Contactor Schneider LC1D115M7C

3-contactor de CA de polo, rated current 115A (AC-3), 220VAC coil, 1Contactos auxiliares NA+1NC, screw terminals Order Number: LC1D11500M7C (full model), LC1D115M7C (abbreviated model) Domestic TeSys D series, eliminado gradualmente (lanzado en julio 2025). Reemplazos recomendados: LC1D115KUEC or LC1E120M5N Complete certifications: UL, CSA, CEI, CCC, CAO, etc.. Compliant with RoHS/REACh standards Model Code Explanation Segment Code Description ...

  • Detalles del producto

3-contactor de CA de polo, rated current 115A (AC-3), 220VAC coil, 1Contactos auxiliares NA+1NC, terminales de tornillo

Número de orden: LC1D11500M7C (full model), LC1D115M7C (abbreviated model)

Domestic TeSys D series, eliminado gradualmente (lanzado en julio 2025). Reemplazos recomendados: LC1D115KUEC o LC1E120M5N

Complete certifications: UL, CSA, CEI, CCC, CAO, etc.. Compliant with RoHS/REACh standards

  1. Explicación del código del modelo
SegmentoCódigoDescripción
Categoría de productoLC1Contactor series
Construction TypeDTeSys D Series (Domestic high-current type)
Corriente nominal115Rated operational current 115A (AC-3, ≤440V)
Contactos auxiliares0Configuración estándar: 1NO + 1Contactos auxiliares NC
Coil RatingMETRO220VAC coil voltage
Código de frecuencia7Universal coil for 50/60Hz
Manufacturing CodedoManufactured by SSIC (rango: 9~620A)

Modelo completo: LC1D11500M7C (official standard model), Abbreviated Model: LC1D115M7C

  1. Especificaciones principales
CategoríaDetalles
Parámetros básicos3-polo (3PAG), 3SIN contactos principales, 1Contactos auxiliares NA+1NC, screw terminal connection
Corriente nominalAC-1: 200A (≤440V, ≤60°C); AC-3: 115A (≤440V, ≤60°C)
Tensión nominalCircuito principal: ≤1000VAC; circuito de control: 220VACACIONES, 50/60Hz
Motor Control Rating30kilovatios (220~230V), 55kilovatios (380~400V), 75kilovatios (500V)
Vida mecánica10 millones de operaciones (AC-3), 10 millones de operaciones (AC-1)
Vida eléctrica1 million operations at rated current (AC-3), 1 million operations at rated current (AC-1)
Coil CharacteristicsPick-up power: 1200Virginia; Holding power: 120Virginia; Impedance: 0.6MΩ
Montaje35mm DIN rail mounting or direct panel mounting
Dimensiones & PesoAltura: 158milímetros; Ancho: 120milímetros; Profundidad: 136milímetros; Peso: aprox. 2.5kilos
Clase de protecciónIP20 (per IEC 60529)
CertificacionesUL, CSA, CEI, CCC, CAO, Marina, RINA, DNV, etc..
  1. Full Model List (LC1D Series 115A)
ModeloVoltaje de la bobinaTipo de terminalObservaciones
LC1D11500M7C220VACACIONESTornilloTipo estándar (original model)
LC1D11500P7C380VACACIONESTornilloCommon alternative voltage
LC1D11500F7C110VACACIONESTornilloLow voltage control
LC1D11500B7C24VACACIONESTornilloSafety extra-low voltage control
LC1D115006M7C220VACACIONESRing terminalFor special wiring requirements
LC1D115KUEC100~250VAC/DCTornilloUniversal voltage, replacement model
LC1D115ABD24VCCTornilloDC coil version
LC1D115ALBD24VCCTornilloLow-power DC coil

 

  1. Cross & Replacement Model List

4.1 Schneider Original Replacements

Modelo OriginalModelo de reemplazoReason for ReplacementCompatibilidad
LC1D115M7CLC1D115KUECUniversal voltage coil (100~250VAC/DC), higher flexibilityTotalmente compatible, identical mounting dimensions
LC1D115M7CLC1E120M5NUpgraded TeSys E Series with improved performanceIdentical mounting dimensions; verify auxiliary contact configuration
LC1D115M7CLC1D11500M7CFull official model, identical to abbreviated version100% compatible

4.2 Reemplazos entre marcas

MarcaModelo de reemplazoPrincipales diferenciasAplicabilidad
TEJIDOA145-30-11Rated current 145A with larger marginDifferent mounting dimensions; layout adjustment required
siemens3RT2036-1BB40125A, AC-3, 220V coilSame auxiliary contact layout, reemplazo directo
Interruptor ChangshuCJX2-1210Alternativa doméstica, rentableSlightly lower performance, for general working conditions
chintNC1-1210Alternativa doméstica, rendimiento de alto costoMeets basic requirements, shorter service life
  1. Solicitud & Casos de la industria

5.1 Escenarios aplicables

Control de motores: Comenzar, stop and reverse control for 30~75kW three-phase squirrel-cage motors

Automatización Industrial: Control circuits for production lines, transportadores, compressors and pumps

Distribución de energía: Switching control for non-inductive or weakly inductive loads such as resistance furnaces and heaters (AC-1)

