers for motor overload and short-circuit protection |
| PAG | Tipo de operación | Rotary knob manual control, imported version (domestic equivalent: GV2PM series) |
| 32 | Clasificación actual | Adjustable setting range: 24-32A, for motor circuits with rated current up to 32A |
Full Model Definition: GV2P32 = Schneider GV2 series, rotary knob type, 32A rated motor circuit breaker
- Especificaciones técnicas básicas
| Categoría | Presupuesto | Observaciones |
| Características generales | ||
| Tipo de producto | 3-pole thermal-magnetic motor circuit breaker (MPCB) | Cumple con IEC 60947-4-1 |
| Rango de corriente ajustable | 24-32A (ajustable) | Thermal trip with ambient temperature compensation |
| polacos | 3PAG (trifásico) | Designed for three-phase motor protection |
| Modo de operación | Rotary knob manual control | With ON/OFF indicator and lockable function |
| Parámetros eléctricos | ||
| Tensión operativa nominal | 230-690V y, 50/60Hz | Suitable for global industrial power grids |
| Compatible Motor Power | 15kW @ 400/415V, 50/60Hz | Maximum applicable power under standard operating conditions |
| Magnetic Trip Threshold | 12×In = 384A (Instant short-circuit protection) | Fast disconnection upon short-circuit faults |
| Capacidad de ruptura de cortocircuito | 10kA @ 400V, 50Hz | Meets industrial standard requirements |
| Tipo de terminal | Terminales de tornillo | Applicable copper wire cross-section: 1.5-25mm² |
| Físico & Parámetros ambientales | ||
| Grado de protección | IP20 | Evita el acceso de los dedos a piezas vivas. |
| Tipo de montaje | Carril DIN estándar de 35 mm | Modular installation, ahorro de espacio |
| Dimensiones (Ancho×Alto×Profundidad) | 45×85×95mm | Compact design for distribution cabinets |
| Temperatura de funcionamiento | -25℃ ~ +60℃ | Amplio rango de temperatura para entornos industriales. |
| Certificaciones | CCC, UL, CSA, CAO, Marine Classification (DNV, GL, BV), ATEX | Multiple certifications for global application |
| Información de pedido | ||
| Manufacturer Part No. | GV2P32 | Official Schneider model |
| Standard Order Code | GV2P32 | Original imported version |
- Full GV2P Series Model List
| Modelo | Rango de corriente ajustable | Compatible Motor Power (400V) | Corriente de disparo magnético |
| GV2P01 | 0.16-0.25A | 0.06kilovatios | 3.0A |
| GV2P02 | 0.25-0.4A | 0.12kilovatios | 4.8A |
| GV2P03 | 0.4-0.63A | 0.25kilovatios | 7.6A |
| GV2P04 | 0.63-1A | 0.37kilovatios | 12A |
| GV2P05 | 1-1.6A | 0.75kilovatios | 19A |
| GV2P06 | 1.6-2.5A | 1.1kilovatios | 30A |
| GV2P07 | 2.5-4A | 1.5kilovatios | 48A |
| GV2P08 | 4-6.3A | 3kilovatios | 76A |
| GV2P09 | 6.3-10A | 4kilovatios | 120A |
| GV2P10 | 10-16A | 7.5kilovatios | 190A |
| GV2P14 | 13-18A | 11kilovatios | 216A |
| GV2P16 | 16-24A | 11kilovatios | 288A |
| GV2P20 | 20-32A | 15kilovatios | 384A |
| GV2P32 | 24-32A | 15kilovatios | 384A |
| GV2P40 | 32-40A | 18.5kilovatios | 480A |
- Modelos de reemplazo & Comparación de competidores
4.1 Internal Schneider Replacements
| Modelo Original | Modelo de reemplazo | Diferencias | Escenarios de aplicación |
| GV2P32 (Importado) | GV2PM32C (Doméstico) | Different origin, minor certification differences; profundidad: 91milímetros (GV2P: 95milímetros) | Domestic projects, cost-sensitive applications, CCC certification required |
| GV2P32 | GV2ME32 (Domestic push-button type) | Push-button operation, parámetros eléctricos idénticos | Applications requiring push-button control, limited budget |
| GV2P32 | GV3P32 (Upgraded series) | Higher breaking capacity and enhanced functions | Environments with high short-circuit risk, advanced protection required |
4.2 Cross-brand Competitor Comparison
| Marca | Modelo | Rango actual | polacos | Magnetic Trip Ratio | Principales diferencias |
| Schneider | GV2P32 | 24-32A | 3PAG | 12×In | Multiple certifications including marine approval, IP20 |
| TEJIDO | MS325-32 | 24-32A | 3PAG | 12×In | Capacidad de ruptura: 15el, larger dimensions |
| siemens | 3RV2031-4KA10 | 24-32A | 3PAG | 13×In | Optional electronic trip, precio más alto |
| Eaton | PKZM0-32 | 24-32A | 3PAG | 12×In | Spring terminals for easy installation |
| chint | NM1-63S/3300 | 25-32A | 3PAG | 10×In | Ventaja de costos, domestic alternative |
- Entornos de aplicación & Casos típicos
5.1 Aplicaciones recomendadas
Control de motores industriales: Main circuit protection for three-phase motors such as pumps, fans, compresores y transportadores
Equipos OEM: Supporting machine tools, maquinaria de embalaje, printing machines and textile machinery
Building Electrical Systems: Protection for critical motors including air conditioning units, fire water pumps and drainage pumps
