Modelo: LADN20
Marca: Electricidad Schneider
Serie de productos: Matching accessories for TeSys D / TeSys Deca contactors
Tipo de producto: Front snap-on instantaneous bloque de contactos auxiliares
Configuración de contacto: 2NO (2 Normally Open contacts, no Normally Closed contacts)
Método de montaje: Direct snap-fit on contactor front face, tool-free installation
Applicable Contactors: LC1D09~LC1D150, CAD control relays, LC1F / CR1F series contactors
- Desglose del código del modelo
- LADN: General prefix for front-mounted auxiliary contacts of TeSys D series
- 2: Total number of contact circuits = 2
- 0: Number of NC (Normalmente cerrado) contacts = 0
Full definition: 2 Normalmente abierto, 0 Normally Closed auxiliary contacts
Universal naming rule for the same series:
LADN02: 0NO, 2CAROLINA DEL NORTE
LADN11: 1NO, 1CAROLINA DEL NORTE
LADN22: 2NO, 2CAROLINA DEL NORTE
- Terminal Markings & Wiring Definition
Two independent NO circuits with standard terminal numbers:
1st NO circuit: 53 (aporte), 54 (producción)
2nd NO circuit: 63 (aporte), 64 (producción)
Terminal structure: Screw-clamp terminals, par de apriete 1.7 Nuevo Méjico
Compatible wire cross-sections:
Single solid wire / ferrule-equipped flexible wire: 1~4 mm²
Two parallel wires: 1~2,5 mm²
- Core Electrical Specifications
4.1 Tensión nominal de aislamiento Ui
690 V (estándar IEC); UL/CSA certified for 600 V
4.2 Conventional Thermal Current Ith
10 A (ambient temperature 60°C)
4.3 AC-15 AC Control Load (Válvulas solenoides / Coils / Indicator Lamps)
120 V y: 6 A
230 V y: 3 A
400 V y: 1.8 A
690 V y: 1.04 A
4.4 DC-13 DC Inductive Load
125 En DC: 0.55 A
600 En DC: 0.1 A
4.5 Minimum Operating Condition (Suitable for Weak Signals)
Minimum switching voltage: 17 V; Minimum switching current: 5 mamá
4.6 Contact Operation Timing
No overlap time between make and break: 1.5 EM (NO and NC contacts never conduct simultaneously)
4.7 Protección & Parámetros ambientales
Clase de protección: IP20 (for indoor cabinet use only)
Temperatura de funcionamiento: -25℃ ~ +60℃
Vida mecánica: ≥ 30 millones de operaciones
Vida eléctrica (under standard load): ≥ 1 millones de operaciones
4.8 Dimensiones & Peso
Dimensiones: 48 (h) × 26 (W.) × 42 (D) milímetros; Net weight ≈ 30 gramo
- Certificaciones & Estándares
Certificaciones: CCC, CE, UL, CSA, CAO, Reino Unido
Compliant Standards: GB/T 14048.5, CEI 60947-5-1, EN 50012
- Funciones & Escenarios de aplicación
- Motor Start-Stop Feedback: Two independent passive NO signals after contactor closure, sent to PLC, indicator lamps and upper computer for operating status collection
- Expansion of Electrical Interlocks: Add interlock contacts for dual-motor and forward/reverse control circuits
- Multi-channel Alarm Output: One circuit for local panel lamps, one for remote control cabinet signals
- Expansión del circuito de control: Supplement auxiliary contacts when factory-built contacts are insufficient (LC1D standard configuration only includes 1NO+1NC)
Industrias aplicables: Máquinas herramienta, climatización, bombas de agua, fans, automatic production line control cabinets
- Selection Table for LADN Front-Mounted Contacts of the Same Series
| Modelo | Configuración de contacto | Aplicación principal |
| LADN20 | 2NO | Dual-channel operation feedback, no NC signal required |
| LADN02 | 2CAROLINA DEL NORTE | Fault shutdown and open-circuit status detection |
| LADN11 | 1NO+1NC | One operation signal + one fault signal (most universal) |
| LADN22 | 2NO+2NC | Multi-signal collection and complex interlock circuits |
- Instalación & Replacement Instructions
- Instalación: Align with the front slot of the contactor and press down until a snap sound is heard for locking; for removal, pinch both side latches and pull upward
- Installation Limit: A single LC1D contactor can be fitted with maximum 1 front LADN contact block. The LAD8N series side-mount modules are required for additional contacts
- Modelos alternativos
Domestic equivalents with identical functions: Delixi F4-20, Chint F4-20
Schneider side expansion contacts: LAD8N20 (side-mounted 2NO contacts)
- Strict Usage Prohibitions
- Not allowed for main power circuits; only applicable to control signals and small coil loads (AC-15 / DC-13)
- Forbidden to operate above the rated insulation voltage of 690 V
- Cannot be exposed outdoors or in humid unprotected environments (IP20 rating limited to cabinet interior)
- Do not connect multiple 4 mm² wires to one single terminal; maximum cross-section for parallel wiring is 2.5 mm²
Full Application Fields of Schneider LADN20 Auxiliary Contact Block
- Automatización Industrial General
- Conveying Line Equipment
Collect contactor status for belt conveyors, líneas de rodillos, transfer machines and lifting positioning mechanisms. Two NO circuits separately transmit local lamp signals and operation data to PLC.