Sistemas HVAC: Control of large air conditioning compressors and ventilation fans

Marina & Ingeniería costa afuera: Certified by marine classification societies for offshore equipment

5.2 Non-Recommended Scenarios

High-Frequency Operation: Más que 120 starts/stops per minute (use LC1D170 series or dedicated contactors)

Harsh Environments: Heavy dust, corrosive gas or severe vibration (additional protection required)

DC Loads: Use dedicated DC contactors (p.ej. LC1D115ABD)

High Altitude: Derating required above 2000m (10% derating per additional 1000m)

5.3 Casos de aplicación típicos

Caso 1: Fan Control in Steel Plant

Operating conditions: 380V, 55kW fan, AC-3, 10 starts per day, 20-hour continuous operation

Solución: LC1D115M7C + LRD3365 thermal overload relay

Ventajas: 3 years of stable operation without failure, bajo costo de mantenimiento

Caso 2: HVAC System in Pharmaceutical Factory

Operating conditions: 400V, 45kW compressor, AC-3, 24-hour continuous operation and frequent cycling

Solución: LC1D115M7C + control PLC + supresor de sobretensiones

Ventajas: Low noise and power consumption, compliant with GMP standards

  1. Solución de problemas & Maintenance Manual

6.1 Diagnóstico de fallas comunes

Fenómeno de fallaPosibles causasSoluciones
El contactor no cierra1. No voltage on coil; 2. bobina quemada; 3. Atasco mecánico1. Measure voltage across terminal A1/A2; 2. Comprobar la resistencia de la bobina (normal: aprox. 320Oh); 3. Apagar, inspect mechanism and remove foreign objects
Loud noise after closing1. Subtensión; 2. Oil contamination on core contact surface; 3. Anillo de sombreado roto1. Ensure voltage within ±10% of rated value; 2. Limpiar la superficie del núcleo; 3. Replace coil assembly
Overheated / burnt main contacts1. Sobrecarga actual; 2. mal contacto; 3. Failed arc suppression1. Check for load overload; 2. Clean or replace contacts; 3. Inspect arc chute integrity
Auxiliary contact malfunction1. Oxidación por contacto; 2. Cableado suelto; 3. Desgaste mecánico1. Contactos limpios; 2. Reapretar terminales; 3. Replace auxiliary contact block
Repeated coil burnout1. Severe voltage fluctuation; 2. Frequent cycling; 3. Excess ambient temperature1. Install voltage stabilizer; 2. Replace with high-cycle model; 3. Mejorar la disipación del calor.

6.2 Programa de mantenimiento & Procedures

Artículo de mantenimientoIntervaloOperación
Inspección visualMensualCheck for overheating marks, abnormal odors and loose parts
Inspección de contactoTrimestralMeasure contact resistance (<50m惟), check for ablation
Inspección de bobinasSemi-annuallyMeasure coil resistance and insulation performance
Mechanical LubricationAnnuallyLightly lubricate moving parts (silicone grease recommended)
OverhaulCada 2 añosDisassemble for full inspection, replace worn parts and clean interior
  1. Phase-Out & Migration Guide

7.1 Phase-Out Information

Phase-out Plan: Schneider launched the phase-out of domestic high-current TeSys D series (115-170A) in July 2025

Transition Period: July 2025 – December 2026. Production will cease after the period

Inventory: Stock is still available via some distributors. Procurement or model replacement is recommended as soon as possible.

7.2 Migration Solutions

Migration TypeModelo recomendadoVentajasNotas
In-Series UpgradeLC1D115KUECUniversal voltage coil for wider applicationIdentical mounting size, no cabinet modification needed
Cross-Series UpgradeLC1E120M5NTeSys E Series with enhanced performance and longer service lifeAuxiliary contact layout may differ; verify control circuit
Cost-Saving ReplacementChangshu CJX2-1210 / Chint NC1-121030-50% reducción de costosSlight performance difference; for non-critical applications

7.3 Migration Steps

  1. Confirm voltage and current requirements of the original control circuit
  2. Select suitable replacement model (LC1D115KUEC recommended)
  3. Verify compatibility of mounting dimensions and fixtures
  4. Confirm quantity and type of auxiliary contacts
  5. Replace contactor and conduct commissioning test
  6. Keep spare parts of the original model until the end of transition period
  7. Directrices de selección

Reglas de referencia rápida

  1. LC1D: Schneider TeSys D series contactor
  2. 115: 115Una corriente nominal (AC-3), matches 55kW motor at 400V
  3. M7C: 220VAC 50/60Hz coil, manufactured by SSIC
  4. 00: Standard 1NO+1NC auxiliary contacts
  5. Phase-out Notice: Prioritize LC1D115KUEC for replacement since July 2025
  6. Cumplimiento del transporte aéreo & Certificaciones

Clasificación de transporte: Mercancías no peligrosas. Sin batería de litio incorporada / supercondensador, compliant with IATA regulations

Certificación CE: Cumple con EN 60947-4-1, CE marked

Environmental Certification: Compliant with RoHS/REACh directives, Green Premium product

Embalaje: Individual packaging to prevent damage during transit. Original packaging is recommended.