Marina & Ingeniería costa afuera: Compliant with marine classification standards for ship power systems
Hazardous Areas: ATEX certified for motor protection in non-explosion-proof zones
5.2 Not Recommended Applications
Single-phase Motors: 3-pole design not suitable for single-phase circuit protection
Frequent Start-Stop Operations: Más que 10 cycles per hour will shorten service life
High Altitude (>2000metro): Derating required (10% reduction per 1000m rise)
Ambientes de vibración severa: Extra reinforcement needed to avoid false tripping
Corrosive Environments: IP20 protection is insufficient; additional enclosure is required
5.3 Casos de aplicación típicos
Caso 1: Water Treatment Plant Pump Protection
Equipo: 3 sets of 15kW submersible three-phase pumps (400V)
Configuración: GV2P32 + LC1D32 Contactor + LRD3322 Thermal Overload Relay (redundant protection)
Outcome: Prevented 3 motor overload faults and 1 short-circuit fault, extending equipment service life by 2 años
Caso 2: Conveyor System in Automobile Manufacturing Plant
Equipo: 12 conveyor lines each equipped with 15kW motor
Configuración: GV2P32 linked with Schneider PLC
Características: Rotary knob enables quick on-site reset and reduces downtime
- Solución de problemas & Maintenance Manual
6.1 Fallos comunes & Soluciones
| Fenómeno de falla | Posibles causas | Soluciones |
| Frequent thermal tripping | 1. Sobrecarga del motor | 1. Check motor load and eliminate mechanical jamming |
| 2. Improper low current setting | 2. Set current to 1.1 times motor Full Load Current (FLA) | |
| 3. Temperatura ambiente excesivamente alta | 3. Mejorar la ventilación y bajar la temperatura ambiente. | |
| 4. Loose terminals causing overheating | 4. Inspect and tighten terminals | |
| Instant magnetic tripping | 1. Circuit short circuit | 1. Power off and test circuit insulation |
| 2. Damaged motor winding insulation | 2. Measure winding resistance and replace faulty motor | |
| 3. Arc short circuit inside contactor | 3. Inspect contactor contacts and replace if necessary | |
| No cerrar | 1. Tripping mechanism not reset | 1. Turn knob to OFF position then re-close |
| 2. Damaged rotary knob | 2. Check knob linkage and replace damaged parts | |
| 3. Internal mechanical failure | 3. Arrange professional maintenance or replace the breaker | |
| No hay salida después del cierre | 1. Burned internal contacts | 1. Apagar, inspect main contacts and replace defective unit |
| 2. Cableado incorrecto | 2. Verify wiring to ensure correct three-phase connection | |
| 3. Faulty tripping mechanism | 3. Check tripping mechanism and replace if needed |
6.2 Maintenance Procedures
- Inspección diaria (Semanalmente)
Check knob position and status indication
Look for abnormal heat, odor or noise
Confirm all terminals are tightly connected
- Mantenimiento de rutina (Cada 6 Meses)
Power off and remove dust with dry compressed air
Inspect main contacts for burning and oxidation
Test tripping function by simulating overload and short circuit conditions
- Annual Maintenance
Check lubrication of internal mechanical components
Verify accuracy of current setting
Retighten all electrical connections
6.3 Quick Diagnosis Tips
Thermal trip? Check load and current setting.
Magnetic trip? Locate short circuit and test insulation.
Fail to close? Reset first; replace for mechanical faults.
Sin salida? Inspect contacts and wiring.
- Selección & Pautas de instalación
7.1 Reglas de selección
Coincidencia actual: Motor FLA must fall within 24-32A; recommended setting: FLA × 1.1
Coincidencia de poder: Standard solution for 15kW @ 400V three-phase motors
Coordinación de Protección: Use with contactors and fuses to ensure selective protection
Ambient Derating: Reducir 1% per ℃ above 40℃
7.2 Notas de instalación
Dirección de montaje: Instalación vertical (allowable deviation: ±15°) for normal tripping operation
Autorización: Reserve 10mm space on left & right sides, 20mm on top & bottom for heat dissipation
Estándar de cableado: Copper wire with cross-section 1.5-25mm²; par de apriete: 6-8Nuevo Méjico
Locking Function: Padlock can be fitted to prevent accidental operation, Cumpliendo con las normas de seguridad.
- Production Status & Soluciones de actualización
Current Status of GV2P32: In production, no discontinuation plan (as of June 2026)
Mejora & Opciones de reemplazo:
- Actualización funcional: GV3P32 (higher breaking capacity and extra protection functions)
- Alternativa Doméstica: GV2PM32C (lower cost with equivalent performance)
- Intelligent Upgrade: TeSys T series (with communication for remote monitoring)