- Custom Non-standard Automation Machines
Expand original contactor contacts on assembly machines, inspection equipment and stamping loading/unloading machines to upload equipment running status remotely.
- Robot Supporting Control Cabinets
Monitor solenoid valve circuits for robot external axes and fixture clamping; two isolated passive signals avoid mutual interference.
- Machine Tool Processing Industry (Principales escenarios de aplicación)
- CNC Lathes, Machining Centers, Milling Machines
Expand contacts for spindle motors, cooling pumps and chip conveyors. One signal feeds local panel running lamps, the other transmits ready signals to the machine tool system.
- Grinding Machines & Drill-Tap Centers
Collect start-stop status of lubrication pumps and hydraulic stations to meet the demand for synchronous multi-signal output on machine tools.
- Stamping & Sheet Metal Machines
Realize status interlock and signal upload for main hydraulic motors and feeding motors.
- climatización, Suministro de agua & Drainage, Construcción de sistemas electromecánicos.
- Admirador & Water Pump Control Boxes
For air conditioning fans, ventiladores de torre de enfriamiento, circulating pumps and sewage pumps, two NO contacts deliver local indication signals and communication data to building BA systems respectively.
- Central Air Conditioning Units
Expand contact terminals for chillers and condensate pumps for remote building monitoring.
- Fire-fighting Supporting Equipment
Upload operating status of smoke exhaust fans and sprinkler pumps to fire alarm control panels.
- Equipo de elevación, Logística & Warehousing Machinery
- Overhead Cranes & Electric Hoist Control Cabinets
Collect running signals of lifting, cross-travel and long-travel contactors. Two signal channels serve local display and upper warehouse management systems separately.
- Automated Warehouses & Stackers
Transmit status feedback of traveling motors and fork lifting motors for stacker safety interlock judgment.
- Energía, climatización & Environmental Protection Equipment
- Air Compressor & Vacuum Pump Control Cabinets
Monitor main loading motors and cooling fans; upload operation data to energy management systems for runtime statistics.
- Sewage Treatment Equipment
Multi-channel status collection for aeration fans, dosing pumps and sludge transfer pumps.
- PV Auxiliary Equipment
Output start-stop signals for cooling fans and circulating water pumps.
- Goma & Plástico, Embalaje & Industria de la impresión
- Moldeo por inyección & Extrusion Machines
Transmit operation feedback of screw motors, mold temperature machine water pumps and conveyor belts.
- Embalaje & Printing Machines
Two independent signal outputs for film feeding and winding motors to distinguish local alarm and remote monitoring signals.
- Rail Transit & EV Charging Pile Supporting Systems
- Status collection for charging pile cooling fans and main contactors
- Signal expansion for station ventilation and water pump electromechanical control cabinets
- Application Matching Features (Matching LADN20’s 2NO-only characteristic)
Universal requirement across all industries: only collect power-on running status without open-circuit fault signals; two isolated passive switching signals with separate grounding and no voltage conflict.
Select LADN11 (1NO+1NC) if both running and shutdown fault signals need to be collected simultaneously.